16
EN
“UEX-PLUS” +030220621 - rel. 1.4 - 04.08.2009
installer
user
ser
vice
HUMIDISTAT (ON/OFF action)
connect outputs M7.1 and M7.2 to a humidistat
•
jumper outputs M2.7 and M2.8
•
M.2
M.7
M.8
M.2.1 M.2.2 M.2.3 M2.4 M.2.5 M.2.6 M.2.7 M.2.8
M.7.1 M.7.2
Fig. 4.e
HUMIDISTAT and REMOTE CONTACT (ON/OFF action)
connect outputs M7.1 and M7.2 to a humidistat
•
connect outputs M2.7 and M2.8 to a remote contact (e.g.: switch,
•
timer,…)
M.2
M.7
M.8
M.2.1 M.2.2 M.2.3 M2.4 M.2.5 M.2.6 M.2.7 M.2.8
M.7.1 M.7.2
Fig. 4.f
2. Enable and control the steam production using:
PROPORTIONAL EXTERNAL CONTROLLER
jumper outputs M2.7 and M2.8 or connect to a remote contact
•
connect outputs M2.1 and M2.2 to an external controller
•
The humidifi er can be programmed to receive one of the following
signals:
Voltage: 0 to 1 Vdc, 0 to 10 Vdc, 2 to 10 V
Current : 0 to 20 mA, 4 to 20 mA
Potentiometric: 135-1000 ohm, 0-135 ohm
M.2
M.7
M.8
M.2.1 M.2.2 M.2.3 M2.4 M.2.5 M.2.6 M.2.7 M.2.8
OUT
REF
Fig. 4.g
PROPORTIONAL EXTERNAL CONTROLLER WITH CAREL LIMIT PROBE
jumper outputs M2.7 and M2.8 or connect to a remote contact
•
connect outputs M2.1 and M2.2 to an external controller
•
connect the limit probe to terminals M2.3, M2.5 and M2.6
•
The humidifi er can be programmed to receive one of the following
signals:
Voltage: 0 to 1 Vdc, 0 to 10 Vdc, 2 to 10 V
Current : 0 to 20 mA, 4 to 20 mA
Potentiometric: 135-1000 ohm, 0-135 ohm
M.2
M.7
M.8
M.2.1 M.2.2 M.2.3 M2.4 M.2.5 M.2.6 M.2.7 M.2.8
OUT
REF
OUT H
M
+ (
G)
Fig. 4.h
The reference (zero) of the external controller must be connected to the
GND terminal (M2.2) and the control signal to terminal M2.1
CONTROL WITH CAREL MAIN PROBE
Complete action with control according to the humidity measured.
jumper outputs M2.7 and M2.8 or connect to a remote contact
•
connect the main probe to terminals M1.2, M2.2 and M2.3
•
M.2
M.7
M.8
M.2.1 M.2.2 M.2.3 M2.4 M.2.5 M.2.6 M.2.7 M.2.8
OUT H
M
+ (
G)
Fig. 4.i
CONTROL WITH CAREL MAIN PROBE AND LIMIT PROBE
jumper outputs M2.7 and M2.8 or connect to a remote contact
•
connect the main probe to terminals M1.2, M2.2 and M2.3
•
connect the limit probe to terminals M2.3, M2.5 and M2.6
•
OUT H
M
+ (
G)
M.2
M.7
M.8
M.2.1 M.2.2 M.2.3 M2.4 M.2.5 M.2.6 M.2.7 M.2.8
OUT H
M
+ (
G)
Fig. 4.j
CONTROL WITH CAREL TEMPERATURE PROBE
The humidifi er can be connected to both active probes (voltage or current
signal), and to passive NTC temperature probes (variable resistance).
CAREL active probe connection:
jumper outputs M2.7 and M2.8 or connect to a remote contact
connect the temperature probe to terminals M1.2, M2.2 and M2.3