background image

25

10 - UNIT OPERATION WITH OPTION 313

10.1 - Operating principle

The units have been designed to optimize the operation of 
systems, using drycoolers as free cooling system (method using 
low outdoor air temperature to chill the water of the air conditioning 
system).
This system allows substantial energy and cost savings, which is 
the most effective when the outdoor air temperature is low.
The Touch'Pilot control of the unit includes algorithms to permit 
constant automatic optimization of: 

 

-

drycooler fans operation

 

-

water flow rate variation in the loop 

 

-

cooling capacity  (drycooler and chiller can operate 
independently or simultaneously)

 

-

valves positions depending on operating  mode.

The control defines the optimal configuration considering water 

set point value, outdoor air temperature and water loop temperature 
(the control will give priority to the drycooler).

Parallel control of the fans and of the variable water flow rate of 

the loop permit system operation down to -20 °C outside 
temperature without any additional control.

Pay  attention  that  drycooler  and  chiller  have  to  be  both 

equipped with the option 313

Chiller

NO

NC

DC free cooling

LEN communication

OAT

V2V control

2

1

3

For an optimal free cooling operation, the chiller has to be 

configurated:

 

-

on entering water temperature control

 

-

on delta temperature control in case of variable speed pump

10.2 - Communication to control the drycooler

When the option is selected, a specific electronic board is 
integrated in the control box of the drycooler. A communication 
LEN bus connected between the drycooler (board AUX1) and the 
chiller  is needed  for the overall system control.
This cable should be a 3 points Wago type (5 mm spacing or 
equivalent) and should be shielded. 
The board integrated in the control box of the drycooler has analog 
inputs for outside air temperature (mark 1), return water loop 
temperature (mark 3)  and drycooler leaving water temperature 
sensors (mark 2), as well as digital outputs permitting the control 
of the fans.
The option works as a system split in two parts:

The chiller (with option 313)

 

-

Dedicated control algorithms with LEN connector to 
communicate and control the drycooler 

The drycooler (with option 313) :

 

-

AUX board with the I/O

 

-

OAT sensor to be place in outdoor zone.

 

-

Dry Cooler Leaving Water Temperature (factory mounted) 

 

-

Water loop Temperature (to be mounted on the common pipe 
before valve) 

 

-

Control & 230V power supply  for 2 two ways valve or one 
three ways valve

The temperature difference between dry-cooler OAT and water 

loop sensor defines if free cooling mode can be activated.

10.3 - Configuration of the fans control 

To set the configuration corresponding the drycooler installed (number 
of fans, control type – fixed or variable speed), please refer to the 

instructions in the Touch'Pilot control IOM. Following these 
parameters, the Touch'Pilot will activate the adequate number of 
digital outputs to control the fans.
Touch'Pilot controls the automatic switching of all fans, based on 
operating time and number of start-up, to ensure a long operating 
life of fan motors.

Compatible fans configuration:

 

-

1 to 20 fans

 

-

fixed speed or variable speed

 

-

fans in one l or 2 lines

Refer to the drycooler electrical diagram to see the fan stages 
arrangement.

10.4 - Water valves

The free cooling system requires 2 two-way valves (one Normally 
Opened, one Normally Closed) or a three-way valve, not supplied 
with the unit or the dry cooler. 
A two-way valves kit is  available in the list of drycooler accessories.
The drycooler electrical box includes 230V power supply for 2 
two-way valves.
Recommended motor valve (per default): 230V 3 points
Refer to drycooler electrical diagram for valves wiring on customer 
connections.

10.5 - System installations recommandation

For physical characteristics, dimensions, performances: refer to 
the drycooler documentation.
For electrical connections information, refer to the electrical wiring 
delivered with the drycooler.
For software configuration information, refer to the control 
documentation of the chiller.
For a proper drycooler installation, follow the professional 
guidelines for the following topics:

 

-

Water pipe sizing

 

-

Pressure drops (verify that the available pressure of the unit 

pump is sufficient compared to the piping and valves pressure 

drops  - check for all running modes)  

 

-

Maximum drycooler elevation (in relation to the unit safety 
valve) 

 

-

Good positioning for temperature sensors: outside air 
temperature and water loop temperature .

Summary of Contents for 19PV550

Page 1: ...INSTALLATION OPERATION AND M A I N T E N A N C E I N S T R U C T I O N S Original document Original document 19PV Nominal cooling capacity 550 1600 kW 50Hz...

Page 2: ...mber of water passes 18 6 6 Min water volume and evaporator condenser water flow rates 18 6 7 Variable flow evaporator 18 6 8 Evaporator pressure drop curves 19 7 WATER CONNECTIONS 20 7 1 Operating pr...

Page 3: ...fer to the 19PV Touch Pilot Control manual CONTENT 12 OPTIONS 28 13 STANDARD MAINTENANCE 29 13 1 Level 1 maintenance 29 13 2 Level 2 maintenance 29 13 3 Level 3 or higher maintenance 29 13 4 Tightenin...

Page 4: ...ressure switches Ensure that the valves are correctly installed before operating the unit Classification and control In accordance with the Pressure Equipment Directive and national usage monitoring r...

Page 5: ...own with the liquid line valve closed as liquid refrigerant can be trapped between this valve and the expansion device This valve is situated on the liquid line before the filter drier box Equip the e...

Page 6: ...ser water flow Check the cut off value Reactivate manually HP switch and reactivate HP soft value Repeat the procedure for each unit compressor CAUTION If the test leads to replacing the pressure swit...

Page 7: ...sfer station The units must never be modified to add refrigerant removal and purging devices All these devices are provided with the units Please refer to the certified dimensional drawings for the un...

Page 8: ...or air flow and to ensure access to the components the number of support points is adequate and that they are in the right places the location is not subject to flooding CAUTION Lift and set down the...

Page 9: ...positioning of the fixing points weight distribution and centre of gravity coordinates please refer to the dimensional drawings Dimension mm A B C D 19PV 550 3045 1120 1745 2800 720 3070 1155 1846 28...

Page 10: ...positioning of the fixing points weight distribution and centre of gravity coordinates please refer to the dimensional drawings Dimension mm A B C D 19PV 900 4257 1290 1955 3950 1010 4257 1290 1955 3...

Page 11: ...positioning of the fixing points weight distribution and centre of gravity coordinates please refer to the dimensional drawings Dimension mm A B C D 19PV 1300 4705 1290 1955 4400 1450 4740 1290 2011...

Page 12: ...on valves EXV Minimum capacity 15 15 15 10 10 10 10 10 10 Evaporator Flooded multi pipe type Water volume l 115 165 180 285 285 285 330 330 365 Water connections Victaulic in 6 6 8 8 8 8 8 8 8 Drain a...

Page 13: ...with option 81 A 387 456 565 570 635 753 Maximum start up current Un Standard unit 3 Lower than max current Dissipated power of electrical equipment 1 W 782 1249 1249 1144 1347 1814 1884 2351 2351 1 V...

Page 14: ...power supply conductors is not provided with the unit 5 The factory installed disconnect switch es circuit breaker s are of a type suitable for power interruption in accordance with EN 60947 3 corres...

Page 15: ...This is less than the permissible 2 and is therefore acceptable 5 3 Power connection disconnect switch Units Connection points 19PV550 to 800 1 per unit 19PV900 to 1600 1 for circuit A 1 for circuit...

Page 16: ...selection Note Option 84 and 84R are not included in these values 5 5 Power cable entry The power cables can enter the 19PV control box from above the unit A removable aluminium plate on the upper par...

Page 17: ...er temperature C Condenser leaving water temperature C 10 20 30 40 50 0 5 10 15 20 6 2 Minimum chilled water flow The minimum chilled water flow is shown in the table in chapter 6 7 If the system flow...

Page 18: ...ndenser water flow rate m3 h Minimum 2 21 21 36 36 36 36 36 36 36 Maximum 3 245 299 346 486 457 454 428 594 526 1 Minimum evaporator flow rate based on a water velocity of 0 5 m s 2 Minimum condenser...

Page 19: ...FG H I J Legend 1 19PV550 6 19PV1180 2 19PV720 7 19PV1300 3 19PV800 8 19PV1450 4 19PV900 9 19PV1600 5 19PV1010 6 9 Condensor pressure drop curves Units with two condenser passes standard Pressure dro...

Page 20: ...the design operating pressures Before any start up verify that the heat exchange fluid is compatible with the materials and the water circuit coating The use of different metals on hydraulic piping co...

Page 21: ...1 219 1 219 1 219 1 219 1 219 1 7 3 Flow control Evaporator flow switch and chilled water pump interlock IMPORTANT On 19PV units the unit water flow switch must be energised Failure to follow this in...

Page 22: ...its own water pump If there is only one common pump in cases with variable flow isolation valves must be installed on each unit They will be activated at the opening and closing by the control of eac...

Page 23: ...mensions clearances are the same as standard 19PV units Unlike in the cooling mode the unit uses the heating setpoint in this configuration The evaporator leaving water control lowest setpoint taken i...

Page 24: ...ital outputs permitting control of up to eight fan stages 9 3 Configuration of the number of fan stages and the automatic changeover of the fan stages Please refer to the instructions in the Touch Pil...

Page 25: ...o communicate and control the drycooler The drycooler with option 313 AUX board with the I O OAT sensor to be place in outdoor zone Dry Cooler Leaving Water Temperature factory mounted Water loop Temp...

Page 26: ...compressor to reduce broadcasting of the noise radiated emissions from the power lines themselves 11 1 6 Fast acting fuses All compressors are fitted with class T fast acting fuses to protect the soli...

Page 27: ...sm module and an under voltage protection circuit are mounted on the main supply disconnect switch Note The following procedure must be done to lock the main supply disconnect switch Set the motor mec...

Page 28: ...management system Allows access to multiple unit parameters 0550 1600 Control for low cond temperature 152 Output signal 0 10 V to control the condenser water inlet valve Simple installation for appli...

Page 29: ...r see chapter 7 Water connections Check the unit operating parameters and compare them with previous values Replace compressor capacitors every 10 years if energized or 5 years if de energized Replace...

Page 30: ...e flanges 22 Brass fitting TT300 Motor cooling brass fitting 40 Brass fitting TT350 Motor cooling brass fitting 50 Phillips head screw Compressor cover plate 13 H M8 Screw Drier cover 35 H M10 Screw C...

Page 31: ...Electrical circuit wiring has been sized and installed properly Unit ground wire has been connected Electrical circuit protection has been sized and installed properly All terminals are tight All chil...

Page 32: ...l kW capacity for air conditioning 6 5 litres nominal kW capacity for process cooling Proper loop volume established Proper loop corrosion inhibitor included litres of Proper loop freeze protection in...

Page 33: ...33...

Page 34: ...Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the European Union CARRIER participates in the ECP programme for LCP HP Check...

Reviews: