Reheat2 ODF Fan On Temp (RF.ON)
This sets the Reheat2 mode change temperature to increased
outdoor fan level.
Reheat2 ODF Fan Off Temp (RF.OF)
This sets the Reheat2 mode change temperature to decrease
outdoor fan level.
Table 10 – Control Modes with Humidi--MiZer
t
System
Output and Valve States versus Circuit Mode .x = Circuit A, B, or C identifier
DEMAND AND MODE
OUTPUTS
48/50PG03---16 VALVES
48/50PG20---28
48/50PM16---28
VALVES
Space
Humidity
Circuit
Cooling
Demand
Circuit
Mode
Indoor
Fan (IDF)
Circuit
Compressor
(CMP.x)
Cooling---
Reheat
Control
(CRC)*
Reheat2
Valve
(RH2.x)
CV.x
Valve
2---way
RH1.x
Valve
2---way
RH2.x
Valve
2---way
RH1.x
Valve
3---way
RH2.x
Valve
2---way
—
—
No
power
OFF
Off
Off
Off
Off
(open)
Off
(open)
Off
(closed)
Off
Off
(closed)
Low
No
Off
Per
Ventilation
Control
Off
Off
Off
Off
(open)
On
(closed)
Off
(closed)
Off
Off
(closed)
Low
Yes
Cool
On
On
Off
Off
Off
(open)
On
(closed)
Off
(closed)
Off
Off
(closed)
High
Yes
Reheat1
On
On
On
Off
On
(closed)
Off
(open)
Off
(closed)
On
Off
(closed)
High
No
Reheat2
On
On
On
On
On
(closed)
Off
(open)
On
(open)
On
On
(open)
COMP
COND COIL
HUMIDI-MIZER COIL
EVAP COIL
INDOOR ENTERING
AIR
OUTDOOR AIR
METERING
DEVICE
CLOSED VALVE
OPEN VALVE
3-WAY VALVE
RH1.x
RH2.x
CV.x
C07003
Fig. 9 -- Normal Cooling Mode — Humidi--MiZer
t
System
48/50PG03--16
48/
50P
G
and
P
M
Summary of Contents for 48/50PG Series
Page 32: ...32 C07009 Fig 20 Air Baffle Dimensions 48 50PG03 16 48 50PG and PM...
Page 33: ...33 C08077 Fig 21 Air Baffle Dimensions 48 50PG20 28 and 48 50PM16 28 48 50PG and PM...
Page 58: ...58 C08549 Fig 28 48PG03 16 Control Wiring Schematic 48 50PG and PM...
Page 59: ...59 C08550 Fig 29 50PG03 16 Control Wiring Schematic 48 50PG and PM...
Page 64: ...64 C08471 Fig 34 Typical 48PG and PM16 28 Control Schematic 48PM16 28 Shown 48 50PG and PM...
Page 66: ...66 C08557 Fig 36 Typical 50PG and PM16 28 Control Schematic 50PG20 28 Shown 48 50PG and PM...
Page 68: ...68 C08558 Fig 38 Typical 48 50PG and PM16 28 Power Schematic 48 50PM16 28 Shown 48 50PG and PM...
Page 72: ...72 C08565 Fig 42 Typical 48 50PG20 28 Component Arrangement 48 50PG20 24 Shown 48 50PG and PM...
Page 73: ...73 C08067 Fig 43 48 50PM16 28 Component Arrangement 48 50PG and PM...
Page 74: ...74 C08562 Fig 44 48 50PM16 28 with Humidi MiZert Component Arrangement 48 50PG and PM...
Page 208: ...208 48 50PG and PM...