Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides (cont)
L. MACHINE ALERTS
PRIMARY MESSAGE
SECONDARY MESSAGE
ALARM MESSAGE/PRIMARY CAUSE
ADDITIONAL CAUSE/REMEDY
RECYCLE ALERT
HIGH AMPS AT SHUTDOWN
High Amps at Recycle: Check guide vane drive.
Check that guide vanes are closing. Check
motor amps correction calibration is cor-
rect. Check actuator for proper operation.
SENSOR FAULT ALERT
LEAVING COND WATER
TEMP
Sensor Fault: Check leaving condenser water sen-
sor.
Check sensor. See sensor test
procedure.
SENSOR FAULT ALERT
ENTERING COND WATER
TEMP
Sensor Fault: Check entering condenser water sen-
sor.
LOW OIL PRESSURE
ALERT
CHECK OIL FILTER
Low Oil Pressure Alert: Check oil
Check oil filter. Check for improper oil level
or temperature.
AUTORESTART PENDING
POWER LOSS
V
P Power Loss: Check voltage
supply.
Check power supply if there are excessive
compressor starts occurring.
AUTORESTART PENDING
LOW LINE VOLTAGE
V
P [VALUE] exceeded limit of [LIMIT]*. Check
voltage supply.
AUTORESTART PENDING
HIGH LINE VOLTAGE
V
P [VALUE] exceeded limit of [LIMIT]*. Check
voltage supply.
SENSOR ALERT
HIGH DISCHARGE TEMP
CMPD [VALUE] exceeded limit of [LIMIT]*. Check
discharge temperature.
Discharge temperature exceeded the alert
threshold. Check entering condenser water
temperature.
SENSOR ALERT
HIGH BEARING
TEMPERATURE
MTRB [VALUE] exceeded limit of [LIMIT]*. Check
thrust bearing temperature.
Thrust bearing temperature exceeded the
alert threshold. Check for closed valves, im-
proper oil level or temperatures.
CONDENSER PRESSURE
ALERT
PUMP RELAY ENERGIZED
CRP High Condenser Pressure [LIMIT]*.
Pump energized to reduce pressure.
Check ambient conditions. Check con-
denser pressure for accuracy.
RECYCLE ALERT
EXCESSIVE RECYCLE
STARTS
Excessive recycle starts.
The machine load is too small to keep the
machine on line and there have been more
than 5 restarts in 4 hours. Increase ma-
chine load, adjust hot gas bypass, increase
RECYCLE RESTART DELTA T.
*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE]
is the actual temperature, pressure, voltage, etc., at which the control tripped.
M. SPARE SENSOR ALERT MESSAGES
PRIMARY MESSAGE
SECONDARY MESSAGE
ALARM MESSAGE/PRIMARY CAUSE
ADDITIONAL CAUSE/REMEDY
SPARE SENSOR ALERT
COMMON CHWS SENSOR
Sensor Fault: Check common CHWS sensor.
Check alert temperature set points on Equipment
Service, SERVICE2 LID table.
Check sensor for accuracy if reading is not
accurate.
SPARE SENSOR ALERT
COMMON CHWR SENSOR
Sensor Fault: Check common CHWR
sensor.
SPARE SENSOR ALERT
REMOTE RESET SENSOR
Sensor Fault: Check remote reset tempera-
ture sensor.
SPARE SENSOR ALERT
TEMP SENSOR — SPARE 1
Sensor Fault: Check temperature sensor —
Spare 1.
SPARE SENSOR ALERT
TEMP SENSOR — SPARE 2
Sensor Fault: Check temperature sensor —
Spare 2.
SPARE SENSOR ALERT
TEMP SENSOR — SPARE 3
Sensor Fault: Check temperature sensor —
Spare 3.
SPARE SENSOR ALERT
TEMP SENSOR — SPARE 4
Sensor Fault: Check temperature sensor —
Spare 4.
SPARE SENSOR ALERT
TEMP SENSOR — SPARE 5
Sensor Fault: Check temperature sensor —
Spare 5.
SPARE SENSOR ALERT
TEMP SENSOR — SPARE 6
Sensor Fault: Check temperature sensor —
Spare 6.
SPARE SENSOR ALERT
TEMP SENSOR — SPARE 7
Sensor Fault: Check temperature sensor —
Spare 7.
SPARE SENSOR ALERT
TEMP SENSOR — SPARE 8
Sensor Fault: Check temperature sensor —
Spare 8.
SPARE SENSOR ALERT
TEMP SENSOR — SPARE 9
Sensor Fault: Check temperature sensor —
Spare 9.
91
Summary of Contents for 17
Page 13: ...Fig 6 Open Drive 17 Series Lubrication Cycle 13 ...
Page 15: ...Fig 7 17EX Controls and Sensor Locations 15 ...
Page 16: ...Fig 7 17EX Controls and Sensor Locations cont 16 ...
Page 17: ...Fig 7 17EX Controls and Sensor Locations cont 17 ...
Page 19: ...Fig 8 19EX Controls and Sensor Locations cont 19 ...
Page 23: ...Fig 16 17 19EX LID Menu Structure 23 ...
Page 24: ...Fig 17 17 19EX Service Menu Structure 24 ...