![Carrier 48/50PG Series Controls, Start-Up, Operation, Service And Troubleshooting Instructions Download Page 183](http://html1.mh-extra.com/html/carrier/48-50pg-series/48-50pg-series_controls-start-up-operation-service-and-troubleshooting-instructions_2560926183.webp)
183
Fan Performance — 50PM and PG24 — Horizontal Supply/Return Units
Airflow
(Cfm)
Available External Static Pressure (in. wg)
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
5500
619
1.71
682
1.96
737
2.21
788
2.45
837
2.71
6000
663
2.09
723
2.35
776
2.62
825
2.88
E
871
3.14
6500
708
2.53
E
765
2.80
E
816
3.08
E
863
3.35
906
3.63
7000
E
753
3.02
807
3.30
857
3.59
902
3.88
944
4.17
7500
800
3.58
850
3.86
898
4.16
942
4.47
982
4.77
8000
847
4.20
894
4.48
940
4.80
F
982
5.11
F
1022
5.43
8500
894
4.88
939
5.17
F
982
5.49
1024
5.82
1062
6.14
9000
941
5.63
983
5.92
1025
6.24
1065
6.58
G
1103
6.92
9500
G
989
6.45
G
1029
6.74
G
1069
7.07
G
1108
7.41
1144
7.77
10000
1037
7.34
1075
7.63
1113
7.96
1150
8.32
H
1186
8.68
Airflow
(Cfm)
Available External Static Pressure (in. wg)
1.2
1.4
1.6
1.8
2.0
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
5500
886
2.97
E
935
3.25
985
3.55
1035
3.87
1086
4.21
6000
E
916
3.41
960
3.69
1005
3.98
1050
4.29
1096
4.61
6500
949
3.90
990
4.19
F
1032
4.48
F
1073
4.78
F
1114
5.10
7000
984
4.46
F
1023
4.75
1062
5.04
1100
5.34
1139
5.66
7500
F
1021
5.07
1059
5.37
1095
5.67
1131
5.98
G
1167
6.29
8000
1059
5.74
1095
6.05
1130
6.36
G
1165
6.67
1199
6.99
8500
1099
6.47
G
1133
6.79
G
1167
7.11
1200
7.43
H
1232
7.76
9000
G
1138
7.26
1172
7.59
1205
7.93
H
1237
8.26
1268
8.59
9500
1179
8.12
1212
8.46
H
1244
8.81
1275
9.15
1305
9.50
10000
H
1220
9.04
H
1252
9.40
1283
9.76
1313
10.11
1342
10.47
LEGEND
Bhp
--- Brake Horsepower Input to Fan
Boldface
indicates field--- supplied drive required.
NOTES
:
1. Motor drive ranges:
(E)
Low Range: 685--- 939 rpm, 4.26 Bhp (208/230 and 460--- v), 751--- 954, 575 Bhp
(575--- v)
(F)
Mid-Low Range: 949 to 1206 rpm, 5.75 Bhp
(G)
Mid-High Range: 941 to 1176 rpm, 8.63 Bhp
(H)
High Range: 1014 to 1297 rpm, 11.50 Bhp
All other rpms require field--- supplied drive.
2. See General Fan Performance Notes.
48/
50P
G
and
P
M
Summary of Contents for 48/50PG Series
Page 32: ...32 C07009 Fig 20 Air Baffle Dimensions 48 50PG03 16 48 50PG and PM...
Page 33: ...33 C08077 Fig 21 Air Baffle Dimensions 48 50PG20 28 and 48 50PM16 28 48 50PG and PM...
Page 58: ...58 C08549 Fig 28 48PG03 16 Control Wiring Schematic 48 50PG and PM...
Page 59: ...59 C08550 Fig 29 50PG03 16 Control Wiring Schematic 48 50PG and PM...
Page 64: ...64 C08471 Fig 34 Typical 48PG and PM16 28 Control Schematic 48PM16 28 Shown 48 50PG and PM...
Page 66: ...66 C08557 Fig 36 Typical 50PG and PM16 28 Control Schematic 50PG20 28 Shown 48 50PG and PM...
Page 68: ...68 C08558 Fig 38 Typical 48 50PG and PM16 28 Power Schematic 48 50PM16 28 Shown 48 50PG and PM...
Page 72: ...72 C08565 Fig 42 Typical 48 50PG20 28 Component Arrangement 48 50PG20 24 Shown 48 50PG and PM...
Page 73: ...73 C08067 Fig 43 48 50PM16 28 Component Arrangement 48 50PG and PM...
Page 74: ...74 C08562 Fig 44 48 50PM16 28 with Humidi MiZert Component Arrangement 48 50PG and PM...
Page 208: ...208 48 50PG and PM...