background image

8

2.1 - Check equipment received

 

-

Inspect the unit for damage or missing parts. If damage is 

detected, or if shipment is incomplete, immediately file a claim 

with the shipping company.

 

-

Confirm that the unit received is the one ordered. Compare 

the name plate data with the order.

 

-

The unit name plate must include the following information:
• Version number
• Model number
• CE marking
• Serial number 
• Year of manufacture and test date
• Fluid being transported
• Refrigerant used and refrigerant class
• Refrigerant charge per circuit
• 

Containment fluid to be used

• PS: Min./max. allowable pressure (high and low pressure 

side)

• TS: Min./max. allowable temperature (high and low pressure 

side)

• Pressure switch cut-out pressures
• Unit leak test pressure
• Voltage, frequency, number of phases
• Maximum current drawn
• Maximum power input
• Unit net weight

 

-

Confirm that all accessories ordered for on-site installation 

have been delivered, and are complete and undamaged.

The  unit  must  be  checked  periodically  during  its  whole 

operating life to ensure that no shocks (handling accessories, 

tools etc.) have damaged it. If necessary, the damaged parts 

must be repaired or replaced. See also chapter 13 “Standard 

maintenance”.

2.2 - Moving and siting the unit

2.2.1 - Moving

See chapter 1.1 “Installation safety considerations”.

CAUTION: 
Only use slings at the designated lifting points which are 

marked on the unit.

2.2.2 - Siting the unit

Always refer to the chapter “Dimensions and clearances” to confirm 

that there is adequate space for all connections and service 
operations. For the centre of gravity coordinates, the position of the 
unit mounting holes, and the weight distribution points, refer to the 

certified dimensional drawing supplied with the unit.

Typical applications of these units are in refrigeration systems, 
and they do not require earthquake resistance. Earthquake 

resistance has not been verified.

Before siting the unit check that:

 

-

the permitted loading at the site is adequate or that 
appropriate strenghtening measures have been taken.

 

-

the unit is installed level on an even surface (maximum 
tolerance is 5 mm in both axes).

 

-

there is adequate space above the unit for air flow and to 

ensure access to the components.

 

-

the number of support points is adequate and that they are 
in the right places.

 

-

the location is not subject to flooding.

CAUTION: 
Lift and set down the unit  with great care. Tilting and jarring 

can damage the unit and impair unit operation.

2.2.3 - Checks before system start-up

Before the start-up of the refrigeration system, the complete 

installation,  including  the  refrigeration  system  must  be  verified 

against the installation drawings, dimensional drawings, system 
piping and instrumentation diagrams and the wiring diagrams.
During the installation test national regulations must be followed. 
If no national regulation exists, standard EN 378 or ISO-5149 can 
be used as a guide.
External visual installation checks:

 

-

Ensure that the machine is charged with refrigerant. Verify on 

the unit nameplate that the ‘fluid being transported’ is R-134a 

and is not nitrogen.

 

-

Compare the complete installation with the refrigeration system 
and power circuit diagrams.

 

-

Check that all components comply with the design 

specifications.

 

-

Check that all protection documents and equipment provided 
by the manufacturer (dimensional drawings, P&ID, declarations 
etc.) to comply with the regulations are present.

 

-

Verify that the environmental safety and protection and devices 
and arrangements provided by the manufacturer to comply with 
the regulations are in place.

 

-

Verify that all document for pressure containers, certificates, 

name plates, files, instruction manuals provided by the 
manufacturer to comply with the regulations are present.

 

-

Verify the free passage of access and safety routes.

 

-

Check that ventilation in the plant room is adequate.

 

-

Check that refrigerant detectors are present.

 

-

Verify the instructions and directives to prevent the deliberate 
removal of refrigerant gases that are harmful to the 
environment.

 

-

Verify the installation of connections.

 

-

Verify the supports and fixing elements (materials, routing 

and connection).

 

-

Verify the quality of welds and other joints.

 

-

Check the protection against mechanical damage.

 

-

Check the protection against heat.

 

-

Check the protection of moving parts.

 

-

Verify the accessibility for maintenance or repair and to check 
the piping.

 

-

Verify the status of the valves.

 

-

Verify the quality of the thermal insulation and of the vapour 
barriers.

2 - PRELIMINARY CHECKS

Summary of Contents for 19PV550

Page 1: ...INSTALLATION OPERATION AND M A I N T E N A N C E I N S T R U C T I O N S Original document Original document 19PV Nominal cooling capacity 550 1600 kW 50Hz...

Page 2: ...mber of water passes 18 6 6 Min water volume and evaporator condenser water flow rates 18 6 7 Variable flow evaporator 18 6 8 Evaporator pressure drop curves 19 7 WATER CONNECTIONS 20 7 1 Operating pr...

Page 3: ...fer to the 19PV Touch Pilot Control manual CONTENT 12 OPTIONS 28 13 STANDARD MAINTENANCE 29 13 1 Level 1 maintenance 29 13 2 Level 2 maintenance 29 13 3 Level 3 or higher maintenance 29 13 4 Tightenin...

Page 4: ...ressure switches Ensure that the valves are correctly installed before operating the unit Classification and control In accordance with the Pressure Equipment Directive and national usage monitoring r...

Page 5: ...own with the liquid line valve closed as liquid refrigerant can be trapped between this valve and the expansion device This valve is situated on the liquid line before the filter drier box Equip the e...

Page 6: ...ser water flow Check the cut off value Reactivate manually HP switch and reactivate HP soft value Repeat the procedure for each unit compressor CAUTION If the test leads to replacing the pressure swit...

Page 7: ...sfer station The units must never be modified to add refrigerant removal and purging devices All these devices are provided with the units Please refer to the certified dimensional drawings for the un...

Page 8: ...or air flow and to ensure access to the components the number of support points is adequate and that they are in the right places the location is not subject to flooding CAUTION Lift and set down the...

Page 9: ...positioning of the fixing points weight distribution and centre of gravity coordinates please refer to the dimensional drawings Dimension mm A B C D 19PV 550 3045 1120 1745 2800 720 3070 1155 1846 28...

Page 10: ...positioning of the fixing points weight distribution and centre of gravity coordinates please refer to the dimensional drawings Dimension mm A B C D 19PV 900 4257 1290 1955 3950 1010 4257 1290 1955 3...

Page 11: ...positioning of the fixing points weight distribution and centre of gravity coordinates please refer to the dimensional drawings Dimension mm A B C D 19PV 1300 4705 1290 1955 4400 1450 4740 1290 2011...

Page 12: ...on valves EXV Minimum capacity 15 15 15 10 10 10 10 10 10 Evaporator Flooded multi pipe type Water volume l 115 165 180 285 285 285 330 330 365 Water connections Victaulic in 6 6 8 8 8 8 8 8 8 Drain a...

Page 13: ...with option 81 A 387 456 565 570 635 753 Maximum start up current Un Standard unit 3 Lower than max current Dissipated power of electrical equipment 1 W 782 1249 1249 1144 1347 1814 1884 2351 2351 1 V...

Page 14: ...power supply conductors is not provided with the unit 5 The factory installed disconnect switch es circuit breaker s are of a type suitable for power interruption in accordance with EN 60947 3 corres...

Page 15: ...This is less than the permissible 2 and is therefore acceptable 5 3 Power connection disconnect switch Units Connection points 19PV550 to 800 1 per unit 19PV900 to 1600 1 for circuit A 1 for circuit...

Page 16: ...selection Note Option 84 and 84R are not included in these values 5 5 Power cable entry The power cables can enter the 19PV control box from above the unit A removable aluminium plate on the upper par...

Page 17: ...er temperature C Condenser leaving water temperature C 10 20 30 40 50 0 5 10 15 20 6 2 Minimum chilled water flow The minimum chilled water flow is shown in the table in chapter 6 7 If the system flow...

Page 18: ...ndenser water flow rate m3 h Minimum 2 21 21 36 36 36 36 36 36 36 Maximum 3 245 299 346 486 457 454 428 594 526 1 Minimum evaporator flow rate based on a water velocity of 0 5 m s 2 Minimum condenser...

Page 19: ...FG H I J Legend 1 19PV550 6 19PV1180 2 19PV720 7 19PV1300 3 19PV800 8 19PV1450 4 19PV900 9 19PV1600 5 19PV1010 6 9 Condensor pressure drop curves Units with two condenser passes standard Pressure dro...

Page 20: ...the design operating pressures Before any start up verify that the heat exchange fluid is compatible with the materials and the water circuit coating The use of different metals on hydraulic piping co...

Page 21: ...1 219 1 219 1 219 1 219 1 219 1 7 3 Flow control Evaporator flow switch and chilled water pump interlock IMPORTANT On 19PV units the unit water flow switch must be energised Failure to follow this in...

Page 22: ...its own water pump If there is only one common pump in cases with variable flow isolation valves must be installed on each unit They will be activated at the opening and closing by the control of eac...

Page 23: ...mensions clearances are the same as standard 19PV units Unlike in the cooling mode the unit uses the heating setpoint in this configuration The evaporator leaving water control lowest setpoint taken i...

Page 24: ...ital outputs permitting control of up to eight fan stages 9 3 Configuration of the number of fan stages and the automatic changeover of the fan stages Please refer to the instructions in the Touch Pil...

Page 25: ...o communicate and control the drycooler The drycooler with option 313 AUX board with the I O OAT sensor to be place in outdoor zone Dry Cooler Leaving Water Temperature factory mounted Water loop Temp...

Page 26: ...compressor to reduce broadcasting of the noise radiated emissions from the power lines themselves 11 1 6 Fast acting fuses All compressors are fitted with class T fast acting fuses to protect the soli...

Page 27: ...sm module and an under voltage protection circuit are mounted on the main supply disconnect switch Note The following procedure must be done to lock the main supply disconnect switch Set the motor mec...

Page 28: ...management system Allows access to multiple unit parameters 0550 1600 Control for low cond temperature 152 Output signal 0 10 V to control the condenser water inlet valve Simple installation for appli...

Page 29: ...r see chapter 7 Water connections Check the unit operating parameters and compare them with previous values Replace compressor capacitors every 10 years if energized or 5 years if de energized Replace...

Page 30: ...e flanges 22 Brass fitting TT300 Motor cooling brass fitting 40 Brass fitting TT350 Motor cooling brass fitting 50 Phillips head screw Compressor cover plate 13 H M8 Screw Drier cover 35 H M10 Screw C...

Page 31: ...Electrical circuit wiring has been sized and installed properly Unit ground wire has been connected Electrical circuit protection has been sized and installed properly All terminals are tight All chil...

Page 32: ...l kW capacity for air conditioning 6 5 litres nominal kW capacity for process cooling Proper loop volume established Proper loop corrosion inhibitor included litres of Proper loop freeze protection in...

Page 33: ...33...

Page 34: ...Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the European Union CARRIER participates in the ECP programme for LCP HP Check...

Reviews: