background image

19

Perform the following steps if state or local code requires

the use of conduit, or if your installation requires a cable length

of more than 8 ft:

1. Secure the probe to the fan coil unit with two field-

supplied self-drilling screws.

2. If you are extending cable length beyond 8 ft, use ple-

num rated, 20 AWG, twisted pair wire.

3. Connect the sensor leads to the fan coil controller’s

wiring harness terminal board at the terminals labeled

SAT (RED) and GND (BLK).

4. Neatly bundle and secure excess wire.

INDOOR AIR QUALITY SENSOR INSTALLATION —

The indoor air quality (IAQ) sensor accessory monitors carbon

dioxide levels. This information is used to monitor IAQ levels.

Three types of sensors are provided. The wall sensor can be

used to monitor the conditioned air space. Sensors use infrared

technology to measure the levels of CO

2

 present in the air. The

wall sensor is available with or without an LCD readout to dis-

play the CO

2

 level in ppm. See Fig. 23.

Sensor accessory descriptions and part numbers are shown

in Table 2. To mount the sensor, refer to the installation instruc-

tions shipped with the accessory kit.

Table 2 — CO

2

 Sensor Accessories

The CO

2

 sensors listed in Table 2 are all factory set for a

range of 0 to 2000 ppm and a linear voltage output of 0 to

10 vdc. Refer to the instructions supplied with the CO

2

 sensor

for electrical requirements and terminal locations.

To accurately monitor the quality of the air in the condi-

tioned air space, locate the sensor near a return air grille (if

present) so it senses the concentration of CO

2

 leaving the

space. The sensor should be mounted in a location to avoid

direct breath contact.

Do not mount the IAQ sensor in drafty areas such as near

supply ducts, open windows, fans, or over heat sources. Allow

at least 3 ft between the sensor and any corner. Avoid mounting

the sensor where it is influenced by the supply air; the sensor

gives inaccurate readings if the supply air is blown directly

onto the sensor or if the supply air does not have a chance

to mix with the room air before it is drawn into the return

air-stream.
Indoor Air Quality Sensor Wiring — To wire the sensors

after they are mounted in the conditioned air space or outdoor

location, see Fig. 24 and the instructions shipped with the sen-

sors. For each sensor, use two 2-conductor 18 AWG twisted-

pair cables (unshielded) to connect the separate isolated 24 vac

power source to the sensor and to connect the sensor to the con-

trol board terminals. To connect the sensor to the control board,

identify the positive (0-10 VDC) and ground (SIG COM) ter-

minals on the sensor. Connect the 1-10 VDC terminal to termi-

nal IAQ and connect the SIG COM terminal to terminal GND.
HUMIDITY SENSOR (WALL-MOUNTED) INSTALLA-

TION —  The accessory space humidity sensor is installed on

an interior wall to measure the relative humidity of the air with-

in the occupied space. See Fig. 25.

The use of a standard 2- x 4-in. electrical box to accommo-

date the wiring is recommended for installation. The sensor can

be mounted directly on the wall, if acceptable by local codes.

If the sensor is installed directly on a wall surface, install the

humidity sensor using 2 screws and 2 hollow wall anchors

(field-supplied); 

do not overtighten screws.

 See Fig. 15.

The sensor must be mounted vertically on the wall. The

Carrier logo should be oriented correctly when the sensor is

properly mounted.

DO NOT mount the sensor in drafty areas such as near heat-

ing or air-conditioning ducts, open windows, fans, or over heat

sources such as baseboard heaters, radiators, or wall-mounted

light dimmers. Sensors mounted in those areas will produce in-

accurate readings.

Avoid corner locations. Allow at least 4 ft between the sen-

sor and any corner. Airflow near corners tends to be reduced,

resulting in erratic sensor readings.

Sensor should be vertically mounted approximately 5 ft up

from the floor, beside the space temperature sensor.

For distances up to 500 feet, use a 3-conductor, 18 or

20 AWG cable. A CCN communication cable can be used,

although the shield is not required. The shield must be removed

from the sensor end of the cable if this cable is used. See

Fig. 26 for wiring details.

The power for the sensor is provided by the control board.

The board provides 24 vdc for the sensor. No additional power

source is required.

To wire the sensor, perform the following:

1. At the sensor, remove 4-in. of jacket from the cable.

Strip 

1

/

4

-in. of insulation from each conductor. Route

the cable through the wire clearance opening in the

center of the sensor.

2. Connect the RED wire to the sensor screw terminal

marked (+). 

3. Install one lead from the resistor (supplied with the

sensor) and the WHITE wire, into the sensor screw ter-

minal marked (–). After tightening the screw terminal,

test the connection by pulling gently on the resistor

lead.

4. Connect the remaining lead from the resistor to the

BLACK wire and secure using a field-supplied closed

end type crimp connector or wire nut.

CO

2

 SENSOR

ACCESSORY

PART NUMBERS

DESCRIPTION

33ZCSENCO2

Wall Mount Sensor (with display)

33ZCT55CO2

Wall Mount Sensor with 
33ZCT55SPT space temperature 
sensor (no display)

33ZCT56CO2

Wall Mount Sensor with 
33ZCT56SPT space temperature 
sensor and set point adjustment (no 
display)

Do NOT clean or touch the sensing element with chemical

solvents; they can permanently damage the sensor.

3.25
(8.3)

5.625
(14.3)

1.125

(2.9)

0.25

(0.8)

5

(12.7)

NOTE: Dimensions are in inches.
Dimensions in (   ) are in centimeters.

Fig. 23 — Indoor Air Quality (CO

2

) Sensor 

(33ZCSENCO2)

1001

Summary of Contents for 33ZCFANCOL

Page 1: ...n 43 SAFETY CONSIDERATIONS GENERAL The Fan Coil Controller is a field retrofit low cost CCN Carrier Comfort Network control for fan coil units The fan coil controller is a microprocessor based direct...

Page 2: ...The 33ZCSENCHG change over sensor is used by the fan coil controller in 2 pipe applica tions to determine the temperature of the heating and cooling medium which is supplied to the fan coil by the bui...

Page 3: ...SECONDARY BUS DATA COLLECTION OPTION BRIDGE RECOMMENDED SYSTEM MONITORING SOFTWARE CCN FAN COIL CONTROLLER TYPICAL FAN COIL UNIT FAN COIL CONTROLLER TYPICAL FAN COIL UNIT FULLY CCN COMPATIBLE CARRIER...

Page 4: ...rs are required for electric heat then it is recommended a 60 va transformer be used The maximum rating for any single output is 20 va NOTE Do not run sensor or communication wiring in the same condui...

Page 5: ...or Setpoint Adjustment GND M BLU L RED H BLK WHT valve 24VAC DX2 Valve Equipment Ground Transformer Ground Fan Relay Fan Motor Voltage Line Voltage Line ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56...

Page 6: ...HG SPT BLK M BLU L RED H BLK WHT Valve 24VAC DX2 Valve Transformer Ground Fan Relays Fan Motor Voltage Line Voltage Line M SAT ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND...

Page 7: ...M BLU L RED H BLK WHT CWV 24VAC DX2 Valve Transformer Ground Fan Relay HWV Fan Motor Voltage Line Voltage Line M SAT SPT ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND GND...

Page 8: ...BLU L RED H BLK WHT CWV 24VAC DX2 Valve Transformer Ground Fan Relays HWV Fan Motor Voltage Line Voltage Line M SAT ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND GND GND GN...

Page 9: ...HEAT1 DX2 DX1 Cool Relays Heat Relays BLK M BLU L RED H BLK WHT 24VAC DX2 Valve Transformer Ground Fan Relays Fan Motor Voltage Line Voltage Line ON FAN HEAT2 HEAT1 COM CONDSW CNGOVR T56 SAT SPT IAQ...

Page 10: ...s Fan Motor Voltage Line Voltage Line M SAT ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND GND GND GND GND RH Damper Air Fresh HIGH MED LOW FAN AC B W R B GND W R 24 VAC DX1...

Page 11: ...an Motor Voltage Line Voltage Line M SAT ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND GND GND GND GND RH Damper Air Fresh HIGH MED LOW FAN AC B W R B GND W R 24 VAC DX1 Va...

Page 12: ...er Board Outputs J6 J7 For single speed fan units connect fan start stop to control fan contactor NOTE J6 1 must be jumpered to 24 VAC J1 1 CHANNEL TERMINATIONS DESCRIPTION CONTROL DEVICE FAN AC J6 1...

Page 13: ...he sensor to the electrical box NOTE Sensor may also be mounted directly on the wall using 2 plastic anchors and 2 sheet metal screws field supplied 6 Use 20 gage wire to connect the sensor to the con...

Page 14: ...he CCN Network Communication Service Jack See Fig 16 18 To wire the service jack perform the following 1 Strip back the jacket from the CCN communication cable s for at least 3 inches Strip 1 4 in of...

Page 15: ...32 32 651 5 41 25 395 10 50 19 903 15 59 15 714 20 68 12 494 25 77 10 000 30 86 8 056 35 95 6 530 40 104 5 325 45 113 4 367 50 122 3 601 55 131 2 985 60 140 2 487 65 149 2 082 70 158 1 752 2 3 4 5 6 1...

Page 16: ...of the supply air temperature during heating and cooling For fan coils using a ducted supply the supply air tempera ture sensor should be located in the supply duct downstream of the discharge of the...

Page 17: ...arm Cool Warm Cool 2 COND TWISTED CABLE OR 3 COND CABLE TEMP SENSOR WIRING TYP SPACE TEMPERATURE SENSOR DISTANCE GREATER THAN 50 FT CCN COMM BUS TYPICAL FAN COIL UNIT FAN COIL ZONE CONTROLLER 50 FT MA...

Page 18: ...PROX 2 FT SUPPLY AIR SENSOR SUPPLY DUCT TYPICAL FAN COIL UNIT 3 00 1 50 0 50 CLEARANCE HOLE ENGAGEMENT HOLE FOR 10 SHEET METAL SCREW 2 Fig 20 Supply Air Temperature Sensor Part Number 33ZCSENSAT Fig 2...

Page 19: ...t the SIG COM terminal to terminal GND HUMIDITY SENSOR WALL MOUNTED INSTALLA TION The accessory space humidity sensor is installed on an interior wall to measure the relative humidity of the air with...

Page 20: ...OM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND GND GND GND GND RH Damper Air Fresh HIGH MED LOW FAN AC B W R B GND W R 24 VAC DX1 Valve communications CCN Not Used communications CCN LINE VOLTA...

Page 21: ...in the applicable wiring diagrams in Fig 4 10 Connect Accessories Refer to accessory installa tion instructions for installation procedures Fan coil controller wiring is shown for the following acces...

Page 22: ...K RED GREEN WHITE GND BLACK RED GREEN WHITE GND SHIELD WIRENUT SHIELD COMMUNICATION BUS WHT RED MAXIMUM WIRE LENGTH OF 100 FT LINKAGE THERMOSTAT WIRING CONNECTION BLOCK POWER SUPPLY BOARD W R WHT RED...

Page 23: ...GND GND GND GND GND RH Damper Air Fresh HIGH MED LOW FAN AC B W R B GND W R 24 VAC DX1 Valve communications CCN Not Used communications CCN 10 uf 25VDC Fig 28 Condensate Pump Switch Wiring NOTE To ens...

Page 24: ...24V DC Equipment Ground 24VAC DX2 Valve Voltage Line ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND GND GND GND GND RH Damper Air Fresh HIGH MED LOW FAN AC B W R B GND W R 2...

Page 25: ...nications CCN Not Used communications CCN J1 1 2 3 24V DC OAD 24VAC Equipment Ground 24VAC DX2 Valve Voltage Line ON FAN HEAT2 HEAT1 COM CONDSW RMT FS CNGOVR T56 SAT SPT IAQ SPEED 10V GND GND GND GND...

Page 26: ...and an outer jacket of PVC PVC nylon chrome vinyl or Teflon with a minimum operating temperature range of 20 C to 60 C is required CONNECTION TO THE COMMUNICATION BUS 1 Strip the ends of the red white...

Page 27: ...oling operation can be tested with the fan running in the occupied mode by forcing the space temperature point Force the point to a value 2 degrees above the cooling set point to test cooling and 2 de...

Page 28: ...operating mode for two pipe heating cooling fan coil units This point will display and follow the value of the Changeover Status after a 5 minute delay Upon a transition of the Changeover Status the...

Page 29: ...ead Write see note NOTE Force both cooling or heating outputs off prior to forc ing either input on Then force only one heating or cooling out put on at a time HEATING 1 The Heating 1 point provides t...

Page 30: ...when more than one Fan Coil is connected to the network Fan Output Display Units Discrete ASCII Default Value Off Display Range Off On Network Access Read Write Alarm Service Configuration Table The...

Page 31: ...The Start Day field is used to determine which day the holiday will start Start Day Range 1 to 31 Default Value 1 DURATION The Duration field indicates how long the holiday will last in days Duration...

Page 32: ...II Range 8 characters Bldg Spvr 96 characters LID 6400 32 characters LID 1600 Default Value SENSDI00 POINT n TYPE The Point n Type set point specifies whether the discrete point being monitored is a n...

Page 33: ...Configuration Screen Fig 38 Runtime Configuration Screen Description Value Units Name Notes Point n Name n 1 to 16 Text String PTnNAME n 1 to 16 Point n Type n 1 to 16 Bldg Spvr Normal Invert LID X PT...

Page 34: ...umber of Fan Speeds 1 3 Range 0 to 3 Default Value 3 AUTOMATIC FAN SPEED CONTROL Automatic fan speed control is based on a PID control which calculates the fan speed as a value between 0 and the Maxim...

Page 35: ...me Gard Enable TG1 Stage 2 Time Gard Disable TG2 2 Pos Valve Logic Type Normal CLT1 Stage 2 DX Logic Type Normal CLT2 Heating Type 0 HEAT_TYP 1 Mod 2 2 Pos 3 Elec 4 2 Pipe Chg w Elec Ht Heating PID Pr...

Page 36: ...e actual supply air temperature and the output is then adjusted to satisfy conditions A Proportional Integral Derivative PID loop is used The modulating con trol function compares the submaster refere...

Page 37: ...llion implied Range 0 to 5000 Default Value 2000 FILTER TIMER HOURS The Filter Timer Hours config uration determines when the filter status will display a Dirty alarm When the Filter Timer Hours is co...

Page 38: ...The Temp Sensor Config is used to specify if the controller is sharing the space temperature only space temperature with temperature offset slidebar or space temperature temperature offset slidebar an...

Page 39: ...schedule broadcast The point will display a 0 for unoccupied and a 1 for occupied Mode Display Range 0 to 1 Default Value 0 Network Access None CURRENT OCCUPIED PERIOD If the fan coil is con figured t...

Page 40: ...point displays the time of day when the fan coil last changed from occupied to the Unoccupied mode This point is read in conjunction with the Last Unoccupied Day to know the last time and day when the...

Page 41: ...41 Fig 43 Fan Coil Maintenance Table Screen...

Page 42: ...Display Range No Yes Default Value No Network Access None FAN SPEED The Fan Speed point displays the current fan speed in percentage Fan Speed Display Units Display Range 0 to 100 Default Value 0 Netw...

Page 43: ...Source Status decisions continue to display their last valid data Cooling Link Active Display Units Yes No Default Value No HEATING LINK ACTIVE The Heating Link Active deci sion displays the status of...

Page 44: ...l Cool Source Status Display Units On Off Default Value Off HOT WATER TEMPERATURE This decision displays the current leaving water temperature at the heat source that is linked to the fan coil by the...

Reviews: