13. GENERAL FEATURES AND MODELS
13.1 humiSteam models and electrical specifi cations
The following table lists the electrical data relating to the power supply
of the various models and the specifi cations of each. Note that some
models may be powered at diff erent voltages, obviously with diff erent
power input and steam production.
power supply
rated specifi cations
model
steam
production
(2; 4)
(kg/h)
power
(2)
(kW)
code
voltage
(1)
(V - type)
current
(2)
(A)
TAM confi guration
(5)
cable
(3)
(mm
2
)
line fuses
(3)
(A /
type)
wiring diagram
(Fig.)
UE001
1.5
1.1
D
230 - 1~
4.9
13.a
100
1.5
10 A / fast-blow
12.1
UE003
3
2.2
D
230 - 1~
9.8
13.d
300
2.5
16 A / fast-blow
12.1
K
230 - 3~
5.6
13.a
100
2.5
16 A / fast-blow
12.2
L
400 - 3~
3.2
13.d
100
1.5
10 A / fast-blow
12.3
UE005
5
3.7
D
230 – 1~
16.3
13.e
300
6.0
32 A / fast-blow
12.1
K
230 - 3~
9.4
13.c
300
2.5
16 A / fast-blow
12.2
L
400 - 3~
5.4
13.a
100
1.5
10 A / fast-blow
12.3
UE008
8
6.0
K
230 – 3~
15.1
13.c
300
6.0
32 A / fast-blow
12.2
L
400 – 3~
8.7
13.a
100
2.5
16 A / fast-blow
12.3
UE009
9
6.7
D
230 - 1~
29.3
13.a
500
10.0
40 A / fast-blow
12.1
UE010
10
7.5
K
230 – 3~
18.8
13.c
300
6.0
32 A / fast-blow
12.2
L
400 – 3~
10.8
13.d
300
2.5
16 A / fast-blow
12.3
UE015
15
11.2
K
230 – 3~
28.2
13.c
500
10.0
40 A / fast-blow
12.2
L
400 – 3~
16.2
13.a
300
6.0
32 A / fast-blow
12.3
E018
18
13.5
L
400 – 3~
19.5
13.a
300
6.0
32 A / fast-blow
12.3
UE025
25
18.7
K
230 – 3~
47.1
13.b
500
25
63 A / fast-blow
12.4
L
400 – 3~
27.1
13.c
500
16
50 A / fast-blow
12.5
UE035
35
26.2
K
230 – 3~
65.9
13.b
700
35
100 A / fast-blow
12.4
L
400 – 3~
37.9
13.b
500
16
60 A / fast-blow
12.5
UE045
45
33.7
K
230 – 3~
84.7
13.b
700
50
125 A / fast-blow
12.4
L
400 – 3~
48.7
13.c
700
25
80 A / fast-blow
12.5
UE065
65
48.7
L
400 – 3~
70.4
13.c
700
35
100 A / fast-blow
12.5
UE090
90
67.5
L
400 – 3~
97.43
13.c
700
70
125A / fast-blow
12.6
UE130
130
97.5
L
400 – 3~
140.73
13.c
700
95
160A / fast-blow
12.6
Tab. 13.a
(1)
tolerance allowed on the rated mains voltage: -15%, +10%;
(2)
tolerance on the rated values: +5%, -10% (EN 60335-1);
(3)
recommended values refer to laying PVC or rubber cables in closed conduits, 20 m
(65.6 feet) long; the standards in force must however be observed,
(4)
rated max instant steam production: the average steam production may be aff ected
by external factors, such as: ambient temperature, water quality, steam distribution
system;
(5)
refer to the wiring diagrams to verify
the data are not absolute and if these diff er from local standards, the latter
must prevail.
TAM confi gurations and connections (transformer for
measuring the current)
Important: the confi gurations and connections are already made
by CAREL, and no changes are required. The following diagrams
represent possible connection modes and may be useful in the event of
serious electrical malfunctions on the humidifi er.
All operations must only be performed by qualifi ed personnel, improper
use may cause serious damage.
one cable turn
one turn of the two cables
of the same phase
two cable turns of the same
phase
one cable in “double turn”
mode
three cable turns of the
same phase
700
500
300
100
700
500
300
100
700
500
300
100
700
500
300
100
700
500
300
100
Fig. 13.a
Fig. 13.b
Fig.13.c
Fig.13.d
Fig.13.e
Important:
to avoid interference, separate the power cables from the probe
•
cables.