Accessory/FIOP Static Pressure Drops (in. wg)* -- 48/50PM16--28
CFM
Economizer
Humidi---MiZer™ (16, 20, 24)
Humidi---MiZer™ (28)
4000
0.02
0.17
---
4500
0.03
0.19
---
5000
0.04
0.21
---
5500
0.05
0.24
---
6000
0.06
0.27
---
6500
0.07
0.31
0.19
7000
0.08
0.35
0.21
7500
0.09
0.39
0.23
8000
0.1
0.43
0.26
8500
0.11
0.48
0.29
9000
0.12
0.52
0.31
9500
0.13
0.57
0.34
10000
0.15
0.62
0.37
10500
0.16
---
0.4
11000
0.17
---
0.43
11500
0.19
---
0.46
12000
0.2
---
0.5
LEGEND
FIOP
--- Factory---Installed Option
* The static pressure must be added to the external static pressure. The sum and the evaporator entering---air cfm should then be used in conjunction with the
Fan Performance tables to determine blower rpm and watts.
Accessory/FIOP Electric Heat Static Pressure Drop (in. wg) -- 50PM16--28 and 50PG20--28
CFM
Nominal Heater
Size (kw)
Pressure Drop (in.
wg)
Nominal Heater
Size (kw)
Pressure Drop (in.
wg)
Nominal Heater
Size (kw)
Pressure Drop (in.
wg)
4800
25
0.01
50
0.02
75
0.03
5000
0.01
0.02
0.04
6000
0.02
0.04
0.06
7000
0.03
0.06
0.08
8000
0.04
0.08
0.12
9000
0.05
0.1
0.15
10000
0.06
0.13
0.2
11500
0.09
0.18
0.27
LEGEND
FIOP
--- Factory---Installed Option
NOTES:
1. Heaters are rated at 240v, 480v, and 600v.
2. The static pressure must be added to the external static pressure. The
sum and the evaporator entering---air cfm should then be used in
conjunction with the Fan Performance tables to determine blower rpm, bhp,
and watts.
Copyright 2009 Carrier Corp.
S
7310 W. Morris St.
S
Indianapolis, IN 46231
Printed in U.S.A.
Edition Date: 7/09
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Catalog No:48---50PGPM---02T
Replaces: 48--- 50PGPM--- 01T
48/
50P
G
and
P
M
Summary of Contents for 48/50PG Series
Page 32: ...32 C07009 Fig 20 Air Baffle Dimensions 48 50PG03 16 48 50PG and PM...
Page 33: ...33 C08077 Fig 21 Air Baffle Dimensions 48 50PG20 28 and 48 50PM16 28 48 50PG and PM...
Page 58: ...58 C08549 Fig 28 48PG03 16 Control Wiring Schematic 48 50PG and PM...
Page 59: ...59 C08550 Fig 29 50PG03 16 Control Wiring Schematic 48 50PG and PM...
Page 64: ...64 C08471 Fig 34 Typical 48PG and PM16 28 Control Schematic 48PM16 28 Shown 48 50PG and PM...
Page 66: ...66 C08557 Fig 36 Typical 50PG and PM16 28 Control Schematic 50PG20 28 Shown 48 50PG and PM...
Page 68: ...68 C08558 Fig 38 Typical 48 50PG and PM16 28 Power Schematic 48 50PM16 28 Shown 48 50PG and PM...
Page 72: ...72 C08565 Fig 42 Typical 48 50PG20 28 Component Arrangement 48 50PG20 24 Shown 48 50PG and PM...
Page 73: ...73 C08067 Fig 43 48 50PM16 28 Component Arrangement 48 50PG and PM...
Page 74: ...74 C08562 Fig 44 48 50PM16 28 with Humidi MiZert Component Arrangement 48 50PG and PM...
Page 208: ...208 48 50PG and PM...