background image

37

STAGED HEATING — The Staged Heating function is used

for two-position valves or for electric heat (1 or 2 stages). The

staging function uses the heating submaster reference value

from the PID and compares it to the supply-air temperature to

calculate the required number of output stages to energize.
Number of Stages:Range

1 to 2

Default Value

1

Two-Position

Valve Logic:

Range

Normal/Inverted

Default Value

Normal

The outputs will send a signal to the device when turned on

if these configurations are set to normal. The device will be

sent a signal in the Off state if Inverted logic is applied.

For electric heat, a Time Guard is provided for the first stage

to prevent excessive cycling and premature contactor failure.

Once heating is active, a maintenance decision indicates that

heating is in effect. Also the heating capacity is then calculated

based upon the Supply Air Temperature, the Space Tempera-

ture, and a maximum supply air temperature limit of 140 F.
TWO POSITION DAMPER — The  Two-Position  Damper

configuration should be set to 1 if the fan coil controller is used

with a two-position outdoor air ventilation damper. The damp-

er control logic determines that if the fan is OFF, or the occu-

pancy status is Unoccupied or Biased Occupied, the damper

will be closed. If the fan is ON and the occupancy status is oc-

cupied, the damper will be open.
Two Position

Damper:

Range

NO/YES

Default Value

NO

INDOOR AIR QUALITY — The  Indoor Air Quality set

points configure the CO

2

 sensor for use with the zone control-

ler. The voltage and reference set points allow the zone control-

ler to interpret the voltage signal from the CO

2

 sensor. The AQ

Low Voltage set point defines the lowest voltage that should be

read from the air quality sensor. The AQ High Voltage configu-

ration defines the highest voltage which should be read from

the air quality sensor.  The Low Reference configuration de-

fines the value in parts per million which correlate to the low

voltage reading from the air quality sensor. The High Refer-

ence configuration defines the value in parts per million which

correlate to the high voltage reading from the air quality sensor.
AQ Low Voltage: Units

Volts

Range

00.0 to 10.0

Default Value

0.0

AQ High Voltage: Units

Volts

Range

00.0 to 10.0

Default Value

10.0 

Low Reference: Units

None (Parts Per Million

 implied)

Range

0 to 5000

Default Value

0

High Reference: Units

None (Parts Per Million

implied)

Range

0 to 5000

Default Value

2000

FILTER TIMER HOURS — The Filter Timer Hours config-

uration determines when the filter status will display a “Dirty”

alarm. When the Filter Timer Hours is configured to a value

other than zero and fan run time exceeds the value configured,

the filter status will display “Dirty” and a CCN alarm will be

generated. Setting the configured Filter Timer Hours value to

zero will disable the alarm condition. The value of the timer is

stored in EEPROM to protect it in the event of a power failure.

The value is stored every 24 hours. The value is multiplied by

100. For example, if the Filter Timer Hours is set to 6, the

“Dirty” condition would be generated after 600 hours of run

time.
Filter Timer

Hours:

Range

0 to 99

Default Value

15

CONDENSATE PUMP TIMER — The  Condensate  Pump

Timer configuration is used to set the amount of time which

must elapse, after the Condensate pump overflow contact clos-

es, before the fan will be shut down. Heating and cooling is dis-

abled and an alarm message is broadcast.
Condensate

Pump Timer:

Units

minutes

Range

1 to 60

Default Value

10

SPACE TEMPERATURE TRIM — The  Space  Temperature

Trim configuration is used to calibrate the temperature display

for a sensor that does not appear to be reading correctly.
Space Temperature

Trim:

Units

Delta F

Range

–5.0 to 5.0

Default Value

0.0

SUPPLY AIR TEMPERATURE TRIM — The  Supply  Air

Temperature Trim configuration is used to calibrate the temper-

ature display for a sensor that does not appear to be reading

correctly.
Supply Air

Temperature

Trim:

Units

Delta F

Range

–5.0 to 5.0

Default Value

0.0

Fan Coil Configuration — 

The Fan Coil Configura-

tion screen allows the user to configure the functions of the fan

coil. See Fig. 41.
OCCUPANCY SCHEDULE NUMBER — The  Occupancy

Schedule Number determines which Global Occupancy

Schedule that the zone controller will follow. A value of 64 dis-

ables global occupancy from CCN and will decide Occupancy

from its local schedule. A value of 65 and above will allow the

zone controller to follow the global occupancy schedule of the

number broadcast over CCN.
Occupancy Schedule

Number

Range

64 to 99

Default Value

64

GLOBAL SCHEDULE MASTER — The  Global  Schedule

Master setting configures the zone controller to broadcast or re-

ceive a global schedule. If set to Yes, the zone controller will

act as a global schedule master and its schedule will be broad-

cast to the CCN. If set to No, the zone controller will not broad-

cast a global schedule and it will receive the configured occu-

pancy schedule number.
Global Schedule

Master:

Range

No/Yes

Default Value

No

Summary of Contents for 33ZCFANCOL

Page 1: ...n 43 SAFETY CONSIDERATIONS GENERAL The Fan Coil Controller is a field retrofit low cost CCN Carrier Comfort Network control for fan coil units The fan coil controller is a microprocessor based direct...

Page 2: ...The 33ZCSENCHG change over sensor is used by the fan coil controller in 2 pipe applica tions to determine the temperature of the heating and cooling medium which is supplied to the fan coil by the bui...

Page 3: ...SECONDARY BUS DATA COLLECTION OPTION BRIDGE RECOMMENDED SYSTEM MONITORING SOFTWARE CCN FAN COIL CONTROLLER TYPICAL FAN COIL UNIT FAN COIL CONTROLLER TYPICAL FAN COIL UNIT FULLY CCN COMPATIBLE CARRIER...

Page 4: ...rs are required for electric heat then it is recommended a 60 va transformer be used The maximum rating for any single output is 20 va NOTE Do not run sensor or communication wiring in the same condui...

Page 5: ...or Setpoint Adjustment GND M BLU L RED H BLK WHT valve 24VAC DX2 Valve Equipment Ground Transformer Ground Fan Relay Fan Motor Voltage Line Voltage Line ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56...

Page 6: ...HG SPT BLK M BLU L RED H BLK WHT Valve 24VAC DX2 Valve Transformer Ground Fan Relays Fan Motor Voltage Line Voltage Line M SAT ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND...

Page 7: ...M BLU L RED H BLK WHT CWV 24VAC DX2 Valve Transformer Ground Fan Relay HWV Fan Motor Voltage Line Voltage Line M SAT SPT ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND GND...

Page 8: ...BLU L RED H BLK WHT CWV 24VAC DX2 Valve Transformer Ground Fan Relays HWV Fan Motor Voltage Line Voltage Line M SAT ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND GND GND GN...

Page 9: ...HEAT1 DX2 DX1 Cool Relays Heat Relays BLK M BLU L RED H BLK WHT 24VAC DX2 Valve Transformer Ground Fan Relays Fan Motor Voltage Line Voltage Line ON FAN HEAT2 HEAT1 COM CONDSW CNGOVR T56 SAT SPT IAQ...

Page 10: ...s Fan Motor Voltage Line Voltage Line M SAT ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND GND GND GND GND RH Damper Air Fresh HIGH MED LOW FAN AC B W R B GND W R 24 VAC DX1...

Page 11: ...an Motor Voltage Line Voltage Line M SAT ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND GND GND GND GND RH Damper Air Fresh HIGH MED LOW FAN AC B W R B GND W R 24 VAC DX1 Va...

Page 12: ...er Board Outputs J6 J7 For single speed fan units connect fan start stop to control fan contactor NOTE J6 1 must be jumpered to 24 VAC J1 1 CHANNEL TERMINATIONS DESCRIPTION CONTROL DEVICE FAN AC J6 1...

Page 13: ...he sensor to the electrical box NOTE Sensor may also be mounted directly on the wall using 2 plastic anchors and 2 sheet metal screws field supplied 6 Use 20 gage wire to connect the sensor to the con...

Page 14: ...he CCN Network Communication Service Jack See Fig 16 18 To wire the service jack perform the following 1 Strip back the jacket from the CCN communication cable s for at least 3 inches Strip 1 4 in of...

Page 15: ...32 32 651 5 41 25 395 10 50 19 903 15 59 15 714 20 68 12 494 25 77 10 000 30 86 8 056 35 95 6 530 40 104 5 325 45 113 4 367 50 122 3 601 55 131 2 985 60 140 2 487 65 149 2 082 70 158 1 752 2 3 4 5 6 1...

Page 16: ...of the supply air temperature during heating and cooling For fan coils using a ducted supply the supply air tempera ture sensor should be located in the supply duct downstream of the discharge of the...

Page 17: ...arm Cool Warm Cool 2 COND TWISTED CABLE OR 3 COND CABLE TEMP SENSOR WIRING TYP SPACE TEMPERATURE SENSOR DISTANCE GREATER THAN 50 FT CCN COMM BUS TYPICAL FAN COIL UNIT FAN COIL ZONE CONTROLLER 50 FT MA...

Page 18: ...PROX 2 FT SUPPLY AIR SENSOR SUPPLY DUCT TYPICAL FAN COIL UNIT 3 00 1 50 0 50 CLEARANCE HOLE ENGAGEMENT HOLE FOR 10 SHEET METAL SCREW 2 Fig 20 Supply Air Temperature Sensor Part Number 33ZCSENSAT Fig 2...

Page 19: ...t the SIG COM terminal to terminal GND HUMIDITY SENSOR WALL MOUNTED INSTALLA TION The accessory space humidity sensor is installed on an interior wall to measure the relative humidity of the air with...

Page 20: ...OM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND GND GND GND GND RH Damper Air Fresh HIGH MED LOW FAN AC B W R B GND W R 24 VAC DX1 Valve communications CCN Not Used communications CCN LINE VOLTA...

Page 21: ...in the applicable wiring diagrams in Fig 4 10 Connect Accessories Refer to accessory installa tion instructions for installation procedures Fan coil controller wiring is shown for the following acces...

Page 22: ...K RED GREEN WHITE GND BLACK RED GREEN WHITE GND SHIELD WIRENUT SHIELD COMMUNICATION BUS WHT RED MAXIMUM WIRE LENGTH OF 100 FT LINKAGE THERMOSTAT WIRING CONNECTION BLOCK POWER SUPPLY BOARD W R WHT RED...

Page 23: ...GND GND GND GND GND RH Damper Air Fresh HIGH MED LOW FAN AC B W R B GND W R 24 VAC DX1 Valve communications CCN Not Used communications CCN 10 uf 25VDC Fig 28 Condensate Pump Switch Wiring NOTE To ens...

Page 24: ...24V DC Equipment Ground 24VAC DX2 Valve Voltage Line ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND GND GND GND GND RH Damper Air Fresh HIGH MED LOW FAN AC B W R B GND W R 2...

Page 25: ...nications CCN Not Used communications CCN J1 1 2 3 24V DC OAD 24VAC Equipment Ground 24VAC DX2 Valve Voltage Line ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND GND GND GND...

Page 26: ...and an outer jacket of PVC PVC nylon chrome vinyl or Teflon with a minimum operating temperature range of 20 C to 60 C is required CONNECTION TO THE COMMUNICATION BUS 1 Strip the ends of the red white...

Page 27: ...oling operation can be tested with the fan running in the occupied mode by forcing the space temperature point Force the point to a value 2 degrees above the cooling set point to test cooling and 2 de...

Page 28: ...operating mode for two pipe heating cooling fan coil units This point will display and follow the value of the Changeover Status after a 5 minute delay Upon a transition of the Changeover Status the...

Page 29: ...ead Write see note NOTE Force both cooling or heating outputs off prior to forc ing either input on Then force only one heating or cooling out put on at a time HEATING 1 The Heating 1 point provides t...

Page 30: ...when more than one Fan Coil is connected to the network Fan Output Display Units Discrete ASCII Default Value Off Display Range Off On Network Access Read Write Alarm Service Configuration Table The...

Page 31: ...The Start Day field is used to determine which day the holiday will start Start Day Range 1 to 31 Default Value 1 DURATION The Duration field indicates how long the holiday will last in days Duration...

Page 32: ...II Range 8 characters Bldg Spvr 96 characters LID 6400 32 characters LID 1600 Default Value SENSDI00 POINT n TYPE The Point n Type set point specifies whether the discrete point being monitored is a n...

Page 33: ...Configuration Screen Fig 38 Runtime Configuration Screen Description Value Units Name Notes Point n Name n 1 to 16 Text String PTnNAME n 1 to 16 Point n Type n 1 to 16 Bldg Spvr Normal Invert LID X PT...

Page 34: ...umber of Fan Speeds 1 3 Range 0 to 3 Default Value 3 AUTOMATIC FAN SPEED CONTROL Automatic fan speed control is based on a PID control which calculates the fan speed as a value between 0 and the Maxim...

Page 35: ...me Gard Enable TG1 Stage 2 Time Gard Disable TG2 2 Pos Valve Logic Type Normal CLT1 Stage 2 DX Logic Type Normal CLT2 Heating Type 0 HEAT_TYP 1 Mod 2 2 Pos 3 Elec 4 2 Pipe Chg w Elec Ht Heating PID Pr...

Page 36: ...e actual supply air temperature and the output is then adjusted to satisfy conditions A Proportional Integral Derivative PID loop is used The modulating con trol function compares the submaster refere...

Page 37: ...llion implied Range 0 to 5000 Default Value 2000 FILTER TIMER HOURS The Filter Timer Hours config uration determines when the filter status will display a Dirty alarm When the Filter Timer Hours is co...

Page 38: ...The Temp Sensor Config is used to specify if the controller is sharing the space temperature only space temperature with temperature offset slidebar or space temperature temperature offset slidebar an...

Page 39: ...schedule broadcast The point will display a 0 for unoccupied and a 1 for occupied Mode Display Range 0 to 1 Default Value 0 Network Access None CURRENT OCCUPIED PERIOD If the fan coil is con figured t...

Page 40: ...point displays the time of day when the fan coil last changed from occupied to the Unoccupied mode This point is read in conjunction with the Last Unoccupied Day to know the last time and day when the...

Page 41: ...41 Fig 43 Fan Coil Maintenance Table Screen...

Page 42: ...Display Range No Yes Default Value No Network Access None FAN SPEED The Fan Speed point displays the current fan speed in percentage Fan Speed Display Units Display Range 0 to 100 Default Value 0 Netw...

Page 43: ...Source Status decisions continue to display their last valid data Cooling Link Active Display Units Yes No Default Value No HEATING LINK ACTIVE The Heating Link Active deci sion displays the status of...

Page 44: ...l Cool Source Status Display Units On Off Default Value Off HOT WATER TEMPERATURE This decision displays the current leaving water temperature at the heat source that is linked to the fan coil by the...

Reviews: