59
ENG
“heaterSteam” +0300087EN - rel. rel. 1.4 - 22.01.2021
Address
Variable name
Description
Default
Min
Max
UoM
Access
93
Alrm_SVOffl
ine.Active
Alarm ALA07: Supervisor offl
ine
Read
101
Alrm_HiBoilerTemp.Active
Alarm ALC05: High boiler temperature (>110°)
Read
102
Warn_AutotestCancel.Active
Warning ALW07: Autotest cancelled, saved and displayed
Read
103
Warn_NoDrainYet.Active
Warning ALW08: No drain to dilute (if micro-fi lling active)
Read
108
DisableVarUnitPause
Disable paused by monitoring service
(0: not disabled 1: disabled)
Read
Tab. 11.j
11.3 heaterSteam tERA service registration
The humidifi er can be connected to the Carel tERA service. This allows
remote monitoring of the humidifi er, saving the variables and therefore
creating a log of humidifi er operation. Use the Ethernet connection and
the humidifi er control port.
To connect the humidifi er to the tERA service, the MAC, the UID code
and password (called “tERA”) of the unit controller are required. This
information is available on the “Resources” page, accessible from the
controller web server (see chapter 9. Web Server).