HEAT MASTER REFERENCE — The Heat Master Refer-
ence point displays the occupied low set point, if occupied, or
the unoccupied low set point, if unoccupied. The set point off-
set (if applicable) is calculated into the value.
Heat Master
Reference:
Display Units
degrees F (degrees C)
Display Range
40.0 to 90.0
Default Value
70.0
Network Access Read Only
HEAT SUBMASTER REFERENCE — If heat is enabled,
the Heat Submaster Reference point displays the desired sup-
ply air temperature calculated to heat the space. This is a result
of the heating PID loop calculation.
Heat Submaster
Reference:
Display Units
degrees F (degrees C)
Display Range
35.0 to 140.0
Default Value
0
Network Access Read/Write
COOL MASTER REFERENCE — The Cool Master Refer-
ence point displays the occupied high set point, if mode is oc-
cupied, or the unoccupied high set point if mode is unoccupied.
The set point offset (if applicable) is calculated into the value.
Cool Master
Reference:
Display Units
degrees F (degrees C)
Display Range
45.0 to 99.9
Default Value
74.0
Network Access Read Only
COOL SUBMASTER REFERENCE — If cooling is en-
abled, the Cool Submaster Reference point displays the de-
sired supply air temperature calculated to cool the space. This
is a result of the cooling PID loop calculation.
Cool Submaster
Reference:
Display Units
degrees F (degrees C)
Display Range
40.0 to 150.0
Default Value
0
Network Access Read/Write
COOLING
IN
EFFECT
—
The Cooling In Effect point
shows if there is a demand for cooling in the space. The space
temperature must be above the Occupied High or Unoccupied
High set point.
Cooling in Effect: Display Range
No/Yes
Default Value
No
Network Access None
HEATING IN EFFECT — The Heating In Effect point shows
if there is a demand for heat in the space. The space tempera-
ture must be below the Occupied Low or Unoccupied Low set
point.
Heating in Effect: Display Range
No/Yes
Default Value
No
Network Access None
REHEAT IN EFFECT — The Reheat in Effect point shows if
the fan coil is in a dehumidification mode and attempting to re-
heat the dehumidified air to maintain the space temperature. If
Reheat is enabled, the zone controller will fully open the cool-
ing valve, if the space temperature is above the heating set
point. Simultaneously, it will modulate the heating valve to
raise or maintain the space temperature at the configured occu-
pied cooling set point during dehumidification.
Reheat in Effect: Display Range
No/Yes
Default Value
No
Network Access None
FAN SPEED — The Fan Speed point displays the current fan
speed (in percentage).
Fan Speed:
Display Units
%
Display Range
0 to 100
Default Value
0
Network Access None
FAN SPEED MEDIUM — The Fan Speed Medium point
displays whether the medium fan speed is on or off.
Fan Speed
Medium:
Display Range
Off/On
Default Value
Off
Network Access Read/Write
FAN SPEED HIGH — The Fan Speed High point displays
whether the high fan speed is on or off.
Fan Speed High: Display Range
Off/On
Default Value
Off
Network Access Read/Write
CHANGEOVER TEMPERATURE — The Changeover Tem-
perature point displays the value from the changeover sensor
(water temperature sensor attached to the two-pipe water loop)
for the fan coil. The Changeover Temperature value is forcible.
It may be received through CCN from a Comfort Controller
that monitors the water loop temperature and provides control
of boilers and/or chillers.
Changeover
Temperature:
Display Units
degrees F (degrees C)
Display Range
–40.0 to 245.0
Default Value
–40.0
Network Access Read/Write
CHANGEOVER STATUS — Applicable to two-pipe heating/
cooling systems, the Changeover Status point determines
whether the temperature indicated by the changeover sensor
will allow the fan coil to provide heating or cooling operation.
The value is determined from the changeover temperature sen-
sor reading as:
<65 F = COOL
>80 F = HEAT
between 65 and 80 = last active status
Changeover Status is forcible. It may be received through
CCN from a Comfort Controller which monitors and maintains
the water loop temperature.
NOTE: This value defaults to HEAT if a changeover sensor
failure occurs or for non-changeover systems.
Changeover
Status:
Display Range
Heat/Cool
Default Value
Heat
Network Access Read/Write
LINKAGE THERMOSTAT — The following Linkage Ther-
mostat points display the standard values received from a Link-
age Thermostat (if one is being used to provide space tempera-
ture, set point and occupancy information) for this fan coil.
The Linkage Status point displays the status of the linkage
broadcasts from the Linkage Thermostat. A value of 0 is nor-
mal communication. A value of 1 is communication failure. A
value of 2 is not configured. A value of 3 is a change in com-
munication status between supervisory and equipment.
Linkage Status:
Display Range
0 to 3
Default Value
2
Network Access None
The Average Occupied Heat Set Point displays the Occu-
pied Heat set point from the Linkage Thermostat.
Average Occupied
Heat Set Point:
Display Units
degrees F (degrees C)
Display Range
0.0 to 99.9
Default Value
0.0
Network Access None