background image

6

• 

Carry out periodic leak tests. In the European Union, 

article 2 of regulation (EU) No.517/2014 makes these 

mandatory and sets their frequency. The table below 

shows  this  frequency,  as  originally  published  in  the 

regulation. Check whether an inspection frequency is 

also set by other regulations or standards applicable 

to your system (e.g. EN 378, ISO 5149, etc.).

 

  A  logbook  must  be  established  for  the  systems 

that  require  a  tightness  check.  It  should  contain 

the  quantity  and  the  type  of  fluid  present  within  the 

installation  (added  and  recovered),  the  quantity  of 

recycled  fluid,  the  date  and  output  of  the  leak  test, 

the designation of the operator and its belonging 

company, etc.

Leak test periodicity:

System WITHOUT 

leakage detection

No test

12 

months

6 months 3 months

System WITH leakage 

detection

No test

24 

months

12 

months

6 months

Refrigerant charge per 

circuit (equivalent CO

2

)

< 5 tons

5 ≤ 

charge < 

50 tons

50 ≤ 

charge < 

500 tons

Charge >

500 

tonnes*

Refrigerant charge per 

circuit (kg)

R134a

(PRP 1430)

Charge

< 3.5 kg

3.5 ≤ 

charge

< 34.9 kg

34.9 ≤ 

charge < 

349.7 kg

charge >

349.7 kg

R407C

(PRP 1774)

Charge

< 2.8 kg

2.8 ≤ 

charge

< 28.2 kg

28.2 ≤ 

charge < 

281.9 kg

charge >

281.9 kg

R410A

(PRP 2088)

Charge

< 2.4 kg

2.4 ≤ 

charge

< 23.9 kg

23.9 ≤ 

charge

< 239.5 

kg

charge >

239.5 kg

HFOs: R1234ze

No requirement

*   From 01/01/2017, units must be equipped with a leak detection system.

• 

During the life-time of the system, inspection and tests 

must  be  carried  out  in  accordance  with  national 

regulations.

Protection device checks (EN 378):

The safety devices must be checked on site once a year for 

safety devices (see chapter 11.3 - High-pressure safety 

switch), and every five years for external overpressure 

devices (external relief valves).

The company or organisation that conducts a pressure switch test 

shall establish and implement a detailed procedure to fix:

 

-

Safety measures

 

-

Measuring equipment calibration

 

-

Validating operation of protective devices

 

-

Test protocols

 

-

Recommissioning of the equipment.

Consult the manufacturer Service for this type of test. The 
manufacturer mentions here only the principle of a test without 
removing the pressure switch:

 

-

Verify and and record the set-points of pressure switches 
and relief devices (valves and possible rupture discs)

 

-

Be ready to switch-off the main disconnect switch of the power 
supply if the pressure switch does not trigger (avoid over-
pressure or excess gas in case of valves on the high-pressure 
side with the recovery condensers)

 

-

Connect a pressure gauge protected against pulsations (filled 

with oil with maximum pointer if mechanical), preferably 
calibrated (the values displayed on the user interface may 
be inaccurate in an instant reading because of the scanning 
delay applied in the control)

 

-

Complete an HP Test 

 

-

Neutralize HP soft protection 

 

-

Cut condenser water flow

 

-

Check the cut-off value

 

-

Reactivate manually HP switch and reactivate HP soft value"

 

-

Repeat the procedure for each unit compressor.

CAUTION: 
If the test leads to replacing the pressure switch, it is 

necessary to recover the refrigerant charge, these pressure 

switches are not installed on automatic valves (Schraeder 

type).
At least once a year thoroughly inspect the protection devices 

(valves). If the machine operates in a corrosive environment, 

inspect the protection devices more frequently. 

Ensure regularly that the vibration levels remain acceptable 

and close to those at the initial unit start-up.
Before opening a refrigerant circuit, purge and consult the 

pressure gauges.
Change the refrigerant when there are equipment failures, 

following a procedure such as the one described in NF E29-

795 or carry out a refrigerant analysis in a specialist 

laboratory.

If the refrigerant circuit remains open for longer than a day 

after an intervention (such as a component replacement), the 

openings must be plugged and the circuit must be charged 

with nitrogen (inertia principle). The objective is to prevent 

penetration of atmospheric humidity and the resulting 

corrosion on the internal walls and on non-protected steel 

surfaces.

1.4 - Repair safety considerations

It is compulsory to wear personal protection equipment. 

The insulation must be removed and warming up must be 

limited by using a wet cloth. 

Before opening the unit always ensure that the circuit has 

been purged.

If work on the evaporator is required, ensure that the piping 

from the compressor is no longer pressurised (as the valve 

is not leaktight in the compressor direction).

All installation parts must be maintained by the personnel in charge, 

in order to avoid material deterioration and injuries to people. Faults 

and leaks must be repaired immediately. The authorized technician 
must have the responsibility to repair the fault immediately. Each 
time repairs have been carried out to the unit, the operation of the 
protection devices must be re-checked.
Comply with the regulations and recommendations in unit and 
HVAC installation safety standards, such as: EN 378, ISO 5149, 
etc.
If a leak occurs or if the refrigerant becomes contaminated (e.g. 
by a short circuit in a motor) remove the complete charge using 
a recovery unit and store the refrigerant in mobile containers.
Repair the leak detected and recharge the circuit with the total 
R-134a charge, as indicated on the unit name plate. Certain parts 
of the circuit can be isolated. Only charge liquid refrigerant R-134a 
at the liquid line.

Ensure that you are using the correct refrigerant type before 

recharging the unit

The compressors operating are NOT lubricated. Charging any 

oil type will impair machine operation and lead to a destruction 

of the compressor.
Charging any refrigerant other than the original charge type 

(R-134a) will impair machine operation and can even lead to 

a destruction of the compressors.

1 - INTRODUCTION

Summary of Contents for 19PV550

Page 1: ...INSTALLATION OPERATION AND M A I N T E N A N C E I N S T R U C T I O N S Original document Original document 19PV Nominal cooling capacity 550 1600 kW 50Hz...

Page 2: ...mber of water passes 18 6 6 Min water volume and evaporator condenser water flow rates 18 6 7 Variable flow evaporator 18 6 8 Evaporator pressure drop curves 19 7 WATER CONNECTIONS 20 7 1 Operating pr...

Page 3: ...fer to the 19PV Touch Pilot Control manual CONTENT 12 OPTIONS 28 13 STANDARD MAINTENANCE 29 13 1 Level 1 maintenance 29 13 2 Level 2 maintenance 29 13 3 Level 3 or higher maintenance 29 13 4 Tightenin...

Page 4: ...ressure switches Ensure that the valves are correctly installed before operating the unit Classification and control In accordance with the Pressure Equipment Directive and national usage monitoring r...

Page 5: ...own with the liquid line valve closed as liquid refrigerant can be trapped between this valve and the expansion device This valve is situated on the liquid line before the filter drier box Equip the e...

Page 6: ...ser water flow Check the cut off value Reactivate manually HP switch and reactivate HP soft value Repeat the procedure for each unit compressor CAUTION If the test leads to replacing the pressure swit...

Page 7: ...sfer station The units must never be modified to add refrigerant removal and purging devices All these devices are provided with the units Please refer to the certified dimensional drawings for the un...

Page 8: ...or air flow and to ensure access to the components the number of support points is adequate and that they are in the right places the location is not subject to flooding CAUTION Lift and set down the...

Page 9: ...positioning of the fixing points weight distribution and centre of gravity coordinates please refer to the dimensional drawings Dimension mm A B C D 19PV 550 3045 1120 1745 2800 720 3070 1155 1846 28...

Page 10: ...positioning of the fixing points weight distribution and centre of gravity coordinates please refer to the dimensional drawings Dimension mm A B C D 19PV 900 4257 1290 1955 3950 1010 4257 1290 1955 3...

Page 11: ...positioning of the fixing points weight distribution and centre of gravity coordinates please refer to the dimensional drawings Dimension mm A B C D 19PV 1300 4705 1290 1955 4400 1450 4740 1290 2011...

Page 12: ...on valves EXV Minimum capacity 15 15 15 10 10 10 10 10 10 Evaporator Flooded multi pipe type Water volume l 115 165 180 285 285 285 330 330 365 Water connections Victaulic in 6 6 8 8 8 8 8 8 8 Drain a...

Page 13: ...with option 81 A 387 456 565 570 635 753 Maximum start up current Un Standard unit 3 Lower than max current Dissipated power of electrical equipment 1 W 782 1249 1249 1144 1347 1814 1884 2351 2351 1 V...

Page 14: ...power supply conductors is not provided with the unit 5 The factory installed disconnect switch es circuit breaker s are of a type suitable for power interruption in accordance with EN 60947 3 corres...

Page 15: ...This is less than the permissible 2 and is therefore acceptable 5 3 Power connection disconnect switch Units Connection points 19PV550 to 800 1 per unit 19PV900 to 1600 1 for circuit A 1 for circuit...

Page 16: ...selection Note Option 84 and 84R are not included in these values 5 5 Power cable entry The power cables can enter the 19PV control box from above the unit A removable aluminium plate on the upper par...

Page 17: ...er temperature C Condenser leaving water temperature C 10 20 30 40 50 0 5 10 15 20 6 2 Minimum chilled water flow The minimum chilled water flow is shown in the table in chapter 6 7 If the system flow...

Page 18: ...ndenser water flow rate m3 h Minimum 2 21 21 36 36 36 36 36 36 36 Maximum 3 245 299 346 486 457 454 428 594 526 1 Minimum evaporator flow rate based on a water velocity of 0 5 m s 2 Minimum condenser...

Page 19: ...FG H I J Legend 1 19PV550 6 19PV1180 2 19PV720 7 19PV1300 3 19PV800 8 19PV1450 4 19PV900 9 19PV1600 5 19PV1010 6 9 Condensor pressure drop curves Units with two condenser passes standard Pressure dro...

Page 20: ...the design operating pressures Before any start up verify that the heat exchange fluid is compatible with the materials and the water circuit coating The use of different metals on hydraulic piping co...

Page 21: ...1 219 1 219 1 219 1 219 1 219 1 7 3 Flow control Evaporator flow switch and chilled water pump interlock IMPORTANT On 19PV units the unit water flow switch must be energised Failure to follow this in...

Page 22: ...its own water pump If there is only one common pump in cases with variable flow isolation valves must be installed on each unit They will be activated at the opening and closing by the control of eac...

Page 23: ...mensions clearances are the same as standard 19PV units Unlike in the cooling mode the unit uses the heating setpoint in this configuration The evaporator leaving water control lowest setpoint taken i...

Page 24: ...ital outputs permitting control of up to eight fan stages 9 3 Configuration of the number of fan stages and the automatic changeover of the fan stages Please refer to the instructions in the Touch Pil...

Page 25: ...o communicate and control the drycooler The drycooler with option 313 AUX board with the I O OAT sensor to be place in outdoor zone Dry Cooler Leaving Water Temperature factory mounted Water loop Temp...

Page 26: ...compressor to reduce broadcasting of the noise radiated emissions from the power lines themselves 11 1 6 Fast acting fuses All compressors are fitted with class T fast acting fuses to protect the soli...

Page 27: ...sm module and an under voltage protection circuit are mounted on the main supply disconnect switch Note The following procedure must be done to lock the main supply disconnect switch Set the motor mec...

Page 28: ...management system Allows access to multiple unit parameters 0550 1600 Control for low cond temperature 152 Output signal 0 10 V to control the condenser water inlet valve Simple installation for appli...

Page 29: ...r see chapter 7 Water connections Check the unit operating parameters and compare them with previous values Replace compressor capacitors every 10 years if energized or 5 years if de energized Replace...

Page 30: ...e flanges 22 Brass fitting TT300 Motor cooling brass fitting 40 Brass fitting TT350 Motor cooling brass fitting 50 Phillips head screw Compressor cover plate 13 H M8 Screw Drier cover 35 H M10 Screw C...

Page 31: ...Electrical circuit wiring has been sized and installed properly Unit ground wire has been connected Electrical circuit protection has been sized and installed properly All terminals are tight All chil...

Page 32: ...l kW capacity for air conditioning 6 5 litres nominal kW capacity for process cooling Proper loop volume established Proper loop corrosion inhibitor included litres of Proper loop freeze protection in...

Page 33: ...33...

Page 34: ...Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the European Union CARRIER participates in the ECP programme for LCP HP Check...

Reviews: