3.4 Steam hoses
use CAREL hoses (max. 4 m long, see “
•
Models of steam hoses”, page 41
).
Rigid pipes may break and cause steam leaks;
avoid the formation of pockets or traps (causes of condensate);
•
avoid choking the hose due to tight bends or twisting.
•
fasten the end of the hose to the connectors on the humidifi er and the
•
steam distributor using metal clamps, so that these do not detach due
to the high temperature
.
3.5 Condensate drain hose
During the operation of the humidifi er some of the steam may condense,
causing a decline in effi
ciency and noise (gurgling).
To drain the condensate, connect a drain hose with a drain trap and a
minimum slope of 5° to the bottom of the humidifi er (see Fig. 3.d). CAREL
condensate drain hoses: code 312353APG
Important:
Important:
the drain trap in the condensate drain hose must be
fi lled with water before starting the humidifi er.
Example of correct and incorrect installation of the steam hose and
condensate drain hose.
Final checks
the steam outlet hoses run upwards and the distributor has a
minimum incline of 2° upwards (see Fig. 3.c);
the ends of the hose are tightened to the fi ttings with metal clamps;
the curves in the tubing are suffi
ciently wide (radius > 300 mm / 11.8”)
so as to not cause bending or choking;
the steam hose has no pockets or traps for condensate to form;
the paths of the steam and condensate hoses are as described in this
chapter (see Fig. 3.d);
the length of the steam hose is no greater than 4 metres (13.1 feet);
the incline of the steam hose is suffi
cient to allow correct draining of
the condensate (> 20° for the upward sections, > 5° for the downward
sections);
the incline of the condensate hose is at least 5° at every point;
the condensate hose always follows a downwards path and features a
drain trap (fi lled with water before starting operation) to avoid steam
being released.
YES
>5°
D> 200mm
>5°
R> 300mm
H
b
2m
YES
>20°
>5°
D>200mm
R>300mm
1
All UE models
Models UE25 to UE130
(1) extend the hose inside the humidifi er to the bottom tank.
YES
>20°
>5°
D>200mm
R>300mm
1
NO
NO
Models UE001 to UE025
(1): connection with fi ll tank
All UE models
Fig. 3.d