Table 2 — LID Screens (cont)
EXAMPLE 7 — SERVICE1 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press
MENU
.
2. Press SERVICE .
3. Scroll down to highlight EQUIPMENT SERVICE.
4. Press SELECT .
5. Scroll down to highlight SERVICE1.
6. Press SELECT .
DESCRIPTION
CONFIGURABLE RANGE
UNITS
REFERENCE POINT NAME
DEFAULT VALUE
Motor Temp Override*
150-200 (66-93)
DEG F (DEG C)
mt
over
200 (93)
Cond Press Override
90-200 (620-1379)
PSI (kPa)
cp
over
125 (862)
Refrig Override Delta T
2-5 (1-3)
DEG F (DEG C)
ref
over
3
D
(1.6
D
)
Chilled Medium
Water/Brine
medium
WATER
Brine Refrig Trippoint
8-40 (–13.3-4)
DEG F (DEG C)
br
trip
33 (1)
Compr Discharge Alert
125-200 (52-93)
DEG F (DEG C)
cd
alert
200 (93)
Bearing Temp Alert
165-210 (74-99)
DEG F (DEG C)
tb
alert
210 (99)
Water Flow Verify Time
0.5-5
MIN
wflow
t
5
Oil Press Verify Time
15-300
SEC
oilpr
t
15
Water/Brine Deadband
0.5-2.0 (0.3-1.1)
DEG F (DEG C)
cw
db
1.0 (0.6)
Recycle Restart Delta T
2.0-10.0 (1.1-5.6)
DEG F (DEG C)
rcycrdt
5 (2.8)
Recycle Shutdown Delta†
0.5-4.0 (.27-2.2)
rcycsdt
1.0 (0.6)
Surge Limit/HGBP Option
0/1
srg
hgbp
0
Select: Surge=0, HGBP=1
Surge/HGBP Delta T1
0.5-15 (0.3-8.3)
DEG F (DEG C)
hgb
dt1
1.5 (0.8)
Surge/HGBP Delta P1
30-170 (207-1172)
PSI (kPa)
hgb
dp1
50 (345)
Min. Load Points (T1/P1)
Surge/HGBP Delta T2
0.5-15 (0.3-8.3)
DEG F (DEG C)
hgb
dt2
10 (5.6)
Surge/HGBP Delta P2
30-170 (207-1172)
PSI (kPa)
hgb
dp2
85 (586)
Full Load Points (T2/P2)
Surge/HGBP Deadband
1-3 (0.6-1.6)
DEG F (DEG C)
hgb
dp
1 (0.6)
Surge Delta Percent Amps
10-50
%
surge
a
25
Surge Time Period
1-5
MIN
surge
t
2
Demand Limit Source
0/1
dem
src
0
Select: Amps=0, Load=1
Amps Correction Factor
1-8
corfact
3
Motor Rated Load Amps
1-9999
AMPS
a
fs
200
Motor Rated Line Voltage
1-9999
VOLTS
v
fs
460
Meter Rated Line KW
1-9999
kW
kw
fs
600
Line Frequency
0/1
HZ
freq
0
Select: 0=60 Hz, 1=50 Hz
Compr Starter Type
REDUCE/FULL
starter
REDUCE
Condenser Freeze Point
–20-35 (–28.9-1.7)
DEG F (DEG C)
cdfreeze
34 (1)
Soft Stop Amps Threshold
40-100
%
softstop
100
Stop to Start Timer†
3-50
MIN
stopmtr
20
NOTE:
D
= delta degrees.
*Information is applicable to hermetic machines only.
†Information is applicable to open-drive machines only.
31
1197
→
Summary of Contents for 17
Page 13: ...Fig 6 Open Drive 17 Series Lubrication Cycle 13 ...
Page 15: ...Fig 7 17EX Controls and Sensor Locations 15 ...
Page 16: ...Fig 7 17EX Controls and Sensor Locations cont 16 ...
Page 17: ...Fig 7 17EX Controls and Sensor Locations cont 17 ...
Page 19: ...Fig 8 19EX Controls and Sensor Locations cont 19 ...
Page 23: ...Fig 16 17 19EX LID Menu Structure 23 ...
Page 24: ...Fig 17 17 19EX Service Menu Structure 24 ...