13.6
CONTROLLING THE BOARD VIA NETWORK
The variables shown in the list are only some of the total variables
available.
DO NOT CONFIGURE VA-RIABLES THAT ARE NOT SHOWN IN THE TABLE,
OTHERWISE THE OPERATION OF THE HUMIDIFIER MAY BE AFFECTED.
“A”
read (R)/
write (W)
analogue variables* (Modbus®: REGISTERS)
CAREL - Modbus®
1
R
room probe/external regulator: demand
2
R/W
room probe/external regulator: minimum (calibration)
3
R/W
room probe/external regulator: maximum (calibration)
4
R/W
room probe/external regulator: off set (calibration)
5
R
current production (kg/h)
6
R
limit probe reading
7
R/W
limit probe: minimum (calibration)
8
R/W
limit probe: maximum (calibration)
9
R/W
limit probe: off set (calibration)
10
R
nominal production (kg/h)
11
R
total actual current (a)
12
R
cylinder 1: actual current (a)
13
R
cylinder 2: actual current (a)
14
R/W
maximum production (p0)
15
R/W
%rh set point
16
R/W
%rh diff erential
17
R/W
limit probe set point
18
R/W
limit diff erential
19
R/W
temperature set point
20
R/W
temperature diff erential
21
R/W
dehumidifi cation off set
22
R/W
dehumidifi cation diff erential
23
R/W
room probe: low humidity warning threshold
24
R/W
room probe: high humidity warning threshold
25
R/W
limit probe: high humidity warning threshold