CP40
Page 29 of 43
Installation Manual
October 2015 • Rev. 2.7
INPUT POINT WIRING (NONSUPERVISED)
If supervision is not required and Cansec end-of-line resistors will not be
used, you must disable supervision at the
Options DIP Switch (S2)
by setting
switch 2 to ON as shown below.
OUTPUT POINT WIRING
NOTES:
-
Relay coil must not exceed
100mA
-
Diode should be installed at
the relay
-
Output s
ignal is an “open
collector” type thus a 5V
relay can be used