Fan Performance — 48PGE06 Vertical Units
AIRFLOW
(Cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
1500
607
0.29
700
0.38
784
0.47
861
0.57
934
0.68
1600
634
0.33
724
0.43
804
0.53
879
0.64
950
0.75
1700
662
0.39
748
0.49
826
0.60
898
0.71
967
0.82
1800
690
0.45
773
0.55
848
0.67
918
0.78
985
0.90
1900
719
0.51
799
0.63
872
0.74
940
0.86
1004
0.98
2000
748
0.59
825
0.70
896
0.83
962
0.95
1024
1.08
2100
777
0.67
852
0.79
920
0.92
985
1.05
1045
1.18
2200
807
0.75
879
0.88
946
1.01
1008
1.15
1067
1.29
2300
837
0.85
907
0.98
971
1.12
1032
1.26
1090
1.40
2400
867
0.95
935
1.09
998
1.24
1057
1.38
1113
1.53
2500
897
1.06
963
1.21
1024
1.36
1082
1.51
1137
1.66
AIRFLOW
(Cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.2
1.4
1.6
1.8
2.0
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
1500
1004
0.79
1070
0.91
1133
1.03
1194
1.15
1253
1.28
1600
1017
0.86
1081
0.98
1143
1.11
1203
1.24
1260
1.37
1700
1032
0.94
1094
1.06
1155
1.19
1213
1.32
1269
1.46
1800
1048
1.02
1109
1.15
1168
1.28
1224
1.42
1279
1.56
1900
1066
1.11
1125
1.24
1182
1.38
1237
1.52
1291
1.66
2000
1084
1.21
1142
1.35
1197
1.49
1251
1.63
1304
1.78
2100
1104
1.31
1160
1.45
1214
1.60
1267
1.75
1318
1.90
2200
1124
1.43
1179
1.57
1231
1.72
1283
1.87
1333
2.03
2300
1145
1.55
1198
1.70
1250
1.85
1300
2.01
1349
2.17
2400
1167
1.68
1219
1.83
1269
1.99
1318
2.15
1366
2.31
2500
1189
1.82
1240
1.97
1290
2.14
1337
2.30
—
—
LEGEND
Bhp ---
Brake Horsepower
NOTES:
1. Motor drive range is 690 to 978 rpm for low range motor/drive and 929 to 1261 rpm
for high range motor/drive. All other rpms require a field-supplied drive.
2. Maximum continuous bhp is 0.85 (single phase) and 2.40 (3 phase) for low range
motor/drive and 1.60 (single phase) and 2.40 (3 phase) for high range motor/drive.
3. See General Fan Performance Notes.
Fan Performance -- 48PGF06 Vertical Units
AIRFLOW
(Cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
1500
620
0.30
711
0.39
794
0.49
871
0.59
944
0.70
1600
648
0.35
736
0.45
816
0.55
890
0.65
960
0.76
1700
677
0.40
762
0.51
838
0.61
910
0.72
978
0.84
1800
707
0.47
788
0.58
862
0.69
931
0.80
997
0.92
1900
737
0.54
815
0.65
887
0.77
954
0.89
1017
1.01
2000
767
0.61
843
0.73
912
0.85
977
0.98
1039
1.11
2100
798
0.70
871
0.82
938
0.95
1001
1.08
1061
1.21
2200
829
0.79
900
0.92
965
1.05
1026
1.19
1084
1.33
2300
861
0.89
929
1.03
992
1.17
1052
1.31
1108
1.45
2400
893
1.00
959
1.15
1020
1.29
1078
1.43
1133
1.58
2500
925
1.12
989
1.27
1048
1.42
1105
1.57
1158
1.72
AIRFLOW
(CFM)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.2
1.4
1.6
1.8
2.0
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
1500
1013
0.81
1078
0.92
1141
1.05
1202
1.17
1260
1.30
1600
1027
0.88
1091
1.00
1152
1.13
1211
1.25
1269
1.39
1700
1043
0.96
1105
1.08
1165
1.21
1222
1.35
1278
1.48
1800
1060
1.05
1120
1.18
1179
1.31
1235
1.44
1290
1.59
1900
1078
1.14
1137
1.27
1194
1.41
1249
1.55
1302
1.70
2000
1098
1.24
1155
1.38
1210
1.52
1264
1.67
1316
1.81
2100
1119
1.35
1174
1.49
1228
1.64
1280
1.79
1331
1.94
2200
1140
1.47
1195
1.62
1247
1.77
1298
1.92
1348
2.08
2300
1163
1.60
1216
1.75
1267
1.90
1317
2.06
1365
2.22
2400
1186
1.73
1238
1.89
1288
2.05
1336
2.21
1384
2.37
2500
1210
1.88
1261
2.04
1309
2.20
1357
2.37
—
—
LEGEND
Bhp ---
Brake Horsepower
NOTES:
1. Motor drive range is 690 to 978 rpm for low range motor/drive and 929 to 1261 rpm
for high range motor/drive. All other rpms require a field-supplied drive.
2. Maximum continuous bhp is 0.85 (single phase) and 2.40 (3 phase) for low range
motor/drive and 1.60 (single phase) and 2.40 (3 phase) for high range motor/drive.
3. See General Fan Performance Notes.
48/
50P
G
and
P
M
Summary of Contents for 48/50PG Series
Page 32: ...32 C07009 Fig 20 Air Baffle Dimensions 48 50PG03 16 48 50PG and PM...
Page 33: ...33 C08077 Fig 21 Air Baffle Dimensions 48 50PG20 28 and 48 50PM16 28 48 50PG and PM...
Page 58: ...58 C08549 Fig 28 48PG03 16 Control Wiring Schematic 48 50PG and PM...
Page 59: ...59 C08550 Fig 29 50PG03 16 Control Wiring Schematic 48 50PG and PM...
Page 64: ...64 C08471 Fig 34 Typical 48PG and PM16 28 Control Schematic 48PM16 28 Shown 48 50PG and PM...
Page 66: ...66 C08557 Fig 36 Typical 50PG and PM16 28 Control Schematic 50PG20 28 Shown 48 50PG and PM...
Page 68: ...68 C08558 Fig 38 Typical 48 50PG and PM16 28 Power Schematic 48 50PM16 28 Shown 48 50PG and PM...
Page 72: ...72 C08565 Fig 42 Typical 48 50PG20 28 Component Arrangement 48 50PG20 24 Shown 48 50PG and PM...
Page 73: ...73 C08067 Fig 43 48 50PM16 28 Component Arrangement 48 50PG and PM...
Page 74: ...74 C08562 Fig 44 48 50PM16 28 with Humidi MiZert Component Arrangement 48 50PG and PM...
Page 208: ...208 48 50PG and PM...