CP40
Page 33 of 43
Installation Manual
October 2015 • Rev. 2.7
INSTALLING THE SIOPT-16 INPUT/OUTPUT BOARD
1.
Remove the SIOPT-16 input/output board from the anti-static bag. With the
power to the CP40 disconnected, connect the SIOPT-16 input/output board
ribbon cable and power cable.
2.
Snap the supplied plastic stand-offs into the mounting holes on the CP40.
Then align the mounting holes on the SIOPT-16 input/output board and
push down to snap the board into place.
3.
Enable the SIOPT-16 input/output board by moving switch 1 on the CP40's
Option Dip Switch (S2)
to the ON position as shown in the picture below:
NOTE
: For the changes to take effect, the CP40 panel must be reset by either
pressing the reset button or by powering up the unit.
4.
Optional:
If switch 2 on the CP40's
Option DIP Switch (S2)
is in the ON
position (pushed to the right), end-of-the-line resistors are not required for
point supervision and input points will not be supervised.