Table 10 — 17/19EX Heat Exchanger, Economizer/Storage Vessel, Piping, and Pumpout Unit Weights*
COOLER
SIZE†
COOLER
TOTAL
WEIGHT
COOLER
CHARGE
ECONOMIZER/
STORAGE
VESSEL**
ECONOMIZER
REFRIGERANT
MISCELLANEOUS
PIPING
PUMPOUT
UNIT
Dry
Operating††
Refrigerant
Water
lb
kg
lb
kg
lb
kg
lb
kg
lb
kg
lb
kg
lb
kg
lb
gal
kg
L
31
14,173
6 429
17,518
7 946
1,540
699
1,810
217
821
821
7,169
3252
610
277
820
372
210
95
32
14,538
6 594
18,117
8 218
1,640
744
1,944
233
882
882
33
14,904
6 760
18,722
8 492
1,740
789
2,078
249
943
943
41
21,674
9 831
26,120
11 848
1,900
862
2,441
293
1 107
1 107
7,169
3 252
610
277
1,095
497
42
22,019
9 988
26,736
12 127
2,000
907
2,575
309
1 168
1 168
43
22,364
10 144
27,322
12 393
2,100
953
2,709
325
1 229
1 229
44
23,841
10 814
29,836
13 533
2,190
993
3,285
394
1 490
1 490
45
25,032
11 354
30,790
13 966
2,260
1 025
3,006
361
1 363
1 363
7,900
3 583
840
381
1,149
521
46
25,529
11 580
31,658
14 360
2,360
1 070
3,192
383
1 448
1 448
47
26,025
11 805
32,496
14 740
2,460
1 116
3,378
405
1 532
1 532
48
28,153
12 770
36,053
16 353
2,540
1 152
4,173
500
1 893
1 893
CONDENSER
SIZE†
CONDENSER TOTAL WEIGHT
CONDENSER CHARGE
Dry
Operating††
Refrigerant
Water
lb
kg
lb
kg
lb
kg
lb
gal
kg
L
31
10,454
4 742
13,022
5 907
950
431
1,613
193
732
732
32
10,809
4 903
13,514
6 130
950
431
1,750
210
794
794
33
11,164
5 064
14,000
6 350
950
431
1,886
226
855
855
41
13,768
6 245
16,999
7 711
1,090
494
2,146
257
973
973
42
14,118
6 404
17,498
7 937
1,090
494
2,282
274
1 035
1 035
43
14,468
6 563
17,978
8 155
1,090
494
2,419
290
1 097
1 097
45
16,676
7 564
20,800
9 435
1,400
635
2,720
326
1 234
1 234
46
17,172
7 789
21,489
9 747
1,400
635
2,908
348
1 319
1 319
47
17,669
8 015
22,178
10 060
1,400
635
3,096
371
1 404
1 404
51
17,188
7 796
20,993
9 522
1,100
499
2,707
325
1 228
1 228
52
17,848
8 096
21,923
9 944
1,100
499
2,964
355
1 344
1 344
53
18,400
8 346
22,682
10 288
1,100
499
3,178
381
1 442
1 442
55
20,725
9 401
25,598
11 611
1,420
644
3,453
412
1 566
1 566
56
21,663
9 826
26,896
12 199
1,420
644
3,808
457
1 727
1 727
57
22,446
10 181
27,980
12 691
1,420
644
4,105
492
1 862
1 862
*If a machine configuration other than 2-pass, 150 psig (1034 kPa), NIH water-
box configuration is used, refer to Tables 11 and 13 to obtain the additional dry
and water weights that must be added to the values shown in this table.
†Cooler and condenser weights shown are based upon 2-pass, nozzle-in-head
(NIH) waterboxes with 150 psig (1034 kPa) covers. Includes components at-
tached to cooler, but does not include suction/discharge, elbow, or other in-
terconnecting piping.
**Dry weight includes all components attached to economizer: Covers, float
valves, brackets, control center (31 lb [14 kg]), and power panel (20 lb
[9 kg]). Dry weight does not include compressor weight, motor weight, or
pumpout condensing unit weight. The pumpout condensing unit weight is
210 lb (95 kg). For compressor and motor weights, refer to Table 12.
††Operating weight is the sum of the dry weight, refrigerant weight, and water
weight.
Fig. 54 — Model Number Nomenclature for Compressor Size (See Fig. 1 Also)
98
Summary of Contents for 17
Page 13: ...Fig 6 Open Drive 17 Series Lubrication Cycle 13 ...
Page 15: ...Fig 7 17EX Controls and Sensor Locations 15 ...
Page 16: ...Fig 7 17EX Controls and Sensor Locations cont 16 ...
Page 17: ...Fig 7 17EX Controls and Sensor Locations cont 17 ...
Page 19: ...Fig 8 19EX Controls and Sensor Locations cont 19 ...
Page 23: ...Fig 16 17 19EX LID Menu Structure 23 ...
Page 24: ...Fig 17 17 19EX Service Menu Structure 24 ...