background image

36

STAGED COOLING —  The staging function is used for two

position valves or DX cooling (1 or 2 stages). The staging

function uses the cooling submaster reference from the PID

and compares the value to the supply-air temperature to calcu-

late the required number of output stages to energize.

For DX cooling, configurable Time Guard delays are pro-

vided to allow for up to 2 stages of compression. Also a

DX Lockout will prevent operation of the DX cooling if the

outdoor-air temperature is below this value.
NOTE: Outdoor-air temperature must be provided through a

CCN broadcast over the network.

Once cooling is active, a maintenance decision indicates

that cooling is in effect. Also the cooling capacity is then calcu-

lated based upon the supply-air temperature, the space temper-

ature, and a minimum supply air temperature limit of 50 F.

The cooling algorithm controls the valve or stages of DX

cooling to prevent the space temperature from exceeding the

current cooling set point (which includes any calculated offset

value from a T56 or T57 sensor slide bar during occupied peri-

ods). Also, the cooling is controlled so that the supply-air tem-

perature does not fall below 50 F when cooling is active. 
Number of Stages:Range

1, 2

Default Value

1

The Time Guards must be set to Enable for output to a com-

pressor, and set to Disable for output to a valve or compressor

unloader.
Stage 1

Time Guard:

Range

Disable/Enable

Default Value

Enable

Stage 2

Time Guard:

Range

Disable/Enable

Default Value

Disable

The stage outputs will send a 24 VAC signal to the device

when turned on if these configurations are set to normal. The

device will be sent a 24 VAC signal in the Off state if Inverted

logic is applied.
Two-Position

Valve Logic Type: Range

Normal/Inverted

Default Value

Normal

Stage 2 DX

Logic Type:

Range

Normal/Inverted

Default Value

Inverted

HEATING TYPE — The Heating Type configuration sets the

type of heating that the fan coil will use. Heating type has four

selections available: 0 = None, 1 = Modulating Valve, 2 = Two-

Position Valve, 3 = Electric Heat, 4 = Pipe Changeover with

Electric Heat.
Heating Type:

Range

0 to 4

Default Value

0

HEATING CONTROL — The fan coil controller determines

if a heating demand exists in the space. The zone controller

reads the space temperature sensor and compares the tempera-

ture to the current low set point (including any calculated offset

value from a T56 or T57 sensor) during occupied periods. If it

is below the set point, and heating is configured and available,

it then calculates the required supply air temperature to satisfy

the given conditions. The calculated value (heating submaster

reference) is compared to the actual supply-air temperature and

the output is then adjusted to satisfy conditions. A Proportional

/ Integral / Derivative (PID) loop is used. The modulating con-

trol function compares the submaster reference from the PID

loop to the supply-air temperature and then calculates the di-

rection and time to position the valve.

The staging function is used for two-position valves or elec-

tric heating (1 or 2 stages). The staging function uses the heat-

ing submaster reference from the PID and compares the value

to the Supply Air Temperature to calculate the required number

of output stages to energize.

For units using floating point valves, the floating point func-

tion compares the submaster reference from the PID loop to the

supply-air temperature to calculate the direction and time to

position the valve. Both outputs are not allowed to be ON

simultaneously.

The heating algorithm will control a modulating heating

valve to maintain the space temperature at the midpoint be-

tween the current low and high set points whenever dehumidi-

fication is active and reheat has been enabled. During this time,

a maintenance parameter will be set (reheat flag). 

For two pipe changeover systems, the valve/DX output ter-

minations are used for a single water valve. IF/THEN logic de-

termines the routing of the control signals from the appropriate

heating or cooling algorithm to the cooling valve hardware out-

puts. The decision to route either heating or cooling is based

upon the Changeover Mode and the 2-pipe Changeover Sys-

tem configuration equal to Yes. The actual control type output

is determined by the configured Heat Type.

The Heating PID includes the following set points: Propor-

tional Gain, Integral Gain, Derivative Gain, Starting Value and

Fan Off Value. 
Proportional Gain:Range

0.0 to 40.0

Default Value

8.0

Integral Gain:

Range

0.0 to 10.0

Default Value

0.3

Derivative Gain: Range

0.0 to 20.0

Default Value

0.0

Starting Value:

Units

Degrees F

Range

40.0 to 90.0

Default Value

80.0

Fan Off Value:

Units

Degrees F

Range

35.0 to 120.0

Default Value

55.0

NOTE: Default values are shown for Type 1 modulating

Heating. For other heating types, refer to the following:
Variable

2 Position/1 Stage Electric

2 Stage Electric

PG

40.0

40.0

IG

0.0

0.5

Starting

85.0

85.0

Value

To maintain a minimum temperature that may prevent a coil

freeze up on units located on an exterior wall, a configured fan

off value is used when the unit is Off. This feature is only appli-

cable to modulating heating and the Changeover Mode must be

Heating for two pipe changeover systems. Heat capacity will

be displayed as 0% and the Heating in Effect maintenance pa-

rameter will display NO during minimum duct temperature

control.

IMPORTANT: For 2-pipe systems, both heating and

cooling types must be the same (for example, both set to

1, modulating, or both set to 2, two-position).

1001

Summary of Contents for 33ZCFANCOL

Page 1: ...n 43 SAFETY CONSIDERATIONS GENERAL The Fan Coil Controller is a field retrofit low cost CCN Carrier Comfort Network control for fan coil units The fan coil controller is a microprocessor based direct...

Page 2: ...The 33ZCSENCHG change over sensor is used by the fan coil controller in 2 pipe applica tions to determine the temperature of the heating and cooling medium which is supplied to the fan coil by the bui...

Page 3: ...SECONDARY BUS DATA COLLECTION OPTION BRIDGE RECOMMENDED SYSTEM MONITORING SOFTWARE CCN FAN COIL CONTROLLER TYPICAL FAN COIL UNIT FAN COIL CONTROLLER TYPICAL FAN COIL UNIT FULLY CCN COMPATIBLE CARRIER...

Page 4: ...rs are required for electric heat then it is recommended a 60 va transformer be used The maximum rating for any single output is 20 va NOTE Do not run sensor or communication wiring in the same condui...

Page 5: ...or Setpoint Adjustment GND M BLU L RED H BLK WHT valve 24VAC DX2 Valve Equipment Ground Transformer Ground Fan Relay Fan Motor Voltage Line Voltage Line ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56...

Page 6: ...HG SPT BLK M BLU L RED H BLK WHT Valve 24VAC DX2 Valve Transformer Ground Fan Relays Fan Motor Voltage Line Voltage Line M SAT ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND...

Page 7: ...M BLU L RED H BLK WHT CWV 24VAC DX2 Valve Transformer Ground Fan Relay HWV Fan Motor Voltage Line Voltage Line M SAT SPT ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND GND...

Page 8: ...BLU L RED H BLK WHT CWV 24VAC DX2 Valve Transformer Ground Fan Relays HWV Fan Motor Voltage Line Voltage Line M SAT ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND GND GND GN...

Page 9: ...HEAT1 DX2 DX1 Cool Relays Heat Relays BLK M BLU L RED H BLK WHT 24VAC DX2 Valve Transformer Ground Fan Relays Fan Motor Voltage Line Voltage Line ON FAN HEAT2 HEAT1 COM CONDSW CNGOVR T56 SAT SPT IAQ...

Page 10: ...s Fan Motor Voltage Line Voltage Line M SAT ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND GND GND GND GND RH Damper Air Fresh HIGH MED LOW FAN AC B W R B GND W R 24 VAC DX1...

Page 11: ...an Motor Voltage Line Voltage Line M SAT ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND GND GND GND GND RH Damper Air Fresh HIGH MED LOW FAN AC B W R B GND W R 24 VAC DX1 Va...

Page 12: ...er Board Outputs J6 J7 For single speed fan units connect fan start stop to control fan contactor NOTE J6 1 must be jumpered to 24 VAC J1 1 CHANNEL TERMINATIONS DESCRIPTION CONTROL DEVICE FAN AC J6 1...

Page 13: ...he sensor to the electrical box NOTE Sensor may also be mounted directly on the wall using 2 plastic anchors and 2 sheet metal screws field supplied 6 Use 20 gage wire to connect the sensor to the con...

Page 14: ...he CCN Network Communication Service Jack See Fig 16 18 To wire the service jack perform the following 1 Strip back the jacket from the CCN communication cable s for at least 3 inches Strip 1 4 in of...

Page 15: ...32 32 651 5 41 25 395 10 50 19 903 15 59 15 714 20 68 12 494 25 77 10 000 30 86 8 056 35 95 6 530 40 104 5 325 45 113 4 367 50 122 3 601 55 131 2 985 60 140 2 487 65 149 2 082 70 158 1 752 2 3 4 5 6 1...

Page 16: ...of the supply air temperature during heating and cooling For fan coils using a ducted supply the supply air tempera ture sensor should be located in the supply duct downstream of the discharge of the...

Page 17: ...arm Cool Warm Cool 2 COND TWISTED CABLE OR 3 COND CABLE TEMP SENSOR WIRING TYP SPACE TEMPERATURE SENSOR DISTANCE GREATER THAN 50 FT CCN COMM BUS TYPICAL FAN COIL UNIT FAN COIL ZONE CONTROLLER 50 FT MA...

Page 18: ...PROX 2 FT SUPPLY AIR SENSOR SUPPLY DUCT TYPICAL FAN COIL UNIT 3 00 1 50 0 50 CLEARANCE HOLE ENGAGEMENT HOLE FOR 10 SHEET METAL SCREW 2 Fig 20 Supply Air Temperature Sensor Part Number 33ZCSENSAT Fig 2...

Page 19: ...t the SIG COM terminal to terminal GND HUMIDITY SENSOR WALL MOUNTED INSTALLA TION The accessory space humidity sensor is installed on an interior wall to measure the relative humidity of the air with...

Page 20: ...OM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND GND GND GND GND RH Damper Air Fresh HIGH MED LOW FAN AC B W R B GND W R 24 VAC DX1 Valve communications CCN Not Used communications CCN LINE VOLTA...

Page 21: ...in the applicable wiring diagrams in Fig 4 10 Connect Accessories Refer to accessory installa tion instructions for installation procedures Fan coil controller wiring is shown for the following acces...

Page 22: ...K RED GREEN WHITE GND BLACK RED GREEN WHITE GND SHIELD WIRENUT SHIELD COMMUNICATION BUS WHT RED MAXIMUM WIRE LENGTH OF 100 FT LINKAGE THERMOSTAT WIRING CONNECTION BLOCK POWER SUPPLY BOARD W R WHT RED...

Page 23: ...GND GND GND GND GND RH Damper Air Fresh HIGH MED LOW FAN AC B W R B GND W R 24 VAC DX1 Valve communications CCN Not Used communications CCN 10 uf 25VDC Fig 28 Condensate Pump Switch Wiring NOTE To ens...

Page 24: ...24V DC Equipment Ground 24VAC DX2 Valve Voltage Line ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND GND GND GND GND RH Damper Air Fresh HIGH MED LOW FAN AC B W R B GND W R 2...

Page 25: ...nications CCN Not Used communications CCN J1 1 2 3 24V DC OAD 24VAC Equipment Ground 24VAC DX2 Valve Voltage Line ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND GND GND GND...

Page 26: ...and an outer jacket of PVC PVC nylon chrome vinyl or Teflon with a minimum operating temperature range of 20 C to 60 C is required CONNECTION TO THE COMMUNICATION BUS 1 Strip the ends of the red white...

Page 27: ...oling operation can be tested with the fan running in the occupied mode by forcing the space temperature point Force the point to a value 2 degrees above the cooling set point to test cooling and 2 de...

Page 28: ...operating mode for two pipe heating cooling fan coil units This point will display and follow the value of the Changeover Status after a 5 minute delay Upon a transition of the Changeover Status the...

Page 29: ...ead Write see note NOTE Force both cooling or heating outputs off prior to forc ing either input on Then force only one heating or cooling out put on at a time HEATING 1 The Heating 1 point provides t...

Page 30: ...when more than one Fan Coil is connected to the network Fan Output Display Units Discrete ASCII Default Value Off Display Range Off On Network Access Read Write Alarm Service Configuration Table The...

Page 31: ...The Start Day field is used to determine which day the holiday will start Start Day Range 1 to 31 Default Value 1 DURATION The Duration field indicates how long the holiday will last in days Duration...

Page 32: ...II Range 8 characters Bldg Spvr 96 characters LID 6400 32 characters LID 1600 Default Value SENSDI00 POINT n TYPE The Point n Type set point specifies whether the discrete point being monitored is a n...

Page 33: ...Configuration Screen Fig 38 Runtime Configuration Screen Description Value Units Name Notes Point n Name n 1 to 16 Text String PTnNAME n 1 to 16 Point n Type n 1 to 16 Bldg Spvr Normal Invert LID X PT...

Page 34: ...umber of Fan Speeds 1 3 Range 0 to 3 Default Value 3 AUTOMATIC FAN SPEED CONTROL Automatic fan speed control is based on a PID control which calculates the fan speed as a value between 0 and the Maxim...

Page 35: ...me Gard Enable TG1 Stage 2 Time Gard Disable TG2 2 Pos Valve Logic Type Normal CLT1 Stage 2 DX Logic Type Normal CLT2 Heating Type 0 HEAT_TYP 1 Mod 2 2 Pos 3 Elec 4 2 Pipe Chg w Elec Ht Heating PID Pr...

Page 36: ...e actual supply air temperature and the output is then adjusted to satisfy conditions A Proportional Integral Derivative PID loop is used The modulating con trol function compares the submaster refere...

Page 37: ...llion implied Range 0 to 5000 Default Value 2000 FILTER TIMER HOURS The Filter Timer Hours config uration determines when the filter status will display a Dirty alarm When the Filter Timer Hours is co...

Page 38: ...The Temp Sensor Config is used to specify if the controller is sharing the space temperature only space temperature with temperature offset slidebar or space temperature temperature offset slidebar an...

Page 39: ...schedule broadcast The point will display a 0 for unoccupied and a 1 for occupied Mode Display Range 0 to 1 Default Value 0 Network Access None CURRENT OCCUPIED PERIOD If the fan coil is con figured t...

Page 40: ...point displays the time of day when the fan coil last changed from occupied to the Unoccupied mode This point is read in conjunction with the Last Unoccupied Day to know the last time and day when the...

Page 41: ...41 Fig 43 Fan Coil Maintenance Table Screen...

Page 42: ...Display Range No Yes Default Value No Network Access None FAN SPEED The Fan Speed point displays the current fan speed in percentage Fan Speed Display Units Display Range 0 to 100 Default Value 0 Netw...

Page 43: ...Source Status decisions continue to display their last valid data Cooling Link Active Display Units Yes No Default Value No HEATING LINK ACTIVE The Heating Link Active deci sion displays the status of...

Page 44: ...l Cool Source Status Display Units On Off Default Value Off HOT WATER TEMPERATURE This decision displays the current leaving water temperature at the heat source that is linked to the fan coil by the...

Reviews: