Table 24 – ECB Connections
DISPLAY
NAME
POINT DESCRIPTION
SENSOR
LOCATION
TYPE OF I/O
CONNECTION
PIN NUMBER
INPUTS
Input power from MBB
control box
24 VAC
J1, 1---2
RM.OC
Remote occupancy switch
field installed
switch input
J4, 2
ENTH or
IAQ.S
Outdoor enthalpy switch, or
Indoor air quality switch
economizer, or
return/space
switch input
J4, 4
IAQ
Indoor air quality sensor
return/space
0---20 mA
J5, 2
OAQ or
SP.RH
Outdoor air quality sensor, or
Relative humidity sensor
field installed
0---20 mA
J5, 5
Sensor Common
Ground
J5, 3
Actuator Common
Ground
J7, 3
OUTPUTS
Output power to enthalpy switch
24 VAC
J4, 3
Output power for loop power sensors
24 VDC
J5, 1
Output power to economizer actuator
24 VAC
J7, 2
PE.1
Power exhaust 1 relay
relay
J8, 3
PE.2
Power exhaust 2 relay
relay
J8, 6
EC.CP or
F.SPD
Commanded Economizer position or
Commanded Fan Speed
0---20 mA
J9, 1
COMMUNICATION
Local Equipment Network (LEN)
communication
J2, 1---3
Carrier Comfort Network (CCN)
communication
J3
EC.CP &
EC.AP
Economizer actuator position
(digital control)
MFT
communication
J7, 1
48/
50P
G
and
P
M
Summary of Contents for 48/50PG Series
Page 32: ...32 C07009 Fig 20 Air Baffle Dimensions 48 50PG03 16 48 50PG and PM...
Page 33: ...33 C08077 Fig 21 Air Baffle Dimensions 48 50PG20 28 and 48 50PM16 28 48 50PG and PM...
Page 58: ...58 C08549 Fig 28 48PG03 16 Control Wiring Schematic 48 50PG and PM...
Page 59: ...59 C08550 Fig 29 50PG03 16 Control Wiring Schematic 48 50PG and PM...
Page 64: ...64 C08471 Fig 34 Typical 48PG and PM16 28 Control Schematic 48PM16 28 Shown 48 50PG and PM...
Page 66: ...66 C08557 Fig 36 Typical 50PG and PM16 28 Control Schematic 50PG20 28 Shown 48 50PG and PM...
Page 68: ...68 C08558 Fig 38 Typical 48 50PG and PM16 28 Power Schematic 48 50PM16 28 Shown 48 50PG and PM...
Page 72: ...72 C08565 Fig 42 Typical 48 50PG20 28 Component Arrangement 48 50PG20 24 Shown 48 50PG and PM...
Page 73: ...73 C08067 Fig 43 48 50PM16 28 Component Arrangement 48 50PG and PM...
Page 74: ...74 C08562 Fig 44 48 50PM16 28 with Humidi MiZert Component Arrangement 48 50PG and PM...
Page 208: ...208 48 50PG and PM...