![Carrier 48/50PG Series Controls, Start-Up, Operation, Service And Troubleshooting Instructions Download Page 79](http://html1.mh-extra.com/html/carrier/48-50pg-series/48-50pg-series_controls-start-up-operation-service-and-troubleshooting-instructions_2560926079.webp)
79
Integrated Gas Control (IGC) Board
The IGC is provided on gas heat units. (See Fig. 47 and Table 25.)
The IGC controls the direct spark ignition system and monitors the
rollout switch, limit switch, and induced-draft motor Hall Effect
switch.
The IGC is equipped with an LED (light-emitting diode) for
diagnostics. See the Troubleshooting section for more information.
RED LED-STATUS
C07028
Fig. 47 -- Integrated Gas Control (IGC) Board
Table 25 – IGC Connections
TERMINAL
LABEL
POINT DESCRIPTION
SENSOR LOCATION
TYPE OF I/O
CONNECTION
PIN NUMBER
INPUTS
RT, C
Input power from TRAN 1
control box
24 VAC
SS
Speed sensor
gas section
analog input
J1, 1---3
FS, T1
Flame sensor
gas section
switch input
W
Heat stage 1
MBB
24 VAC
J2, 2
RS
Rollout switch
gas section
switch input
J2, 5---6
LS
Limit switch
gas section
switch input
J2, 7---8
CS
Centrifugal switch (not used)
switch input
J2, 9---10
OUTPUTS
L1, CM
Induced draft combustion motor
gas section
line VAC
IFO
Indoor fan request
control box
relay
J2, 1
GV (W1)
Gas valve (heat stage 1)
gas section
relay
J2, 12
GV (W2)
Gas Valve (heat stage 2, from MBB)
gas section
Not on IGC
48/
50P
G
and
P
M
Summary of Contents for 48/50PG Series
Page 32: ...32 C07009 Fig 20 Air Baffle Dimensions 48 50PG03 16 48 50PG and PM...
Page 33: ...33 C08077 Fig 21 Air Baffle Dimensions 48 50PG20 28 and 48 50PM16 28 48 50PG and PM...
Page 58: ...58 C08549 Fig 28 48PG03 16 Control Wiring Schematic 48 50PG and PM...
Page 59: ...59 C08550 Fig 29 50PG03 16 Control Wiring Schematic 48 50PG and PM...
Page 64: ...64 C08471 Fig 34 Typical 48PG and PM16 28 Control Schematic 48PM16 28 Shown 48 50PG and PM...
Page 66: ...66 C08557 Fig 36 Typical 50PG and PM16 28 Control Schematic 50PG20 28 Shown 48 50PG and PM...
Page 68: ...68 C08558 Fig 38 Typical 48 50PG and PM16 28 Power Schematic 48 50PM16 28 Shown 48 50PG and PM...
Page 72: ...72 C08565 Fig 42 Typical 48 50PG20 28 Component Arrangement 48 50PG20 24 Shown 48 50PG and PM...
Page 73: ...73 C08067 Fig 43 48 50PM16 28 Component Arrangement 48 50PG and PM...
Page 74: ...74 C08562 Fig 44 48 50PM16 28 with Humidi MiZert Component Arrangement 48 50PG and PM...
Page 208: ...208 48 50PG and PM...