BAUD RATE DIP SWITCH (S3)
The Baud Rate DIP switch (S3) is used to set communication baud
rate.
NOTE
: Default is 9600 baud. Do not change this default rate.
READER TYPE DIP SWITCH (S5)
The Reader Type DIP Switch (S5) is used to specify the reader
type(s), exit button use, and the Wiegand data format.
* See Appendix for Magstripe Reader Jumper settings diagram.
NOTE: If switch #2 or #5 is off (exit button disabled) then there is no forced
entry alarm for that door/reader.
*
*