![Carel HeaterSteam 4 UR002 User Manual Download Page 18](http://html1.mh-extra.com/html/carel/heatersteam-4-ur002/heatersteam-4-ur002_user-manual_2557527018.webp)
18
ENG
“heaterSteam” +0300087EN - rel. 1.4 - 22.01.2021
4.3 Control
board
The control board (S) is inside of the electrical panel in the wall dividing.
The auxiliary connections (probes, remote terminal, alarm) are made by
inserting the cables form the outside into the electrical panel.
To do this, use cables gland located on the base of the unit to the plug-in
screw terminals on the control board.
UR002-UR013
UR020-UR080
S
S
Fig. 4.i
M2
M9
1 2
1
1 2 3
1 2 3
4 5
2
1 2
1
1
2
2
1 2 3 4 5 6
J17C
G
2 1
J17L
J23
J24
J19
J20
J3
J16
M3
J18
2 1
J21
M8
M1
M5
M6
M12
1
1
2
3
4
5
6
7
8
2
1
1
3 2
3
1
2
2
1
2
1
2
main pr
obe
ex
t. r
egula
tor
GND
GND
Remot
e
ON/OFF
limit pr
obe
12V
dc
Control signal
Ethernet
GND
RS485 Serial
L+
L-
Alarm
relay
NO
NC
C
NO
C
Unit
status
relay
Fig. 4.j
Key:
Terminal
Function
Electrical specifi cations
M1
M1.1
GND (G0)
M1.2
Controller power supply
24Vac +10%/-15% 50/60Hz
M2
M2.1
Main room probe signal
input or signal from external
controller
0/1V, 0/10V, 2/10V, 0/20mA,
4/20mA, NTC 10 kΩ a 25 °C
M2.2
GND
M2.3
Probe power supply (+G)
+12 Vdc, maximum current that
can be delivered 50 mA; Protec-
tion against short-circuits
G
Probe power supply (+G)
CAREL 0-10 V
M2.4
Digital input for backup/
rotation function
Maximum current output: 5 mA;
Maximum voltage with contact
open: 13 Vdc
M2.5
Limit humidity probe signal
input
0/1V, 0/10V, 2/10V, 0/20mA,
4/20mA, NTC
M2.6
GND
M2.7
GND
M2.8
Remote on/off contact
digital input
Maximum current output: 5 mA;
Maximum voltage with contact
open: 13 Vdc
M3
M3.1
Fieldbus
Tx/Rx-
M3.2
Tx/Rx+
M3.3
GND
M5
M5.1
Unit status contact (NO)
250 Vac; 2 A with resistive load;
2 A with inductive load
M5.2
Unit status contact
common
M6
M6.1
Alarm common
250 Vac; 2 A with resistive load;
2 A with inductive load
M6.2
NC alarm contact
M6.3
NO alarm contact
Terminal
Function
Electrical specifi cations
M8
M8.1
Production request analo-
gue output
Output voltage range: 0-10 V
max 10 mA
M8.2
GND
M9
M9.1
Backup and rotation contact
common
250 Vac; 2 A with resistive load;
2 A with inductive load
M9.2
Backup and rotation NO
contact
M11
Ethernet port
M12
M12.1
BMS 485
Tx/Rx-
M12.2
Tx/Rx+
M12.3
GND
Earth connection
J18
pLAN/display terminal
J19
J19.1
Auxiliary/blower contact
(NO)
250 Vac; 2 A with resistive load;
2 A with inductive load
J19.2
Auxiliary/blower contact
common
USB Port (type A)
Ethernet RJ45 Port
Tab. 4.c
Summary of Contents for HeaterSteam 4 UR002
Page 2: ......
Page 4: ......
Page 6: ......
Page 91: ...91 ENG heaterSteam 0300087EN rel rel 1 4 22 01 2021...