Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides (cont)
G. COMPRESSOR JUMPSTART AND REFRIGERANT PROTECTION
PRIMARY MESSAGE
SECONDARY MESSAGE
ALARM MESSAGE/PRIMARY CAUSE
ADDITIONAL CAUSE/REMEDY
UNAUTHORIZED
OPERATION
UNIT SHOULD BE
STOPPED
CA
P Emergency: Compressor
running without control authorization.
Compressor is running with more than 10% RLA
and control is trying to shut it down. Throw power
off to compressor if unable to stop. Determine cause
before repowering.
POTENTIAL FREEZE-UP
EVAP PRESS/TEMP
TOO LOW
ERT Emergency: Freeze-up
prevention.
Determine cause. If pumping refrigerant out of ma-
chine, stop operation and go over pumpout
procedures.
FAILURE TO STOP
DISCONNECT POWER
RUN
AUX Emergency: DISCONNECT
POWER.
Starter and run and start contacts are energized
while control tried to shut down. Disconnect power
to starter.
LOSS OF
COMMUNCIATION
WITH STARTER
Loss of Communication with Starter: Check
machine.
Check wiring from PSIO to SMM. Check SMM mod-
ule troubleshooting procedures.
STARTER CONTACT
FAULT
ABNORMAL 1CR OR
RUN AUX
1CR
AUX Starter Contact Fault: Check
1CR/1M aux. contacts.
Starter run and start contacts energized while ma-
chine was off. Disconnect power.
POTENTIAL FREEZE UP
COND PRESS/TEMP
TOO LOW
CRT [VALUE] exceeded limit of [LIMIT]*
Emergency: Freeze-up prevention.
The condenser pressure transducer is reading a
pressure that could freeze the water in the con-
denser tubes. Check for condenser refrigerant leaks,
bad transducers, or transferred refrigerant. Place
the unit in Pumpdown mode to eliminate ALARM
if vessel is evacuated.
*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE]
is the actual pressure, temperature, voltage, etc., at which the control tripped.
H. NORMAL RUN WITH RESET, TEMPERATURE, OR DEMAND
PRIMARY MESSAGE
SECONDARY MESSAGE
PROBABLE CAUSE/REMEDY
RUNNING — RESET ACTIVE
4-20MA SIGNAL
Reset program active based upon Config table setup.
RUNNING — RESET ACTIVE
REMOTE SENSOR CONTROL
RUNNING — RESET ACTIVE
CHW TEMP DIFFERENCE
RUNNING — TEMP CONTROL
LEAVING CHILLED WATER
Default method of temperature control.
RUNNING — TEMP CONTROL
ENTERING CHILLED WATER
ECW control activated on Config table.
RUNNING — TEMP CONTROL
TEMPERATURE RAMP LOADING
Ramp loading in effect. Use Service1 table to modify.
RUNNING — DEMAND LIMITED
BY DEMAND RAMP LOADING
Ramp loading in effect. Use Service1 table to modify.
RUNNING — DEMAND LIMITED
BY LOCAL DEMAND SETPOINT
Demand limit setpoint is
,
actual demand.
RUNNING — DEMAND LIMITED
BY 4-20MA SIGNAL
Demand limit is active based on Config table setup.
RUNNING — DEMAND LIMITED
BY CCN SIGNAL
RUNNING — DEMAND LIMITED
BY LOADSHED/REDLINE
RUNNING — TEMP CONTROL
HOT GAS BYPASS
Hot Gas Bypass is energized. See surge prevention in the control
section.
RUNNING — DEMAND LIMITED
BY LOCAL SIGNAL
Active demand limit manually overridden or Status01 table.
RUNNING — TEMP CONTROL
ICE BUILD MODE
Machine is running under Ice Build temperature control.
88
Summary of Contents for 17
Page 13: ...Fig 6 Open Drive 17 Series Lubrication Cycle 13 ...
Page 15: ...Fig 7 17EX Controls and Sensor Locations 15 ...
Page 16: ...Fig 7 17EX Controls and Sensor Locations cont 16 ...
Page 17: ...Fig 7 17EX Controls and Sensor Locations cont 17 ...
Page 19: ...Fig 8 19EX Controls and Sensor Locations cont 19 ...
Page 23: ...Fig 16 17 19EX LID Menu Structure 23 ...
Page 24: ...Fig 17 17 19EX Service Menu Structure 24 ...