![Carel HeaterSteam 4 UR002 User Manual Download Page 25](http://html1.mh-extra.com/html/carel/heatersteam-4-ur002/heatersteam-4-ur002_user-manual_2557527025.webp)
25
ENG
“heaterSteam” +0300087EN - rel. rel. 1.4 - 22.01.2021
Selecting and confi guring the model (only for replacement controllers
that are not confi gured):
if needing to replace the controller only
(heaterSteam process version spare part URH00000P4, heaterSteam
titanium version spare part URH00000T4), the fi rst time the controller is
powered on, the model will need to be set (capacity and power supply).
6.3 Shutdown
•
To avoid stagnation, drain the water from the
cylinder by pressing UP and DOWN together
for 5 seconds; to stop the drain cycle, press
ESC.
•
move the switch to 0, “OFF”.
I
0
OFF
Fig. 6.b
6.4 Graphic
terminal
The 4.3” touch graphic terminal has a graphic interface with coloured and
animated icons. The contents of the display can be scrolled up and down
simply and intuitively.
Fig. 6.c
The 6-button keypad provides simplifi ed access to all the confi guration
and programming operations:
Fig. 6.d
6.5 Touch
display
“HOME” menu
The “HOME” menu comprises information on the probes, including the
set point or external request signal.
Fig. 6.e
Pos.
Function
Pos.
Function
1
System menu
6
Alarm list
2
home
7
ON/OFF
3
Scheduler settings
8
Set point setting
4
System date and time
9
System information
5
Notifi cation centre
10
Descriptive icon of humidifi er
status
Tab. 6.a
6.5.1
S
ys
te
m m
e
nu
The System menu provides access to the system items that are available
without entering a password.
Fig. 6.f
Description of the menus:
Menu
Description
Clock
Date and time setting
Input/Output Display the analogue and digital inputs/outputs
Graphs
Display historical and real-time operation of the humidifi er
Functions
Special and manual functions
Scheduler
Manage scheduling of working time bands
Alarm thresh-
old
Set the alarm thresholds
Language
Set the menu language
Settings
Access advanced humidifi er confi guration (Installer password 77).
Menu: E. Settings.
Change unit of measure (Imperial/International)
Tab. 6.b
6.5.2
Sche
dul
e
r s
ett
in
g
s
Set the time bands for humidifi er activation. After enabling the scheduler,
six on/off time bands can be set for each day. Use the copy button to
copy the set time bands from one day to the next.
Fig. 6.g
Fig. 6.h
Summary of Contents for HeaterSteam 4 UR002
Page 2: ......
Page 4: ......
Page 6: ......
Page 91: ...91 ENG heaterSteam 0300087EN rel rel 1 4 22 01 2021...