35
Fig. 40 — Service Configuration Selection Screen
Description
Value
Units
Name
Notes
2-Pipe Changeover
Disable
UNITTYPE
Fan Control
Fan Operation
1
FANOPR
0=Auto, 1=Continuous
# Fan Speeds (1-3)
3
FAN_TYPE
Fan PID
Proportional Gain
10.0
KP
Integral Gain
3.0
KI
Derivative
0.0
KD
Starting Value
0.0
%
STARTVAL
Cooling Type
0
COOL_TYP
1=Mod, 2=2-Pos, 3=DX
Cooling PID
Proportional Gain
8.0
KP
Integral Gain
0.3
KI
Derivative Gain
0.0
KD
Starting Value
65.0
dF
STARTVAL
Staged Cooling
Number of Stages
1
STAGES
Stage 1 Time Gard
Enable
TG1
Stage 2 Time Gard
Disable
TG2
2-Pos Valve Logic Type
Normal
CLT1
Stage 2 DX Logic Type
Normal
CLT2
Heating Type
0
HEAT_TYP
1=Mod, 2=2 Pos, 3=Elec
4=2-Pipe Chg w/Elec Ht
Heating PID
Proportional Gain
8.0
KP
Integral Gain
0.3
KI
Derivative Gain
0.0
KD
Starting Value
80.0
dF
STARTVAL
Fan Off Value
55.0
dF
HCROV
Staged Heating
Number of Stages
2
STAGES
2-Pos Valve Logic Type
Normal
HLT1
2-Position Damper
No
DMP
Air Quality
AQ Low Voltage
0.0
Volts
AQINLO
AQ High Voltage
10.0
Volts
AQINHI
AQ Low Reference (PPM)
0.0
AQLO
AQ High Reference (PPM)
2000.0
AQHI
Filter Timer hrs * 100
15
FIL_TIMR
Condensate Pump Timer
10
min
CPTIMR
Space Temp Trim
0.0
^F
RATTRIM
Supply Air Temp Trim
0.0
^F
SATTRIM
1001
→