CP40
Page 34 of 43
Installation Manual
October 2015 • Rev. 2.7
INPUT AND OUTPUT POINT WIRING
Each point on the SIOPT-16 input/output board can be individually
configured via jumpers to be:
an input point
a normally open output point
a normally closed output point
All supervised input points must use Cansec end-of-line resistors (CA-
EOLRES). If supervision is not required, it must be disabled by moving
switch 2 on the CP40's
Options DIP Switch (S2)
to the ON position.
In the diagram above, point 1 is configured as an input and points 2-3
are configured as outputs.