background image

20

7 - WATER CONNECTIONS

ATTENTION: Before carrying out any water connections 

install the water box purge plugs (one plug per water box in 

the lower section - supplied in the control box).

For size and position of the heat exchanger water inlet and outlet 

connections refer to the certified dimensional drawings supplied with 

the unit.
The water pipes must not transmit any radial or axial force to the 
heat exchangers nor any vibration. 

The  water  supply  must  be  analysed  and  appropriate  filtering, 

treatment, control devices, isolation and bleed valves and circuits 
built in, to prevent corrosion, fouling and deterioration of the pump 

fittings. Consult either a water treatment specialist or appropriate 
literature on the subject.

7.1 - Operating precautions

The water circuit should be designed to have the least number of 
elbows and horizontal pipe runs at different levels. Below the main 
points to be checked for the connection:

 

-

Comply with the water inlet and outlet connections shown on 
the unit.

 

-

Install manual or automatic air purge valves at all high points 
in the circuit(s).

 

-

Use a pressure reducer to maintain pressure in the circuit(s) 
and install a relief valve as well as an expansion tank.

 

-

Install thermometers in both the entering and leaving water 
connections.

 

-

Install drain connections at all low points to allow the whole 
circuit to be drained.

 

-

Install stop valves, close to the entering and leaving water 
connections.

 

-

Use flexible connections to reduce the transmission of 
vibrations.

 

-

Insulate all pipework, after testing for leaks, both to reduce 
heat gains and to prevent condensation.

 

-

Cover the insulation with a vapour barrier.

 

-

Where there are particles in the fluid that could foul the heat 
exchanger, a screen filter should be installed ahead of the 

pump, or directly at the exchanger inlet in case the pump is 

more than 20m away. The mesh size of the filter must be 1.2 

mm.

 

-

Before the system start-up verify that the water circuits are 
connected to the appropriate heat exchangers (e.g. no 
reversal between evaporator and condenser).

 

-

Do not introduce any significant static or dynamic pressure 

into the heat exchange circuit (with regard to the design 
operating pressures).

 

-

Before  any  start-up  verify  that  the  heat  exchange  fluid  is 

compatible with the materials and the water circuit coating.

 

-

The use of different metals on hydraulic piping could generate 
eletrolytic pairs and consequently corrosion. Verify then, the 

need to install sacrificial anodes.

In case additives or other fluids than those recommended by the 
manufacturer are used, ensure that the fluids are not considered 
as a gas, and that they belong to class 2, as defined in directive 

2014/68/UE.

The manufacturer recommendations on heat exchange fluids:

 

-

No NH

4+

 ammonium ions in the water, they are very 

detrimental for copper. This is one of the most important 
factors for the operating life of copper piping. A content of 
several tenths of mg/l will badly corrode the copper over time.

 

-

Cl

-

 Chloride ions are detrimental for copper with a risk of 

perforations by corrosion by puncture. If possible keep below 
125 mg/l.

 

-

SO

4

2-

 sulphate ions can cause perforating corrosion, if their 

content is above 30 mg/l.

 

-

No fluoride ions (<0.1 mg/l).

 

-

No Fe

2+

 and Fe

3+

 ions with non negligible levels of dissolved 

oxygen must be present. Dissolved iron < 5 mg/l with dissolved 
oxygen < 5 mg/l.

 

-

Dissolved silicon: silicon is an acid element of water and can 
also lead to corrosion risks. Content < 1 mg/l.

 

-

Water hardness: > 0.5 mmol/l. Values between 1 and 2.5 can 
be recommended. This will facilitate scale deposit that can limit 
corrosion of copper. Values that are too high can cause piping 
blockage over time. A total alkalimetric titre (TAC) below 100 
mg/l is desirable.

 

-

Dissolved oxygen: Any sudden change in water oxygenation 
conditions must be avoided. It is as detrimental to deoxygenate 
the water by mixing it with inert gas as it is to over-oxygenate 
it by mixing it with pure oxygen. The disturbance of the 
oxygenation conditions encourages destabilisation of copper 
hydroxides and enlargement of particles.

 

-

Electric conductivity 10-600µS/cm.

 

-

pH: Ideal case pH neutral at 20-25°C

    7 < pH < 8

If the water circuit must be emptied for longer than one month, 
the complete circuit must be placed under nitrogen charge to avoid 
any risk of corrosion by differential aeration.

Charging and removing heat exchange fluids should be done with 

devices that must be included on the water circuit by the installer. 

Never use the unit heat exchangers to add heat exchange fluid.

Summary of Contents for 19PV550

Page 1: ...INSTALLATION OPERATION AND M A I N T E N A N C E I N S T R U C T I O N S Original document Original document 19PV Nominal cooling capacity 550 1600 kW 50Hz...

Page 2: ...mber of water passes 18 6 6 Min water volume and evaporator condenser water flow rates 18 6 7 Variable flow evaporator 18 6 8 Evaporator pressure drop curves 19 7 WATER CONNECTIONS 20 7 1 Operating pr...

Page 3: ...fer to the 19PV Touch Pilot Control manual CONTENT 12 OPTIONS 28 13 STANDARD MAINTENANCE 29 13 1 Level 1 maintenance 29 13 2 Level 2 maintenance 29 13 3 Level 3 or higher maintenance 29 13 4 Tightenin...

Page 4: ...ressure switches Ensure that the valves are correctly installed before operating the unit Classification and control In accordance with the Pressure Equipment Directive and national usage monitoring r...

Page 5: ...own with the liquid line valve closed as liquid refrigerant can be trapped between this valve and the expansion device This valve is situated on the liquid line before the filter drier box Equip the e...

Page 6: ...ser water flow Check the cut off value Reactivate manually HP switch and reactivate HP soft value Repeat the procedure for each unit compressor CAUTION If the test leads to replacing the pressure swit...

Page 7: ...sfer station The units must never be modified to add refrigerant removal and purging devices All these devices are provided with the units Please refer to the certified dimensional drawings for the un...

Page 8: ...or air flow and to ensure access to the components the number of support points is adequate and that they are in the right places the location is not subject to flooding CAUTION Lift and set down the...

Page 9: ...positioning of the fixing points weight distribution and centre of gravity coordinates please refer to the dimensional drawings Dimension mm A B C D 19PV 550 3045 1120 1745 2800 720 3070 1155 1846 28...

Page 10: ...positioning of the fixing points weight distribution and centre of gravity coordinates please refer to the dimensional drawings Dimension mm A B C D 19PV 900 4257 1290 1955 3950 1010 4257 1290 1955 3...

Page 11: ...positioning of the fixing points weight distribution and centre of gravity coordinates please refer to the dimensional drawings Dimension mm A B C D 19PV 1300 4705 1290 1955 4400 1450 4740 1290 2011...

Page 12: ...on valves EXV Minimum capacity 15 15 15 10 10 10 10 10 10 Evaporator Flooded multi pipe type Water volume l 115 165 180 285 285 285 330 330 365 Water connections Victaulic in 6 6 8 8 8 8 8 8 8 Drain a...

Page 13: ...with option 81 A 387 456 565 570 635 753 Maximum start up current Un Standard unit 3 Lower than max current Dissipated power of electrical equipment 1 W 782 1249 1249 1144 1347 1814 1884 2351 2351 1 V...

Page 14: ...power supply conductors is not provided with the unit 5 The factory installed disconnect switch es circuit breaker s are of a type suitable for power interruption in accordance with EN 60947 3 corres...

Page 15: ...This is less than the permissible 2 and is therefore acceptable 5 3 Power connection disconnect switch Units Connection points 19PV550 to 800 1 per unit 19PV900 to 1600 1 for circuit A 1 for circuit...

Page 16: ...selection Note Option 84 and 84R are not included in these values 5 5 Power cable entry The power cables can enter the 19PV control box from above the unit A removable aluminium plate on the upper par...

Page 17: ...er temperature C Condenser leaving water temperature C 10 20 30 40 50 0 5 10 15 20 6 2 Minimum chilled water flow The minimum chilled water flow is shown in the table in chapter 6 7 If the system flow...

Page 18: ...ndenser water flow rate m3 h Minimum 2 21 21 36 36 36 36 36 36 36 Maximum 3 245 299 346 486 457 454 428 594 526 1 Minimum evaporator flow rate based on a water velocity of 0 5 m s 2 Minimum condenser...

Page 19: ...FG H I J Legend 1 19PV550 6 19PV1180 2 19PV720 7 19PV1300 3 19PV800 8 19PV1450 4 19PV900 9 19PV1600 5 19PV1010 6 9 Condensor pressure drop curves Units with two condenser passes standard Pressure dro...

Page 20: ...the design operating pressures Before any start up verify that the heat exchange fluid is compatible with the materials and the water circuit coating The use of different metals on hydraulic piping co...

Page 21: ...1 219 1 219 1 219 1 219 1 219 1 7 3 Flow control Evaporator flow switch and chilled water pump interlock IMPORTANT On 19PV units the unit water flow switch must be energised Failure to follow this in...

Page 22: ...its own water pump If there is only one common pump in cases with variable flow isolation valves must be installed on each unit They will be activated at the opening and closing by the control of eac...

Page 23: ...mensions clearances are the same as standard 19PV units Unlike in the cooling mode the unit uses the heating setpoint in this configuration The evaporator leaving water control lowest setpoint taken i...

Page 24: ...ital outputs permitting control of up to eight fan stages 9 3 Configuration of the number of fan stages and the automatic changeover of the fan stages Please refer to the instructions in the Touch Pil...

Page 25: ...o communicate and control the drycooler The drycooler with option 313 AUX board with the I O OAT sensor to be place in outdoor zone Dry Cooler Leaving Water Temperature factory mounted Water loop Temp...

Page 26: ...compressor to reduce broadcasting of the noise radiated emissions from the power lines themselves 11 1 6 Fast acting fuses All compressors are fitted with class T fast acting fuses to protect the soli...

Page 27: ...sm module and an under voltage protection circuit are mounted on the main supply disconnect switch Note The following procedure must be done to lock the main supply disconnect switch Set the motor mec...

Page 28: ...management system Allows access to multiple unit parameters 0550 1600 Control for low cond temperature 152 Output signal 0 10 V to control the condenser water inlet valve Simple installation for appli...

Page 29: ...r see chapter 7 Water connections Check the unit operating parameters and compare them with previous values Replace compressor capacitors every 10 years if energized or 5 years if de energized Replace...

Page 30: ...e flanges 22 Brass fitting TT300 Motor cooling brass fitting 40 Brass fitting TT350 Motor cooling brass fitting 50 Phillips head screw Compressor cover plate 13 H M8 Screw Drier cover 35 H M10 Screw C...

Page 31: ...Electrical circuit wiring has been sized and installed properly Unit ground wire has been connected Electrical circuit protection has been sized and installed properly All terminals are tight All chil...

Page 32: ...l kW capacity for air conditioning 6 5 litres nominal kW capacity for process cooling Proper loop volume established Proper loop corrosion inhibitor included litres of Proper loop freeze protection in...

Page 33: ...33...

Page 34: ...Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the European Union CARRIER participates in the ECP programme for LCP HP Check...

Reviews: