12
EN
“UEX-PLUS” +030220621 - rel. 1.4 - 04.08.2009
installer
user
ser
vice
2.1 Supply water
Only use mains water with:
pressure between 0.1 and 0.8 MPa (14.5 and 116 PSI), temperature
•
between 1 and 40 °C (33.8 and104 °F) and an instant fl ow-rate no lower
than the rated fl ow of the fi ll solenoid valve, the connection is G3/4M
(see par. “Technical specifi cations” page 41);
range hardness 10 to 40 °F h (equal to 400 ppm of CaCO
•
3
), conductivity:
75 to 1250 μS/cm;
no organic compounds.
•
supply water
characteristics
unit of
measure
normal water
water with low
salt content
min.
max.
min.
max.
Hydrogen ions (pH)
7
8.5
7
8,5
Specifi c conductivity at
20°C (
σ
R, 20 °C
)
μS/cm
350
1250
75
300
Total dissolved solids (c
R
)
mg/l
(
1
)
(
1
)
(
1
)
(
1
)
Dry residue at 180°C (R
180
)
mg/l
(
1
)
(
1
)
(
1
)
(
1
)
Total hardness (TH)
mg/l CaCO
3
100
(2)
400
50
(2)
150
Temporary hardness
mg/l CaCO
3
60
(3)
300
30
(3)
100
Iron + Manganese
mg/l Fe+Mn
=
0.2
=
0.2
Chlorides
ppm Cl
=
30
=
20
Silica
mg/l SiO
2
=
20
=
20
Residual chlorine
mg/l Cl-
=
0.2
=
0.2
Calcium sulphate
mg/l CaSO
4
=
100
=
60
Metallic impurities
mg/l
0
0
0
0
Solvents, thinners,
detergents, lubricants
mg/l
0
0
0
0
Tab. 3.a
(1)
= values depend on the specifi c conductivity; in general:
TDS
≅
0,93 * σ
R, 20 °C
;
R
180
≅
0,65 * σ
R, 20 °C
(2)
= not less than 200% of the chloride content in mg/l CL
(3)
= not less than 300% of the chloride content in mg/l CL
There is not reliable relationship between hardness and conductivity of
the water
Important:
Important:
do not treat the water with softeners, this may cause the entrainment
•
of foam, aff ecting the operation of the unit;
do not add disinfectants or anticorrosive compounds to the water, as
•
these are potential irritants;
the use of well water, industrial water or water from cooling circuits
•
and, in general, any potentially chemically or bacteriologically
contaminated water is not recommended.
2.2 Drain water
this contains the same substances dissolved in the supply water,
•
however in larger quantities;
it may reach a temperature of 100 °C (212 °F);
•
it is not toxic and can be drained into the sewerage system.
•