background image

5

1 - INTRODUCTION

These  pipes  must  be  installed  in  a  way  that  ensures  that 

people and property are not exposed to refrigerant leaks. 

These fluids may be diffused in the air, but far away from any 

building air intake, or they must be discharged in a quantity 

that is appropriate for a suitably absorbing environment.

It is recommended to install an indicating device to show if 

part of the refrigerant has leaked from the valve.

The calibration of a valve that has leaked is generally lower 

than its original calibration. The new calibration may affect 

the operating range. To avoid a nuisance tripping or leaks, 

replace or re-calibrate the valve.

Periodic check of the relief valves: See paragraph 1.3 

“Maintenance safety considerations”.
Provide a drain in the discharge circuit, close to each relief 

valve, to avoid an accumulation of condensate or rain water. 
Ensure good ventilation, as accumulation of refrigerant in an 

enclosed space can displace oxygen and cause asphyxiation 

or explosions.
Inhalation of high concentrations of vapour is harmful and 

may cause heart irregularities, unconsciousness, or death. 

Vapour is heavier than air and reduces the amount of oxygen 

available for breathing. These products cause eye and skin 

irritation. Decomposition products are hazardous.

1.2 - Equipment and components under pressure

The units are intended to be stored and operate in an environment 
where the ambient temperature must not be less than the lowest 
allowable temperature indicated on the nameplate. See section 
“11.2 - Pressure vessels”.

1.3 - Maintenance safety considerations

The manufacturer recommends the following drafting for a logbook 
(the table below should not be considered as reference and does 
not involve manufacturer responsibility):

Intervention

Name of the 

commissioning 

engineer

Applicable 

national 

regulations

Verification 

Organism

Date

Nature

 (1)

(1)  Maintenance, repairs, regular verifications (EN 378), leakage, etc.

Engineers working on the electric or refrigeration components 

must be authorized, trained and fully qualified to do so.

All refrigerant circuit repairs must be carried out by a trained person, 

fully qualified to work on these units. He must have been trained 

and be familiar with the equipment and the installation. All welding 

operations must be carried out by qualified specialists.

The insulation must be removed and heat generation must be 
limited by using a wet cloth.

Any manipulation (opening or closing) of a shut-off valve 

must be carried out by a qualified and authorised engineer. 

These  procedures  must  be  carried  out  with  the  unit  shut-

down.

NOTE: The unit must never be left shut down with the liquid 

line valve closed, as liquid refrigerant can be trapped between 

this valve and the expansion device. (This valve is situated 

on the liquid line before the filter drier box.)

Equip the engineers that work on the unit as follows:

Personal protection 

equipment (PPE)

(1)

Operations

Handling Maintenance, 

service

Welding or 

brazing

(2)

Protective gloves,
eye protection,
safety shoe,
protective clothing.

X

X

X

Ear protection.

X

X

Filtering respirator.

X

(1)  We recommend to follow the instructions in EN 378-3.

(2)  Performed in the presence of A1 refrigerant according to EN 378-1.

Never work on a unit that is still energized. 
CAUTION: 

The 19PV units are fitted with electrical circuit not disconnected 

by the main disconnect switch(es). 

Never work on any of the electrical components, until the 

general  power  supply  to  the  unit  has  been  cut  at  field 

installation or using the main supply and the excepted 

disconnect switches in the control box.

CAUTION: 
A motor mechanism module is integrated to insure the 

automatic main supply disconnect switch closure. If any 

maintenance operations are carried out on the unit, lock all 

the power supply circuit(s) in the open position.
If the work is interrupted, always ensure that all circuits are 

still deenergized before resuming the work.

CAUTION:

Even if the unit has been stopped the power circuit remains 

energized, unless the unit or circuit disconnect switch is 

open. Refer to the wiring diagram for further details. Attach 

appropriate safety labels.

CAUTION:
The frequency variator drive integrated in the compressor(s) 

used in 19PV units are equipped with capacitor batteries. A 

delay of twenty (20) minutes after disconnecting the power, 

corresponding  to  the  discharge  time,  must  be  observed 

before to remove the compressor(s) input cover.

Operating checks:
Important information regarding the refrigerant used:

• 

  This  product  contains  fluorinated  greenhouse  gas   

covered by the Kyoto protocol.

 

Fluid type: R-134A 

 

Global Warming Potential (GWP): 1430

CAUTION: 

1.  Prevent the release of fluorinated gas from the unit. Ensure 

that fluorinated gas is never released to the atmosphere 

during installation, maintenance or disposal. If a leak of 

fluorinated gas is detected, ensure the leak is stopped 

and repaired as quickly as possible.

2.  Only a qualified service technician is allowed to access 

this product and to correct the fault.

3.  Any handling of fluorinated gas contained in this product 

(e.g. removing the charge or topping up the gas) must 

comply  with  the  F-Gas  Directive  (EC)  No.  517/2014 

concerning certain fluorinated greenhouse gases and any 

other applicable local legislation.

4.  The gas recovery for recycling, regeneration or destruction 

is at customer charge.

5.  The deliberate gas release is strictly not allowed.

6.  Contact  your  local  dealer  or  installer  if  you  have  any 

questions.

Summary of Contents for 19PV550

Page 1: ...INSTALLATION OPERATION AND M A I N T E N A N C E I N S T R U C T I O N S Original document Original document 19PV Nominal cooling capacity 550 1600 kW 50Hz...

Page 2: ...mber of water passes 18 6 6 Min water volume and evaporator condenser water flow rates 18 6 7 Variable flow evaporator 18 6 8 Evaporator pressure drop curves 19 7 WATER CONNECTIONS 20 7 1 Operating pr...

Page 3: ...fer to the 19PV Touch Pilot Control manual CONTENT 12 OPTIONS 28 13 STANDARD MAINTENANCE 29 13 1 Level 1 maintenance 29 13 2 Level 2 maintenance 29 13 3 Level 3 or higher maintenance 29 13 4 Tightenin...

Page 4: ...ressure switches Ensure that the valves are correctly installed before operating the unit Classification and control In accordance with the Pressure Equipment Directive and national usage monitoring r...

Page 5: ...own with the liquid line valve closed as liquid refrigerant can be trapped between this valve and the expansion device This valve is situated on the liquid line before the filter drier box Equip the e...

Page 6: ...ser water flow Check the cut off value Reactivate manually HP switch and reactivate HP soft value Repeat the procedure for each unit compressor CAUTION If the test leads to replacing the pressure swit...

Page 7: ...sfer station The units must never be modified to add refrigerant removal and purging devices All these devices are provided with the units Please refer to the certified dimensional drawings for the un...

Page 8: ...or air flow and to ensure access to the components the number of support points is adequate and that they are in the right places the location is not subject to flooding CAUTION Lift and set down the...

Page 9: ...positioning of the fixing points weight distribution and centre of gravity coordinates please refer to the dimensional drawings Dimension mm A B C D 19PV 550 3045 1120 1745 2800 720 3070 1155 1846 28...

Page 10: ...positioning of the fixing points weight distribution and centre of gravity coordinates please refer to the dimensional drawings Dimension mm A B C D 19PV 900 4257 1290 1955 3950 1010 4257 1290 1955 3...

Page 11: ...positioning of the fixing points weight distribution and centre of gravity coordinates please refer to the dimensional drawings Dimension mm A B C D 19PV 1300 4705 1290 1955 4400 1450 4740 1290 2011...

Page 12: ...on valves EXV Minimum capacity 15 15 15 10 10 10 10 10 10 Evaporator Flooded multi pipe type Water volume l 115 165 180 285 285 285 330 330 365 Water connections Victaulic in 6 6 8 8 8 8 8 8 8 Drain a...

Page 13: ...with option 81 A 387 456 565 570 635 753 Maximum start up current Un Standard unit 3 Lower than max current Dissipated power of electrical equipment 1 W 782 1249 1249 1144 1347 1814 1884 2351 2351 1 V...

Page 14: ...power supply conductors is not provided with the unit 5 The factory installed disconnect switch es circuit breaker s are of a type suitable for power interruption in accordance with EN 60947 3 corres...

Page 15: ...This is less than the permissible 2 and is therefore acceptable 5 3 Power connection disconnect switch Units Connection points 19PV550 to 800 1 per unit 19PV900 to 1600 1 for circuit A 1 for circuit...

Page 16: ...selection Note Option 84 and 84R are not included in these values 5 5 Power cable entry The power cables can enter the 19PV control box from above the unit A removable aluminium plate on the upper par...

Page 17: ...er temperature C Condenser leaving water temperature C 10 20 30 40 50 0 5 10 15 20 6 2 Minimum chilled water flow The minimum chilled water flow is shown in the table in chapter 6 7 If the system flow...

Page 18: ...ndenser water flow rate m3 h Minimum 2 21 21 36 36 36 36 36 36 36 Maximum 3 245 299 346 486 457 454 428 594 526 1 Minimum evaporator flow rate based on a water velocity of 0 5 m s 2 Minimum condenser...

Page 19: ...FG H I J Legend 1 19PV550 6 19PV1180 2 19PV720 7 19PV1300 3 19PV800 8 19PV1450 4 19PV900 9 19PV1600 5 19PV1010 6 9 Condensor pressure drop curves Units with two condenser passes standard Pressure dro...

Page 20: ...the design operating pressures Before any start up verify that the heat exchange fluid is compatible with the materials and the water circuit coating The use of different metals on hydraulic piping co...

Page 21: ...1 219 1 219 1 219 1 219 1 219 1 7 3 Flow control Evaporator flow switch and chilled water pump interlock IMPORTANT On 19PV units the unit water flow switch must be energised Failure to follow this in...

Page 22: ...its own water pump If there is only one common pump in cases with variable flow isolation valves must be installed on each unit They will be activated at the opening and closing by the control of eac...

Page 23: ...mensions clearances are the same as standard 19PV units Unlike in the cooling mode the unit uses the heating setpoint in this configuration The evaporator leaving water control lowest setpoint taken i...

Page 24: ...ital outputs permitting control of up to eight fan stages 9 3 Configuration of the number of fan stages and the automatic changeover of the fan stages Please refer to the instructions in the Touch Pil...

Page 25: ...o communicate and control the drycooler The drycooler with option 313 AUX board with the I O OAT sensor to be place in outdoor zone Dry Cooler Leaving Water Temperature factory mounted Water loop Temp...

Page 26: ...compressor to reduce broadcasting of the noise radiated emissions from the power lines themselves 11 1 6 Fast acting fuses All compressors are fitted with class T fast acting fuses to protect the soli...

Page 27: ...sm module and an under voltage protection circuit are mounted on the main supply disconnect switch Note The following procedure must be done to lock the main supply disconnect switch Set the motor mec...

Page 28: ...management system Allows access to multiple unit parameters 0550 1600 Control for low cond temperature 152 Output signal 0 10 V to control the condenser water inlet valve Simple installation for appli...

Page 29: ...r see chapter 7 Water connections Check the unit operating parameters and compare them with previous values Replace compressor capacitors every 10 years if energized or 5 years if de energized Replace...

Page 30: ...e flanges 22 Brass fitting TT300 Motor cooling brass fitting 40 Brass fitting TT350 Motor cooling brass fitting 50 Phillips head screw Compressor cover plate 13 H M8 Screw Drier cover 35 H M10 Screw C...

Page 31: ...Electrical circuit wiring has been sized and installed properly Unit ground wire has been connected Electrical circuit protection has been sized and installed properly All terminals are tight All chil...

Page 32: ...l kW capacity for air conditioning 6 5 litres nominal kW capacity for process cooling Proper loop volume established Proper loop corrosion inhibitor included litres of Proper loop freeze protection in...

Page 33: ...33...

Page 34: ...Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the European Union CARRIER participates in the ECP programme for LCP HP Check...

Reviews: