background image

26

11 - MAJOR SYSTEM COMPONENTS AND OPERATION DATA

11.1 - MagLev centrifugal compressor

 

-

19PV units use TT (Twin-Turbine) MagLev centrifugal 
compressors equipped with an inlet guide valve and 
controlled by a speed variator.

 

-

Compressor capacity control is ensured by successive use 
of speed variation (using a frequency variator) and swept 
volume variation at the turbine (using the Inlet Guide Valve).

 

-

The  combination  of  these  two  control  modes  permits  fine 

control of the unit capacity between 15% and 100%.

 

-

The MagLev centrifugal compressor models used are: TT300, 
TT350

 

-

The MagLev centrifugal compressors are NOT lubrificated

 

-

The compressor drive and the compressor motor are cooled 
by a liquid line. The cooling system is controlled by two valves 
located in the compressor drive.

11.1.1 - Refrigerant

The 19PV is a liquid chiller operating only with refrigerant R-134a.

11.1.2 - Capacity control system

19PV  units are equipped with a frequency variator that permits 

compressor capacity adjustment by varying the motor speed. The 

frequency range depends on the refrigerant pressure ratio. At the 
minimum speed, the compressor reduces the capacity by closing 
the inlet guide valve.
The compressor drive uses power supply waveform generation 
with variable frequency and voltage, generated by pulse width 
modulation (PWM).
Compressor start-up and stopping and the frequency setting for 
the operating range is only by RS485 communication in the 
MODBUS protocol via the controller.

11.1.3 - Suction valve (Option 92)

An isolating valve can be added to ease maintenance on 
compressor. This valve can be moved ONLY without pressure 
differential upstream and downstream of this valve.
The following markers indicate the fully opened position and the 
fully closed position of the valve. 

Opened position

Closed position

11.1.4 - Line reactor

A line reactor is a special form of inductor that is typically used 
between the line and the load to smooth current inrush, reduce 
harmonics and noise, and buffer the systems connected to it. 

Specifically it is an inductor that adds inductive impedance to a 

circuit
One Line reactor by compressor is mandatory and they are located 
in the electrical box.

11.1.5 - EMC Filter

The EMC filter reduces electrical noise on the power lines 
(conducted emissions), it is located close to the compressor to 
reduce broadcasting of the noise (radiated emissions) from the 
power lines themselves.

11.1.6 - Fast acting fuses

All compressors are fitted with class T fast acting fuses to protect 

the solid state inverter.
The fuses are included in the TT300 compressor under the main 
cover. With the TT350 compressor, the fast acting fuses are located 
in the electrical box.

11.2 - Pressure vessels

General

Monitoring  during  operation,  re-qualification,  re-testing  and  re-

testing dispensation:

 

-

Follow the regulations on monitoring pressurised equipment.

 

-

It is normally required that the user or operator sets up and 

maintains a monitoring and maintenance file.

 

-

If no regulations exist or to complement regulations, follow 
the control programmes of EN 378.

 

-

If they exist follow local professional recommendations.

 

-

Regularly inspect the condition of the coating (paint) to detect 
blistering resulting from corrosion. To do this, check a non-
insulated section of the container or the rust formation at the 

insulation joints.

 

-

Regularly check for possible presence of impurities (e.g. 

silicon grains) in the heat exchange fluids. These impurities 

maybe the cause of the wear or corrosion by puncture.

 

-

Filter the heat exchange fluid check and carry out internal 

inspections as described in EN 378.

 

-

In case of re-testing please refer to the maximum operating 
pressure given on the unit nameplate.

 

-

The reports of periodical checks by the user or operator must 

be included in the supervision and maintenance file.

Repair

Any repair or modification, including the replacement of moving 

parts:

 

-

must follow local regulations and be made by qualified 
operators and in accordance with qualified procedures, 
including changing the heat exchanger tubes.

 

-

must be made in accordance with the instructions of the original 
manufacturer. Repair and modification that necessitate 
permanent assembly (soldering, welding, expanding etc.) 
must be made using the correct procedures and by qualified 
operators.

 

-

An indication of any modification or repair must be shown in 
the monitoring and maintenance file.

Recycling

The unit is wholly or partly recyclable. After use it contains 
refrigerant vapours. It is coated by paint.

Operating life

The evaporator is designed for:

 

-

prolonged storage of 15 years under nitrogen charge with a 
temperature difference of 20 K per day.

 

-

452000 cycles (start-ups) with a maximum difference of 6 K 
between two neighbouring points in the vessel, based on 6 
start-ups per hour over 15 years at a usage rate of 57%.

Summary of Contents for 19PV550

Page 1: ...INSTALLATION OPERATION AND M A I N T E N A N C E I N S T R U C T I O N S Original document Original document 19PV Nominal cooling capacity 550 1600 kW 50Hz...

Page 2: ...mber of water passes 18 6 6 Min water volume and evaporator condenser water flow rates 18 6 7 Variable flow evaporator 18 6 8 Evaporator pressure drop curves 19 7 WATER CONNECTIONS 20 7 1 Operating pr...

Page 3: ...fer to the 19PV Touch Pilot Control manual CONTENT 12 OPTIONS 28 13 STANDARD MAINTENANCE 29 13 1 Level 1 maintenance 29 13 2 Level 2 maintenance 29 13 3 Level 3 or higher maintenance 29 13 4 Tightenin...

Page 4: ...ressure switches Ensure that the valves are correctly installed before operating the unit Classification and control In accordance with the Pressure Equipment Directive and national usage monitoring r...

Page 5: ...own with the liquid line valve closed as liquid refrigerant can be trapped between this valve and the expansion device This valve is situated on the liquid line before the filter drier box Equip the e...

Page 6: ...ser water flow Check the cut off value Reactivate manually HP switch and reactivate HP soft value Repeat the procedure for each unit compressor CAUTION If the test leads to replacing the pressure swit...

Page 7: ...sfer station The units must never be modified to add refrigerant removal and purging devices All these devices are provided with the units Please refer to the certified dimensional drawings for the un...

Page 8: ...or air flow and to ensure access to the components the number of support points is adequate and that they are in the right places the location is not subject to flooding CAUTION Lift and set down the...

Page 9: ...positioning of the fixing points weight distribution and centre of gravity coordinates please refer to the dimensional drawings Dimension mm A B C D 19PV 550 3045 1120 1745 2800 720 3070 1155 1846 28...

Page 10: ...positioning of the fixing points weight distribution and centre of gravity coordinates please refer to the dimensional drawings Dimension mm A B C D 19PV 900 4257 1290 1955 3950 1010 4257 1290 1955 3...

Page 11: ...positioning of the fixing points weight distribution and centre of gravity coordinates please refer to the dimensional drawings Dimension mm A B C D 19PV 1300 4705 1290 1955 4400 1450 4740 1290 2011...

Page 12: ...on valves EXV Minimum capacity 15 15 15 10 10 10 10 10 10 Evaporator Flooded multi pipe type Water volume l 115 165 180 285 285 285 330 330 365 Water connections Victaulic in 6 6 8 8 8 8 8 8 8 Drain a...

Page 13: ...with option 81 A 387 456 565 570 635 753 Maximum start up current Un Standard unit 3 Lower than max current Dissipated power of electrical equipment 1 W 782 1249 1249 1144 1347 1814 1884 2351 2351 1 V...

Page 14: ...power supply conductors is not provided with the unit 5 The factory installed disconnect switch es circuit breaker s are of a type suitable for power interruption in accordance with EN 60947 3 corres...

Page 15: ...This is less than the permissible 2 and is therefore acceptable 5 3 Power connection disconnect switch Units Connection points 19PV550 to 800 1 per unit 19PV900 to 1600 1 for circuit A 1 for circuit...

Page 16: ...selection Note Option 84 and 84R are not included in these values 5 5 Power cable entry The power cables can enter the 19PV control box from above the unit A removable aluminium plate on the upper par...

Page 17: ...er temperature C Condenser leaving water temperature C 10 20 30 40 50 0 5 10 15 20 6 2 Minimum chilled water flow The minimum chilled water flow is shown in the table in chapter 6 7 If the system flow...

Page 18: ...ndenser water flow rate m3 h Minimum 2 21 21 36 36 36 36 36 36 36 Maximum 3 245 299 346 486 457 454 428 594 526 1 Minimum evaporator flow rate based on a water velocity of 0 5 m s 2 Minimum condenser...

Page 19: ...FG H I J Legend 1 19PV550 6 19PV1180 2 19PV720 7 19PV1300 3 19PV800 8 19PV1450 4 19PV900 9 19PV1600 5 19PV1010 6 9 Condensor pressure drop curves Units with two condenser passes standard Pressure dro...

Page 20: ...the design operating pressures Before any start up verify that the heat exchange fluid is compatible with the materials and the water circuit coating The use of different metals on hydraulic piping co...

Page 21: ...1 219 1 219 1 219 1 219 1 219 1 7 3 Flow control Evaporator flow switch and chilled water pump interlock IMPORTANT On 19PV units the unit water flow switch must be energised Failure to follow this in...

Page 22: ...its own water pump If there is only one common pump in cases with variable flow isolation valves must be installed on each unit They will be activated at the opening and closing by the control of eac...

Page 23: ...mensions clearances are the same as standard 19PV units Unlike in the cooling mode the unit uses the heating setpoint in this configuration The evaporator leaving water control lowest setpoint taken i...

Page 24: ...ital outputs permitting control of up to eight fan stages 9 3 Configuration of the number of fan stages and the automatic changeover of the fan stages Please refer to the instructions in the Touch Pil...

Page 25: ...o communicate and control the drycooler The drycooler with option 313 AUX board with the I O OAT sensor to be place in outdoor zone Dry Cooler Leaving Water Temperature factory mounted Water loop Temp...

Page 26: ...compressor to reduce broadcasting of the noise radiated emissions from the power lines themselves 11 1 6 Fast acting fuses All compressors are fitted with class T fast acting fuses to protect the soli...

Page 27: ...sm module and an under voltage protection circuit are mounted on the main supply disconnect switch Note The following procedure must be done to lock the main supply disconnect switch Set the motor mec...

Page 28: ...management system Allows access to multiple unit parameters 0550 1600 Control for low cond temperature 152 Output signal 0 10 V to control the condenser water inlet valve Simple installation for appli...

Page 29: ...r see chapter 7 Water connections Check the unit operating parameters and compare them with previous values Replace compressor capacitors every 10 years if energized or 5 years if de energized Replace...

Page 30: ...e flanges 22 Brass fitting TT300 Motor cooling brass fitting 40 Brass fitting TT350 Motor cooling brass fitting 50 Phillips head screw Compressor cover plate 13 H M8 Screw Drier cover 35 H M10 Screw C...

Page 31: ...Electrical circuit wiring has been sized and installed properly Unit ground wire has been connected Electrical circuit protection has been sized and installed properly All terminals are tight All chil...

Page 32: ...l kW capacity for air conditioning 6 5 litres nominal kW capacity for process cooling Proper loop volume established Proper loop corrosion inhibitor included litres of Proper loop freeze protection in...

Page 33: ...33...

Page 34: ...Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the European Union CARRIER participates in the ECP programme for LCP HP Check...

Reviews: