Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides
A. SHUTDOWN WITH ON/OFF/RESET-OFF
PRIMARY MESSAGE
SECONDARY MESSAGE
PROBABLE CAUSE/REMEDY
MANUALLY STOPPED — PRESS
CCN OR LOCAL TO START
PIC in OFF mode, press the CCN or local softkey to
start unit.
TERMINATE PUMPDOWN MODE
TO SELECT CCN OR LOCAL
Enter the Control Test table and select Terminate Lockout to
unlock compressor.
SHUTDOWN IN PROGRESS
COMPRESSOR UNLOADING
Machine unloading before shutdown due to Soft Stop feature.
SHUTDOWN IN PROGRESS
COMPRESSOR DEENERGIZED
Machine compressor is being commanded to stop. Water pumps are
deenergized within one minute.
ICE BUILD
OPERATION COMPLETE
Machine shutdown from Ice Build operation.
B. TIMING OUT OR TIMED OUT
PRIMARY MESSAGE
SECONDARY MESSAGE
PROBABLE CAUSE/REMEDY
READY TO START IN XX MIN
UNOCCUPIED MODE
Time schedule for PIC is unoccupied.
Machines will start only when occupied.
READY TO START IN XX MIN
REMOTE CONTACTS OPEN
Remote contacts have stopped machine. Close contacts to start.
READY TO START IN XX MIN
STOP COMMAND IN EFFECT
Chiller START/STOP on Status01 manually forced to stop. Release
value to start.
READY TO START IN XX MIN
RECYCLE RESTART PENDING
Machine in recycle mode.
READY TO START
UNOCCUPIED MODE
Time schedule for PIC is UNOCCUPIED. Machine will start when
occupied. Make sure the time and date have been set on the
Service menu.
READY TO START
REMOTE CONTACTS OPEN
Remote contacts have stopped machine. Close contacts to start.
READY TO START
STOP COMMAND IN EFFECT
Chiller START/STOP on Status01 manually forced to stop. Release
value to start.
READY TO START IN XX MIN
REMOTE CONTACTS CLOSED
Machine timer counting down unit. Ready for start.
READY TO START IN XX MIN
OCCUPIED MODE
Machine timer counting down unit. Ready for start.
READY TO START
REMOTE CONTACTS CLOSED
Machine timers complete, unit start will commence.
READY TO START
OCCUPIED MODE
Machine timers complete, unit start will commence.
STARTUP INHIBITED
LOADSHED IN EFFECT
CCN loadshed module commanding chiller to stop.
READY TO START IN XX MIN
START COMMAND IN EFFECT
Chiller START/STOP on Status01 has been manually forced to start.
Machine will start regardless of time schedule or remote contact
status.
C. IN RECYCLE SHUTDOWN
PRIMARY MESSAGE
SECONDARY MESSAGE
PROBABLE CAUSE/REMEDY
RECYCLE RESTART PENDING
OCCUPIED MODE
Unit in recycle mode, chilled water temperature is not high enough
to start.
RECYCLE RESTART PENDING
REMOTE CONTACT CLOSED
Unit in recycle mode, chilled water temperature is not high enough
to start.
RECYCLE RESTART PENDING
START COMMAND IN EFFECT
Chiller START/STOP on Status01 manually forced to start, chilled
water temperature is not high enough to start.
RECYCLE RESTART PENDING
ICE BUILD MODE
Machine in ICE BUILD mode. Chilled Water/Brine Temperature is
satisfied for Ice Build Setpoint temperature.
D. PRE-START ALERTS: These alerts only delay start-up. When alert is corrected, the start-up will continue. No reset is necessary.
PRIMARY MESSAGE
SECONDARY MESSAGE
ALARM MESSAGE/PRIMARY CAUSE
ADDITIONAL CAUSE/REMEDY
PRESTART ALERT
STARTS LIMIT EXCEEDED
STARTS EXCESSIVE Compressor Starts (8 in
12 hours)
Depress the RESET softkey if additional start is
required. Reassess start-up requirements.
PRESTART ALERT
HIGH MOTOR TEMPERATURE
MTRW [VALUE] exceeded limit of [LIMIT]*.
Check motor temperature.
Check motor cooling line for proper operation.
Check for excessive starts within a short time
span.
PRESTART ALERT
HIGH BEARING TEMPERATURE
MTRB [VALUE] exceeded limit of [LIMIT]*.
Check thrust bearing temperature.
Check oil heater for proper operation, check for
low oil level, partially closed oil supply valves,
etc. Check sensor accuracy.
PRESTART ALERT
HIGH DISCHARGE TEMP
CMPD [VALUE] exceeded limit of [LIMIT]*.
Check discharge temperature.
Check sensor accuracy. Allow discharge tem-
perature to cool. Check for excessive starts.
PRESTART ALERT
LOW REFRIGERANT TEMP
ERT [VALUE] exceeded limit of [LIMIT]*. Check
refrigerant temperature.
Check transducer accuracy. Check for low chilled
water/brine supply temperature.
PRESTART ALERT
LOW OIL TEMPERATURE
OILT [VALUE] exceeded limit of [LIMIT]*.
Check oil temperature.
Check oil heater power, oil heater relay. Check
oil level.
PRESTART ALERT
LOW LINE VOLTAGE
V
P [VALUE] exceeded limit of [LIMIT]*.
Check voltage suppy.
Check voltage supply. Check voltage transform-
ers. Consult power utility if voltage is low. Cali-
brate voltage reading on STATUS01 Table.
PRESTART ALERT
HIGH LINE VOLTAGE
V
P [VALUE] exceeded limit of [LIMIT]*.
Check voltage supply.
Check voltage supply. Check voltage transform-
ers. Consult power utility if voltage is low. Cali-
brate voltage reading on STATUS01 table.
PRESTART ALERT
HIGH CONDENSER PRESSURE
CRP [VALUE] exceeded limit of [LIMIT]*. Check
condenser water and transducer.
Check for high condenser water temperature.
Check transducer accuracy.
*[LIMIT] is shown on the LID as temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE]
is the actual pressure, temperature, voltage, etc., at which the control tripped.
86
Summary of Contents for 17
Page 13: ...Fig 6 Open Drive 17 Series Lubrication Cycle 13 ...
Page 15: ...Fig 7 17EX Controls and Sensor Locations 15 ...
Page 16: ...Fig 7 17EX Controls and Sensor Locations cont 16 ...
Page 17: ...Fig 7 17EX Controls and Sensor Locations cont 17 ...
Page 19: ...Fig 8 19EX Controls and Sensor Locations cont 19 ...
Page 23: ...Fig 16 17 19EX LID Menu Structure 23 ...
Page 24: ...Fig 17 17 19EX Service Menu Structure 24 ...