MODE — CONFIGURATION (cont)
ITEM
EXPANSION
RANGE
UNITS
DEFAULT
CCN TABLE/
SUB---TABLE
CCN POINT
ENTRY
COOL (cont)
Cooling Configuration
COOL_CFG
OFC
Outdoor Fan Control
OFC.3
OFC3 Enable. CCH Dis-
able
Yes/No
No (PG03--- 16)
Yes (20--- 28, PM16)
OFC3_CTL
0.MXP
Fan Lev0 Max Pressure
100 to 500
psig
200
LEV0MAXP
1.MXP
Fan Lev1 Max Pressure
100 to 500
psig
400 (PG03--- 16)
450 (20--- 28, PM16)
LEV1MAXP
2.MNP
Fan Lev2 Min Pressure
100 to 500
psig
150 (PG03--- 16)
200 (20--- 28, PM16)
LEV2MINP
2.ON
Fan Lev2 On Temperature
0 to 100
F
no Humidi--- MiZer FIOP:
55 (03--- 20)
45 (24--- 28)
Humidi--- MiZer FIOP:
68 (20, PM16)
61 (24--- 28, PG03--- 16)
LEV2ON
2.OFF
Fan Lev2 Off Temperature
0 to 100
F
no Humidi--- MiZer FIOP:
45 (PG03--- 16)
50 (20, PM16)
40 (24--- 28)
Humidi--- MiZer FIOP:
57
LEV2OFF
2.MXP
Fan Lev2 Max Pressure
100 to 500
psig
400
LEV2MAXP
3.MNP
Fan Lev3 Min Pressure
100 to 500
psig
250
LEV3MINP
3.ON
Fan Lev3 On Temperature
0 to 100
F
no Humidi--- MiZer FIOP:
65
Humidi--- MiZer FIOP:
88 (20, PM16)
68 (24--- 28, PG03--- 16)
LEV3ON
3.OFF
Fan Lev3 Off Temperature
0 to 100
F
no Humidi--- MiZer FIOP:
55
Humidi--- MiZer FIOP:
78 (20, PM16)
62 (24--- 28, PG03--- 16)
LEV3OFF
HMZR
Humidimizer Config
HMZR_CFG
REHT
Humidimizer Equipped
Yes/No
No: no Humidi--- MiZer
FIOP
Yes: Humidi--- MiZer FIOP
REHEAT
R.DEC
Reheat2 Stage Decr.
Time
0 to 999
secs
60
RSTAGDEC
R.INC
Reheat2 Stage Incr. Time
0 to 999
secs
300
RSTAGINC
RH.FN
Reheat Fan Control
Yes/No
No (03--- 14)
Yes (16--- 28)
RHFANCTL
RF.LV
Reheat2 ODF Fan On
Level
0 to 3
2
RHFANLEV
RF. ON
Reheat2 ODF Fan On
Temp
0 to 100
F
75 (PG03--- 16)
93 (PG20--- 24,PM 16--- 28)
85 (PG 28)
RHFANON
RF.OF
Reheat2 ODF Fan Off
Temp
0 to 100
F
70 (PG03--- 16)
83 (20, PM16)
88 (24)(PM 28)
80 (PG 28)
RHFANOFF
RA.LO
Reheat2 OAT Limit A
2
0 to 70
F
40
OATLRH_A
RA.LP
Reheat2 SSP Lo Limit A
5
0 to 100
psig
80
RHSSPL_A
RA.HP
Reheat2 SSP Hi Limit A
5
0 to 100
psig
90
RHSSPH_A
RB.LO
Reheat2 OAT Limit B,C
2
0 to 70
F
50
OATLRH_B
RB.LP
Reheat2 SSP Lo Limit
B,C
5
0 to 100
psig
80
RHSSPL_B
RB.HP
Reheat2 SSP Hi Limit B,C
5
0 to 100
psig
90
RHSSPH_B
48/
50P
G
and
P
M
Summary of Contents for 48/50PG Series
Page 32: ...32 C07009 Fig 20 Air Baffle Dimensions 48 50PG03 16 48 50PG and PM...
Page 33: ...33 C08077 Fig 21 Air Baffle Dimensions 48 50PG20 28 and 48 50PM16 28 48 50PG and PM...
Page 58: ...58 C08549 Fig 28 48PG03 16 Control Wiring Schematic 48 50PG and PM...
Page 59: ...59 C08550 Fig 29 50PG03 16 Control Wiring Schematic 48 50PG and PM...
Page 64: ...64 C08471 Fig 34 Typical 48PG and PM16 28 Control Schematic 48PM16 28 Shown 48 50PG and PM...
Page 66: ...66 C08557 Fig 36 Typical 50PG and PM16 28 Control Schematic 50PG20 28 Shown 48 50PG and PM...
Page 68: ...68 C08558 Fig 38 Typical 48 50PG and PM16 28 Power Schematic 48 50PM16 28 Shown 48 50PG and PM...
Page 72: ...72 C08565 Fig 42 Typical 48 50PG20 28 Component Arrangement 48 50PG20 24 Shown 48 50PG and PM...
Page 73: ...73 C08067 Fig 43 48 50PM16 28 Component Arrangement 48 50PG and PM...
Page 74: ...74 C08562 Fig 44 48 50PM16 28 with Humidi MiZert Component Arrangement 48 50PG and PM...
Page 208: ...208 48 50PG and PM...