Displayed Text
Fault Cause
Corrective Action
ERROR CODES
(Cont.)
Code
TROUBLESHOOTING GUIDE
(Cont.)
B020
B030
B040
B050
B060
RIO - Invalid
BTW Type
RIO - Invalid
BTR Type
Gun/Channel
Number
RIO - Invalid
BTR Job
Number
RIO - Invalid
BTW Length
The PLC has issured a BTW with an
invalid BTW data type in the first word
offset.
The PLC has issued a BTW with an
invalid BTR data type in the second
word offset.
The PLC has issued a BTW with an
invalid gun or channel number in the
third word offset.
The PLC has issued a BTW with an
invalid job number in the fourth word
offset.
The PLC has issued a BTW with an
invalid message length (word count).
Have the PLC programmer reference the
"DynaFlow Programmer" manual for the correct
BTW data types.
Have the PLC programmer reference the
"DynaFlow Programmer" manual for the correct
BTR data types.
Have the PLC programmer ensure gun and
channel numbers are between 1 and 8, or 0 if
not required for the particular data type.
Have the PLC programmer ensure job numbers
are between 1 and 100, or 0 if not required for
the particular data type.
Have the PLC programmer reference the
"DynaFlow Programmer" manual for the correct
BTW message lengths.
LN-9400-00-R11 (08/2018)
62 / 96
www.carlisleft.com
MAINTENANCE