Displayed Text
Fault Cause
Corrective Action
ERROR CODES
(Cont.)
Code
TROUBLESHOOTING GUIDE
(Cont.)
(Continued On Next Page)
Non-Existent
Program -
GUN #<>
JOB # number entered for the indicated
GUN does not exist. JOB # number
defaulted to 00.
Last digit indicates
CHANNEL #
.
Verify the following:
1. The JOB # has been saved in memory for
the indicated GUN.
2. The correct JOB # is being re-quested.
3. For discrete hard-wired JOB # select,
PROGRAM TOGGLE and JOB # inputs have
been asserted correctly by the PLC or host
computer.
A011
A012
A013
A014
A015
A016
A017
A018
A021
A022
A023
A024
A025
A026
A027
A028
B001
B010
GUN Flow Out
of Range
System Halted
RIO -
Communications
Error
The total flow rate for GUN # has
exceeded the MAXIMUM FLOW RATE
JOB parameter or fallen below the
MINIMUM FLOW RATE JOB parameter.
For Manual GUNs only.
System Ready/Halt input is
inactive.
PLC and DynaFlow are not set to the same:
- baud rate
- rack address
- rack size
- rack starting quarter
RIO cable is not connected to the proper
terminals at either end.
See "Flow Too Low" and "Flow Too High" faults.
This input is typically used as an interlock to other
control equipment or it is simply hard-wired to 24
VDC. Supply 24 VDC to the System Ready/Halt
input.
Check with the PLC programmer to determine the
correct values for baud rate, rack address, rack
size, and rack starting quarter and then set the
DynaFlow Interface Module DIP SW1 and SW2 to
the appropriate settings per "Interface Module DIP
SW2 Settings" and "Mother Board Signal ID (J3, J4,
J5, J6 Channel Cards" respect-ively in this section.
Check cable connections per Figure 25
RIO cable is not properly terminated at
each end.
Check cable connections per Figure 25 of this
manual.
Check each end of the cable to de-termine if the
terminating resistor is installed at each end. The
DynaFlow system may not be the last rack on the
RIO cable. The value of the terminating resistor is
based on cable length, baud rate, and if Extended
Node Capability is enabled at the PLC. If Extended
Node Capability is enabled, the terminating resis-
tors should always be 82 ohms. Otherwise, the
term-inating resistors should be 150 ohms for 57.6
and 115.2 Kbaud and 82 ohms for 230.4 Kbaud.
In any case, use 1/2 watt resistors.