background image

2

INSTALLATION

General — 

The fan coil controller is connected to a wall-

mounted, field-supplied, space temperature sensor (SPT) in

order to monitor zone temperature changes and satisfy zone

demand. 

On all heating or cooling applications, the fan coil controller

must be connected to a field-installed and -supplied supply air

temperature (SAT) sensor to monitor the temperature of the air

delivered by the fan coil.

Carrier’s Network Service Tool can be connected to the sys-

tem at the SPT sensor if CCN communication wiring is run to

an RJ-11 jack at the SPT sensor. The Network Service Tool can

be used to adjust set points, set operating parameters, and fully

configure the fan coil controller or any device on the system.

See Fig. 1.

Fan Coil Controller Hardware — 

The fan coil con-

troller consists of the following hardware:
• control module

• plastic enclosure

• two no. 8 x 

1

/

2

-in. sheet metal screws (for fan coil con-

troller mounting to fan coil)

Figure 2 shows the fan coil controller physical details.

Field-Supplied Hardware — 

Each fan coil controller

requires the following field-supplied components to complete

its installation:
• fan coil unit

• space temperature sensor (33ZCT55SPT, 33ZCT56SPT,

or 33ZCT57SPT)

• transformer — 24 vac, 40 va (standard applications)

• changeover sensor (required for 2-pipe applications)

• contactors (as required for fan, electric heat, or DX cool-

ing)

• supply air temperature sensor (33ZCSENSAT) with two

no. 10 x 

1

/

2

-in. sheet metal screws (to secure SAT sensor

to fan coil unit)

• indoor air quality sensor (as required)

• relative humidity sensor (as required)

• valve and actuator for hot water heat or chilled water (as

required)

• linkage thermostat (as required)
SPACE TEMPERATURE SENSOR — Each  fan  coil  con-

troller requires a field-supplied Carrier space temperature sen-

sor. There are three sensors available for this application:
• 33ZCT55SPT, Space Temperature Sensor with Override

Button

• 33ZCT56SPT, Space Temperature Sensor with Override

Button and Set Point Adjustment

• 33ZCT57SPT, Space Temperature Sensor with Override

Button, Set Point Adjustment, and Manual Fan Speed

control

SUPPLY AIR TEMPERATURE

 

(SAT) SENSOR — The

fan coil controller must be connected to a field-supplied supply

air temperature (SAT) sensor (part number 33ZCSENSAT) to

monitor the temperature of the air delivered by the fan coil.
CHANGEOVER SENSOR — The  33ZCSENCHG  change-

over sensor is used by the fan coil controller in 2-pipe applica-

tions to determine the temperature of the heating and cooling

medium which is supplied to the fan coil by the building piping

system. The fan coil controller can then determine if it is capa-

ble of providing heating or cooling to the space based on sens-

ing the pipe water temperature. This value may be broadcast to

other fan coils.
LINKAGE THERMOSTAT — The 

linkage 

thermostat

(33CSKITLST-01) is used to control multiple units from a sin-

gle thermostat. The linkage thermostat provides thermostat

functions for up to 8 units. Thermostat functions include space

temperature sensing, remote set point adjustment, and occu-

pancy information. The linkage thermostat can be used in place

of any space temperature sensor. If fail-safe operation is re-

quired, it is recommended to also install a 33ZCSENSAT in the

return air duct of each unit, wired to the space temperature sen-

sor input of the fan coil controller.
RELATIVE HUMIDITY SENSOR — The 33AMSENRHS000

relative humidity sensor is an indoor, wall-mounted sensor and

is required for zone humidity control (dehumidification).
INDOOR AIR QUALITY (CO

2

) SENSOR — An indoor air

quality sensor is required for IAQ monitoring. Three different

CO

2

 sensors are available for zone CO

2

 level monitoring.

The 33ZCSENCO2 sensor is an indoor, wall mounted sen-

sor with an LED (light-emitting diode) display.

The 33ZCT55CO2 sensor is an indoor, wall mounted sen-

sor without display. The CO

2

 sensor also includes a space tem-

perature sensor with override button.

The 33ZCT56CO2 sensor is an indoor, wall mounted sen-

sor without display. The CO

2

 sensor also includes a space tem-

perature sensor with override button and temperature offset.

Mount Fan Coil Controller

LOCATION — The fan coil controller should be located in-

side one of the available service access panels of the fan coil

unit. The fan coil controller may also be mounted on the exteri-

or of the fan coil unit. Select a location which will be safe from

water damage and allow sufficient access for service and wir-

ing. For service access, there should be at least 6 in. of clear-

ance between the front of the fan coil controller and adjacent

surfaces. Refer to Fig. 3.
MOUNTING — Mount the fan coil controller to the desired

location by holding the fan coil controller in place and screw-

ing two no. 8, pan-head, Phillips, sheet metal screws provided

through two of the holes available in the plastic base on the

either side of the fan coil controller.

Summary of Contents for 33ZCFANCOL

Page 1: ...n 43 SAFETY CONSIDERATIONS GENERAL The Fan Coil Controller is a field retrofit low cost CCN Carrier Comfort Network control for fan coil units The fan coil controller is a microprocessor based direct...

Page 2: ...The 33ZCSENCHG change over sensor is used by the fan coil controller in 2 pipe applica tions to determine the temperature of the heating and cooling medium which is supplied to the fan coil by the bui...

Page 3: ...SECONDARY BUS DATA COLLECTION OPTION BRIDGE RECOMMENDED SYSTEM MONITORING SOFTWARE CCN FAN COIL CONTROLLER TYPICAL FAN COIL UNIT FAN COIL CONTROLLER TYPICAL FAN COIL UNIT FULLY CCN COMPATIBLE CARRIER...

Page 4: ...rs are required for electric heat then it is recommended a 60 va transformer be used The maximum rating for any single output is 20 va NOTE Do not run sensor or communication wiring in the same condui...

Page 5: ...or Setpoint Adjustment GND M BLU L RED H BLK WHT valve 24VAC DX2 Valve Equipment Ground Transformer Ground Fan Relay Fan Motor Voltage Line Voltage Line ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56...

Page 6: ...HG SPT BLK M BLU L RED H BLK WHT Valve 24VAC DX2 Valve Transformer Ground Fan Relays Fan Motor Voltage Line Voltage Line M SAT ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND...

Page 7: ...M BLU L RED H BLK WHT CWV 24VAC DX2 Valve Transformer Ground Fan Relay HWV Fan Motor Voltage Line Voltage Line M SAT SPT ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND GND...

Page 8: ...BLU L RED H BLK WHT CWV 24VAC DX2 Valve Transformer Ground Fan Relays HWV Fan Motor Voltage Line Voltage Line M SAT ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND GND GND GN...

Page 9: ...HEAT1 DX2 DX1 Cool Relays Heat Relays BLK M BLU L RED H BLK WHT 24VAC DX2 Valve Transformer Ground Fan Relays Fan Motor Voltage Line Voltage Line ON FAN HEAT2 HEAT1 COM CONDSW CNGOVR T56 SAT SPT IAQ...

Page 10: ...s Fan Motor Voltage Line Voltage Line M SAT ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND GND GND GND GND RH Damper Air Fresh HIGH MED LOW FAN AC B W R B GND W R 24 VAC DX1...

Page 11: ...an Motor Voltage Line Voltage Line M SAT ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND GND GND GND GND RH Damper Air Fresh HIGH MED LOW FAN AC B W R B GND W R 24 VAC DX1 Va...

Page 12: ...er Board Outputs J6 J7 For single speed fan units connect fan start stop to control fan contactor NOTE J6 1 must be jumpered to 24 VAC J1 1 CHANNEL TERMINATIONS DESCRIPTION CONTROL DEVICE FAN AC J6 1...

Page 13: ...he sensor to the electrical box NOTE Sensor may also be mounted directly on the wall using 2 plastic anchors and 2 sheet metal screws field supplied 6 Use 20 gage wire to connect the sensor to the con...

Page 14: ...he CCN Network Communication Service Jack See Fig 16 18 To wire the service jack perform the following 1 Strip back the jacket from the CCN communication cable s for at least 3 inches Strip 1 4 in of...

Page 15: ...32 32 651 5 41 25 395 10 50 19 903 15 59 15 714 20 68 12 494 25 77 10 000 30 86 8 056 35 95 6 530 40 104 5 325 45 113 4 367 50 122 3 601 55 131 2 985 60 140 2 487 65 149 2 082 70 158 1 752 2 3 4 5 6 1...

Page 16: ...of the supply air temperature during heating and cooling For fan coils using a ducted supply the supply air tempera ture sensor should be located in the supply duct downstream of the discharge of the...

Page 17: ...arm Cool Warm Cool 2 COND TWISTED CABLE OR 3 COND CABLE TEMP SENSOR WIRING TYP SPACE TEMPERATURE SENSOR DISTANCE GREATER THAN 50 FT CCN COMM BUS TYPICAL FAN COIL UNIT FAN COIL ZONE CONTROLLER 50 FT MA...

Page 18: ...PROX 2 FT SUPPLY AIR SENSOR SUPPLY DUCT TYPICAL FAN COIL UNIT 3 00 1 50 0 50 CLEARANCE HOLE ENGAGEMENT HOLE FOR 10 SHEET METAL SCREW 2 Fig 20 Supply Air Temperature Sensor Part Number 33ZCSENSAT Fig 2...

Page 19: ...t the SIG COM terminal to terminal GND HUMIDITY SENSOR WALL MOUNTED INSTALLA TION The accessory space humidity sensor is installed on an interior wall to measure the relative humidity of the air with...

Page 20: ...OM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND GND GND GND GND RH Damper Air Fresh HIGH MED LOW FAN AC B W R B GND W R 24 VAC DX1 Valve communications CCN Not Used communications CCN LINE VOLTA...

Page 21: ...in the applicable wiring diagrams in Fig 4 10 Connect Accessories Refer to accessory installa tion instructions for installation procedures Fan coil controller wiring is shown for the following acces...

Page 22: ...K RED GREEN WHITE GND BLACK RED GREEN WHITE GND SHIELD WIRENUT SHIELD COMMUNICATION BUS WHT RED MAXIMUM WIRE LENGTH OF 100 FT LINKAGE THERMOSTAT WIRING CONNECTION BLOCK POWER SUPPLY BOARD W R WHT RED...

Page 23: ...GND GND GND GND GND RH Damper Air Fresh HIGH MED LOW FAN AC B W R B GND W R 24 VAC DX1 Valve communications CCN Not Used communications CCN 10 uf 25VDC Fig 28 Condensate Pump Switch Wiring NOTE To ens...

Page 24: ...24V DC Equipment Ground 24VAC DX2 Valve Voltage Line ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND GND GND GND GND RH Damper Air Fresh HIGH MED LOW FAN AC B W R B GND W R 2...

Page 25: ...nications CCN Not Used communications CCN J1 1 2 3 24V DC OAD 24VAC Equipment Ground 24VAC DX2 Valve Voltage Line ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND GND GND GND...

Page 26: ...and an outer jacket of PVC PVC nylon chrome vinyl or Teflon with a minimum operating temperature range of 20 C to 60 C is required CONNECTION TO THE COMMUNICATION BUS 1 Strip the ends of the red white...

Page 27: ...oling operation can be tested with the fan running in the occupied mode by forcing the space temperature point Force the point to a value 2 degrees above the cooling set point to test cooling and 2 de...

Page 28: ...operating mode for two pipe heating cooling fan coil units This point will display and follow the value of the Changeover Status after a 5 minute delay Upon a transition of the Changeover Status the...

Page 29: ...ead Write see note NOTE Force both cooling or heating outputs off prior to forc ing either input on Then force only one heating or cooling out put on at a time HEATING 1 The Heating 1 point provides t...

Page 30: ...when more than one Fan Coil is connected to the network Fan Output Display Units Discrete ASCII Default Value Off Display Range Off On Network Access Read Write Alarm Service Configuration Table The...

Page 31: ...The Start Day field is used to determine which day the holiday will start Start Day Range 1 to 31 Default Value 1 DURATION The Duration field indicates how long the holiday will last in days Duration...

Page 32: ...II Range 8 characters Bldg Spvr 96 characters LID 6400 32 characters LID 1600 Default Value SENSDI00 POINT n TYPE The Point n Type set point specifies whether the discrete point being monitored is a n...

Page 33: ...Configuration Screen Fig 38 Runtime Configuration Screen Description Value Units Name Notes Point n Name n 1 to 16 Text String PTnNAME n 1 to 16 Point n Type n 1 to 16 Bldg Spvr Normal Invert LID X PT...

Page 34: ...umber of Fan Speeds 1 3 Range 0 to 3 Default Value 3 AUTOMATIC FAN SPEED CONTROL Automatic fan speed control is based on a PID control which calculates the fan speed as a value between 0 and the Maxim...

Page 35: ...me Gard Enable TG1 Stage 2 Time Gard Disable TG2 2 Pos Valve Logic Type Normal CLT1 Stage 2 DX Logic Type Normal CLT2 Heating Type 0 HEAT_TYP 1 Mod 2 2 Pos 3 Elec 4 2 Pipe Chg w Elec Ht Heating PID Pr...

Page 36: ...e actual supply air temperature and the output is then adjusted to satisfy conditions A Proportional Integral Derivative PID loop is used The modulating con trol function compares the submaster refere...

Page 37: ...llion implied Range 0 to 5000 Default Value 2000 FILTER TIMER HOURS The Filter Timer Hours config uration determines when the filter status will display a Dirty alarm When the Filter Timer Hours is co...

Page 38: ...The Temp Sensor Config is used to specify if the controller is sharing the space temperature only space temperature with temperature offset slidebar or space temperature temperature offset slidebar an...

Page 39: ...schedule broadcast The point will display a 0 for unoccupied and a 1 for occupied Mode Display Range 0 to 1 Default Value 0 Network Access None CURRENT OCCUPIED PERIOD If the fan coil is con figured t...

Page 40: ...point displays the time of day when the fan coil last changed from occupied to the Unoccupied mode This point is read in conjunction with the Last Unoccupied Day to know the last time and day when the...

Page 41: ...41 Fig 43 Fan Coil Maintenance Table Screen...

Page 42: ...Display Range No Yes Default Value No Network Access None FAN SPEED The Fan Speed point displays the current fan speed in percentage Fan Speed Display Units Display Range 0 to 100 Default Value 0 Netw...

Page 43: ...Source Status decisions continue to display their last valid data Cooling Link Active Display Units Yes No Default Value No HEATING LINK ACTIVE The Heating Link Active deci sion displays the status of...

Page 44: ...l Cool Source Status Display Units On Off Default Value Off HOT WATER TEMPERATURE This decision displays the current leaving water temperature at the heat source that is linked to the fan coil by the...

Reviews: