background image

30

FAN OUTPUT — During occupied periods, the fan operation

is determined by the Occupied Fan Operation configuration de-

cision. If this decision is set to continuous (1), the fan will oper-

ate continuously during the occupied periods and during heat-

ing, cooling, and dehumidification during unoccupied periods.

If it is set to automatic (0), the fan will only operate only if

heating, cooling or dehumidification is required (and heating or

cooling is available in a 2-pipe changeover system). The Fan

Output point displays the status of the fan.

During unoccupied periods, the fan will only operate if at

least one of the following conditions is true:
• the Space Temperature exceeds the Cooling Set Point

and Cooling is available

• Space Temperature falls below the Heating Set Point and

Heating is available

• Space Humidity exceeds the Unoccupied High Humidity

limit and the Space Temperature is above the Heating set

point

• Space Humidity exceeds the Unoccupied High Humidity

limit, the Space Temperature is below the Heating set

point, the Heat Type is not None, and the unit is not con-

figured for 2-pipe Changeover (0)

• the control is configured for Unoccupied Fan Cycling

and the current minute is equal to the calculated

1-minute time interval.

The fan stops at the end of the occupied time if the above

conditions are satisfied. A 5-minute fan off delay will continue

to provide fan operation after a cooling cycle is completed and

under conditions where the fan would otherwise stop. This

function improves IAQ by evaporating residual coil moisture

(condensate) which contributes to bacteria growth.

The fan coil controller Unoccupied Fan Cycling option,

when enabled, causes the fan to run for one minute each hour

during unoccupied times. The exact time of operation is deter-

mined by the CCN address. The purpose of this mode is to pre-

vent air stagnation from causing the unit to operate or not oper-

ate based upon improperly sensing the space temperature

conditions.

Whenever a fan speed change is required, the zone control-

ler will disable the fan output (for approximately 1 second) pri-

or to changing the fan speed relays (FANSPD 1 and FANSPD

2). This will allow the speed relays to be switched under a no-

load condition and will also prevent excessive EMI from being

generated if the speed is being reduced. Once the fan speed re-

lays are correctly positioned, the fan relay will be re-energized.

Following the execution of the initialization routine, the Fan

Coil will delay an amount of time (in seconds) equal to the re-

mainder of the Level II address divided by 60, before turning

the fan on.  This will allow for sequenced start-ups when more

than one Fan Coil is connected to the network.
 Fan Output:

Display  Units

Discrete ASCII

Default Value

Off

Display Range

Off/On

Network Access Read/Write

Alarm Service Configuration Table — 

The Alarm

Service Configuration Table is used to configure the alarms

used on the fan coil controller. See Fig. 34.
ALARM ROUTING CONTROL — The  Alarm  Routing

Control decision indicates which CCN system software or de-

vices will receive and process alarms sent by the Fan Coil con-

troller. This decision consists of eight digits which can be set to

zero or one. A setting of one indicates alarms should be sent to

this device. A setting of zero disables alarm processing for that

device. Currently the corresponding digits are configured for

the following devices: first digit - user interface software

(ComfortWORKS

®

, ComfortVIEW™, etc.); second digit -

Autodial Gateway or Telink; fourth digit - Alarm Printer Inter-

face Module, DataLINK module; digits 3 and 5 through 8 - un-

used.
Alarm Routing

Control:

Range

00000000 to 1111111

Default Value

11010000 

RE-ALARM TIME — This decision is used to configure the

number of minutes the fan coil controller will wait before an

alarm condition (which still exists) will be transmitted on the

communications network again. Re-alarming of an alarm con-

dition will continue until the condition no longer exists.
Re-Alarm Time: Units

Minutes

Range

0 to 1440

Default Value

0 (Disabled)

CONTROL TEMPERATURE HYSTERESIS — This  con-

figuration defines the range above the high set point and below

the low set point the space temperature must exceed for an

alarm condition to exist during occupied hours.
Control Temperature

Hysteresis: 

Units

delta F (delta C)

Range

1.0 to 20.0

Default Value

5

SUPPLY AIR TEMPERATURE — The Supply Air Temper-

ature High and Low Limit alarms are used to monitor the sup-

ply air temperature. If the temperature becomes too low or too

high, an alarm condition will exist.
Supply Air Temperature

Low Limit:

Units

degrees F (degrees C) 

Range

–40.0 to 245.0

Default Value

45.0

Supply Air Temperature

High Limit:

Units

degrees F (degrees C) 

Range

–40.0 to 245.0

Default Value

150

OCCUPIED RELATIVE HUMIDITY — The Occupied Rel-

ative Humidity alarm defines the allowable humidity levels

during occupied periods. If the humidity becomes too low or

too high, an alarm condition will exist.
Occupied Relative Humidity

Low Limit:

Units

% RH

Range

0 to 100

Default Value

30

Occupied Relative Humidity

High Limit

Units

% RH

Range

0 to 100

Default Value

70

UNOCCUPIED RELATIVE HUMIDITY — The  Unoccu-

pied Relative Humidity alarm defines the allowable humidity

levels during unoccupied periods. If the humidity becomes too

low or too high, an alarm condition will exist.
Unoccupied

Relative Humidity

Low Limit:

Units

% RH

Range

0 to 100

Default Value

10

Unoccupied

Relative Humidity

High Limit:

Units

% RH

Range

0 to 100

Default Value

90

Summary of Contents for 33ZCFANCOL

Page 1: ...n 43 SAFETY CONSIDERATIONS GENERAL The Fan Coil Controller is a field retrofit low cost CCN Carrier Comfort Network control for fan coil units The fan coil controller is a microprocessor based direct...

Page 2: ...The 33ZCSENCHG change over sensor is used by the fan coil controller in 2 pipe applica tions to determine the temperature of the heating and cooling medium which is supplied to the fan coil by the bui...

Page 3: ...SECONDARY BUS DATA COLLECTION OPTION BRIDGE RECOMMENDED SYSTEM MONITORING SOFTWARE CCN FAN COIL CONTROLLER TYPICAL FAN COIL UNIT FAN COIL CONTROLLER TYPICAL FAN COIL UNIT FULLY CCN COMPATIBLE CARRIER...

Page 4: ...rs are required for electric heat then it is recommended a 60 va transformer be used The maximum rating for any single output is 20 va NOTE Do not run sensor or communication wiring in the same condui...

Page 5: ...or Setpoint Adjustment GND M BLU L RED H BLK WHT valve 24VAC DX2 Valve Equipment Ground Transformer Ground Fan Relay Fan Motor Voltage Line Voltage Line ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56...

Page 6: ...HG SPT BLK M BLU L RED H BLK WHT Valve 24VAC DX2 Valve Transformer Ground Fan Relays Fan Motor Voltage Line Voltage Line M SAT ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND...

Page 7: ...M BLU L RED H BLK WHT CWV 24VAC DX2 Valve Transformer Ground Fan Relay HWV Fan Motor Voltage Line Voltage Line M SAT SPT ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND GND...

Page 8: ...BLU L RED H BLK WHT CWV 24VAC DX2 Valve Transformer Ground Fan Relays HWV Fan Motor Voltage Line Voltage Line M SAT ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND GND GND GN...

Page 9: ...HEAT1 DX2 DX1 Cool Relays Heat Relays BLK M BLU L RED H BLK WHT 24VAC DX2 Valve Transformer Ground Fan Relays Fan Motor Voltage Line Voltage Line ON FAN HEAT2 HEAT1 COM CONDSW CNGOVR T56 SAT SPT IAQ...

Page 10: ...s Fan Motor Voltage Line Voltage Line M SAT ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND GND GND GND GND RH Damper Air Fresh HIGH MED LOW FAN AC B W R B GND W R 24 VAC DX1...

Page 11: ...an Motor Voltage Line Voltage Line M SAT ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND GND GND GND GND RH Damper Air Fresh HIGH MED LOW FAN AC B W R B GND W R 24 VAC DX1 Va...

Page 12: ...er Board Outputs J6 J7 For single speed fan units connect fan start stop to control fan contactor NOTE J6 1 must be jumpered to 24 VAC J1 1 CHANNEL TERMINATIONS DESCRIPTION CONTROL DEVICE FAN AC J6 1...

Page 13: ...he sensor to the electrical box NOTE Sensor may also be mounted directly on the wall using 2 plastic anchors and 2 sheet metal screws field supplied 6 Use 20 gage wire to connect the sensor to the con...

Page 14: ...he CCN Network Communication Service Jack See Fig 16 18 To wire the service jack perform the following 1 Strip back the jacket from the CCN communication cable s for at least 3 inches Strip 1 4 in of...

Page 15: ...32 32 651 5 41 25 395 10 50 19 903 15 59 15 714 20 68 12 494 25 77 10 000 30 86 8 056 35 95 6 530 40 104 5 325 45 113 4 367 50 122 3 601 55 131 2 985 60 140 2 487 65 149 2 082 70 158 1 752 2 3 4 5 6 1...

Page 16: ...of the supply air temperature during heating and cooling For fan coils using a ducted supply the supply air tempera ture sensor should be located in the supply duct downstream of the discharge of the...

Page 17: ...arm Cool Warm Cool 2 COND TWISTED CABLE OR 3 COND CABLE TEMP SENSOR WIRING TYP SPACE TEMPERATURE SENSOR DISTANCE GREATER THAN 50 FT CCN COMM BUS TYPICAL FAN COIL UNIT FAN COIL ZONE CONTROLLER 50 FT MA...

Page 18: ...PROX 2 FT SUPPLY AIR SENSOR SUPPLY DUCT TYPICAL FAN COIL UNIT 3 00 1 50 0 50 CLEARANCE HOLE ENGAGEMENT HOLE FOR 10 SHEET METAL SCREW 2 Fig 20 Supply Air Temperature Sensor Part Number 33ZCSENSAT Fig 2...

Page 19: ...t the SIG COM terminal to terminal GND HUMIDITY SENSOR WALL MOUNTED INSTALLA TION The accessory space humidity sensor is installed on an interior wall to measure the relative humidity of the air with...

Page 20: ...OM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND GND GND GND GND RH Damper Air Fresh HIGH MED LOW FAN AC B W R B GND W R 24 VAC DX1 Valve communications CCN Not Used communications CCN LINE VOLTA...

Page 21: ...in the applicable wiring diagrams in Fig 4 10 Connect Accessories Refer to accessory installa tion instructions for installation procedures Fan coil controller wiring is shown for the following acces...

Page 22: ...K RED GREEN WHITE GND BLACK RED GREEN WHITE GND SHIELD WIRENUT SHIELD COMMUNICATION BUS WHT RED MAXIMUM WIRE LENGTH OF 100 FT LINKAGE THERMOSTAT WIRING CONNECTION BLOCK POWER SUPPLY BOARD W R WHT RED...

Page 23: ...GND GND GND GND GND RH Damper Air Fresh HIGH MED LOW FAN AC B W R B GND W R 24 VAC DX1 Valve communications CCN Not Used communications CCN 10 uf 25VDC Fig 28 Condensate Pump Switch Wiring NOTE To ens...

Page 24: ...24V DC Equipment Ground 24VAC DX2 Valve Voltage Line ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND GND GND GND GND RH Damper Air Fresh HIGH MED LOW FAN AC B W R B GND W R 2...

Page 25: ...nications CCN Not Used communications CCN J1 1 2 3 24V DC OAD 24VAC Equipment Ground 24VAC DX2 Valve Voltage Line ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND GND GND GND...

Page 26: ...and an outer jacket of PVC PVC nylon chrome vinyl or Teflon with a minimum operating temperature range of 20 C to 60 C is required CONNECTION TO THE COMMUNICATION BUS 1 Strip the ends of the red white...

Page 27: ...oling operation can be tested with the fan running in the occupied mode by forcing the space temperature point Force the point to a value 2 degrees above the cooling set point to test cooling and 2 de...

Page 28: ...operating mode for two pipe heating cooling fan coil units This point will display and follow the value of the Changeover Status after a 5 minute delay Upon a transition of the Changeover Status the...

Page 29: ...ead Write see note NOTE Force both cooling or heating outputs off prior to forc ing either input on Then force only one heating or cooling out put on at a time HEATING 1 The Heating 1 point provides t...

Page 30: ...when more than one Fan Coil is connected to the network Fan Output Display Units Discrete ASCII Default Value Off Display Range Off On Network Access Read Write Alarm Service Configuration Table The...

Page 31: ...The Start Day field is used to determine which day the holiday will start Start Day Range 1 to 31 Default Value 1 DURATION The Duration field indicates how long the holiday will last in days Duration...

Page 32: ...II Range 8 characters Bldg Spvr 96 characters LID 6400 32 characters LID 1600 Default Value SENSDI00 POINT n TYPE The Point n Type set point specifies whether the discrete point being monitored is a n...

Page 33: ...Configuration Screen Fig 38 Runtime Configuration Screen Description Value Units Name Notes Point n Name n 1 to 16 Text String PTnNAME n 1 to 16 Point n Type n 1 to 16 Bldg Spvr Normal Invert LID X PT...

Page 34: ...umber of Fan Speeds 1 3 Range 0 to 3 Default Value 3 AUTOMATIC FAN SPEED CONTROL Automatic fan speed control is based on a PID control which calculates the fan speed as a value between 0 and the Maxim...

Page 35: ...me Gard Enable TG1 Stage 2 Time Gard Disable TG2 2 Pos Valve Logic Type Normal CLT1 Stage 2 DX Logic Type Normal CLT2 Heating Type 0 HEAT_TYP 1 Mod 2 2 Pos 3 Elec 4 2 Pipe Chg w Elec Ht Heating PID Pr...

Page 36: ...e actual supply air temperature and the output is then adjusted to satisfy conditions A Proportional Integral Derivative PID loop is used The modulating con trol function compares the submaster refere...

Page 37: ...llion implied Range 0 to 5000 Default Value 2000 FILTER TIMER HOURS The Filter Timer Hours config uration determines when the filter status will display a Dirty alarm When the Filter Timer Hours is co...

Page 38: ...The Temp Sensor Config is used to specify if the controller is sharing the space temperature only space temperature with temperature offset slidebar or space temperature temperature offset slidebar an...

Page 39: ...schedule broadcast The point will display a 0 for unoccupied and a 1 for occupied Mode Display Range 0 to 1 Default Value 0 Network Access None CURRENT OCCUPIED PERIOD If the fan coil is con figured t...

Page 40: ...point displays the time of day when the fan coil last changed from occupied to the Unoccupied mode This point is read in conjunction with the Last Unoccupied Day to know the last time and day when the...

Page 41: ...41 Fig 43 Fan Coil Maintenance Table Screen...

Page 42: ...Display Range No Yes Default Value No Network Access None FAN SPEED The Fan Speed point displays the current fan speed in percentage Fan Speed Display Units Display Range 0 to 100 Default Value 0 Netw...

Page 43: ...Source Status decisions continue to display their last valid data Cooling Link Active Display Units Yes No Default Value No HEATING LINK ACTIVE The Heating Link Active deci sion displays the status of...

Page 44: ...l Cool Source Status Display Units On Off Default Value Off HOT WATER TEMPERATURE This decision displays the current leaving water temperature at the heat source that is linked to the fan coil by the...

Reviews: