background image

 

 

13

 

The appliance and its individual gas shut-off valve must be 
disconnected from the supply piping when pressure testing 
the gas supply piping at pressures above ½ PSI 

Table 8: Gas Pressures at Inlet to Appliance 

 

PROPANE 

NATURAL 

GAS 

Minimum (inches W.C.) 

11 

Maximum (inches W.C.) 

11 

14 

*Recommended regulator settings is 7.0” w.c. 

The  gas  supply  line  must  be  of  adequate  size  to  prevent 
undue  pressure  drop  and  must  never  be  smaller  than  the 
size  of  the  connection  on  the  appliance.  Sizing  based  on 
Table 8 is recommended, depending on model. 
Before operating the appliance, the complete gas train and 
all connections must be tested using soap solution. 

Verify  that  the  appliance  is  supplied  with  the  type  of  gas 
specified on the rating plate. Heating values of local natural 
gas are to be between 950 and 1010 Btu/ft

3

. Consult factory 

if  heating  values  are  outside  this  range  or  if  a  gas  with  a 
mixture of constituents is being used. 

3.4 

CHECKING GAS SUPPLY PRESSURE 

 

Turn the main power switch to “OFF” position.  

 

Shut off gas supply at the manual gas cock in the gas 
piping to the appliance. If fuel supply is LP gas, shut off 
gas supply at the tank.  

 

Remove  the  1/8"  hex  plug  from  the  gas  pressure  test 
port  located  on  the  inlet  gas  supply  connection  at  the 
rear  of  the  appliance.  Install  a  fitting  in  the  inlet 
pressure  tapping  suitable  to  connect  to  a  manometer 
or  magnahelic  gauge.  Range  of  scale  should  be  0  to 
14 inch W.C. or greater to check inlet pressure  

 

Turn  on  gas  supply  at  the  field  installed  manual  gas 
cock; turn on LP gas at tank if required.  

 

Turn the power switch to “ON” position.  

 

Adjust the thermostat set point to call for heat.  

 

Observe the gas supply pressure as the burner fires at 
100%  of  rated  input.  Supply  pressure  is  to  remain 
stable. 

 

Ensure  inlet  pressure  is  within  specified  range. 
Minimum  and  maximum  gas  supply  pressures  are 
specified in Table 8. 

 

If gas pressure  is  out  of  range,  contact  the  gas  utility, 
gas  supplier,  qualified  installer  or  service  agency  to 
determine  necessary  steps  to  provide  proper  gas 
pressure to the control.  

 

If gas supply pressure is within normal range, proceed 
to  remove  gas  manometer  and  replace  pressure  tap 
fittings  in  the  gas  piping  to  the  appliance.    Turn  the 
power switch to “OFF” position. 

 

Turn  on  gas  supply  at  the  manual  valve;  turn  on  LP 
gas at tank if required.  

 

Turn the power switch to “ON” position.  

 

Adjust  the  thermostat  temperature  set  point  to  the 
desired water temperature so the appliance will call for 
heat.  

 

Check  appliance  performance  by  cycling  the  system 
while you observe burner response. The burner should 
ignite  promptly.    Flame  profile  should  be  stable,  see 
section 10.2, Visually Check Main Burner Flames. Turn 
system off and allow  burner to  cool,  then cycle burner 
again 

to 

ensure 

proper 

ignition 

and 

flame 

characteristics.  

IMPORTANT 

Upon completion of initial installation or following any repair 

work on the gas system, leak test all gas connections with a 

soap solution while the main burner is firing. Immediately 

repair any leak found in the gas train or related components. 

DO NOT operate an appliance with a leak in the gas train, 

valves or related gas piping. 

 

3.5 

HIGH and LOW GAS PRESSURE SWITCHES 
(Optional) 

High  and  low  gas  pressure  switches  are  available  as  an 
option  and  are  wired  in  series  with  the  blocked  flue  switch. 
The  high  gas  pressure  switch  is  used  to  monitor  the 
differential  gas  pressure  between  the  outlet  of  the  control 
valve and the fan inlet. If differential gas pressure exceeds the 
maximum  setting  of  the  pressure  switch,  the  appliance  will 
shut  down  and  a  low  air  condition  will  be  indicated  on  the 
display  panel.  The  low  gas  pressure  switch  is  to  monitor  the 
minimum  incoming  gas  supply  pressure  supplied  to  the  gas 
train.  If  gas  pressure  falls  below  the  minimum  setting  of  the 
pressure  switch,  the  appliance  will  shut  down  and  a  low  air 
condition will be displayed on the display panel. 

3.6 

AIR/GAS RATIO VALVE 

The  main  gas  valve  supplying  gas  to  the  burner  on  this 
appliance utilizes a servo pressure regulator providing a slow 
opening,  fast  closing  safety  shut  off  and  air/gas  ratio  control 
for  the  gas  combustion  process.  The  valve  is  a  1:1  negative 
pressure  gas  valve.  The  valve  performs  the  functions  of  a 
pressure  regulator,  safety  shutoff,  and  air/gas  ratio  control. 
Full closing of the valve seat occurs in less than 0.8 seconds 
when the valve is de-energized. Operation of the gas valve in 
combination  with  the  combustion  air  fan  allows  the  burner 
input  rate  to  vary  from  20%  to  100%  based  on  temperature 
demand.  The  inlet  gas  supply  pressure  must  be  maintained 
within the specified minimum and maximum pressures.  

The air/gas ratio is preset at the factory and adjustment is not 
usually  required  if  gas  supply  pressure  is  maintained  within 
the specified range.  
There are no serviceable parts on the air/gas ratio valve 
control. 

Figure 12: TH 82 – 252 1:1 Air/Gas Ratio Control Valve  

 

Figure 13: TH 292 – 392 1:1 Air/Gas Ratio Control Valve 

 

 
 

 

 

High fire adjustment: 
use throttle screw 
located on venturi 

Low fire adjustment 
screw Torx 40m 
clockwise increases CO

Gas Inlet

 

Low-fire air gas ratio adjustment 
(use Torx 40 for adjustment, 
clockwise increases CO

2

High-fire air gas ratio adjustment (Use 
slotted screwdriver for adjustment, 
counter-clockwise increases CO

2

Summary of Contents for TH082

Page 1: ...ity of this or any other appliance WHAT TO DO IF YOU SMELL GAS o Do not try to light any appliance o Do not touch any electrical switch do not use any phone in your building o Immediately call your ga...

Page 2: ......

Page 3: ...ERMINATION AND AIR INLET CLEARANCES 9 2 5 1 Sidewall Venting 9 2 5 2 Sidewall Air Inlet 10 2 5 3 Sidewall Concentric Vent Air 10 2 6 Vertical Direct Venting 10 PART 3 GAS CONNECTION 12 3 1 GAS CONNECT...

Page 4: ...MENT 41 10 4 1 Condensate Volume 41 10 5 IGNITER AND FLAME SENSOR ELECTRODES 42 10 6 CHECK IGNITER GROUND WIRING 42 10 7 BURNER MAINTENANCE 42 10 7 1 Burner Removal and Cleaning 42 10 8 REMOVAL OF COM...

Page 5: ...arrier 1 4 DISPLAY UNIT The display unit will indicate status and will display selected temperature Refer to Part 8 TH Control Panel which provides details to modes and error codes displayed on the ap...

Page 6: ...n anything against it store trash or debris near it stand on it or in any way block the flow of fresh air to appliance UNDER NO CIRCUMSTANCES may flammable materials such as gasoline or paint thinner...

Page 7: ...ll soot or other obstructions from the chimney and flue which might impede draft action Replace any damaged or deteriorated parts of the venting system A qualified service technician should follow thi...

Page 8: ...e designed for indoor installation Indoor Models must be installed indoors where it is protected from exposure to wind rain and weather The appliance designed for outdoor installation Outdoor Models m...

Page 9: ...im F in Dim G in Dim H in Equivalent Length of Vent Air Intake Pipes at Recommended Diameter in Water Conn at Boiler in NPT Gas Conn at Boiler in NPT Category IV CAT II Comb Vents Over 25 and up to 10...

Page 10: ...r adequate operation All installations must allow sufficient space for servicing the vent connections water pipe connections circulating pump bypass piping and other auxiliary equipment as well as the...

Page 11: ...to the vent terminal The weight of the venting system must not rest on the unit Adequate support of the venting system must be provided in compliance with local codes and other applicable codes All co...

Page 12: ...vertical or horizontal Outside air ducted to jacket flange Indoor Air Table 6 Required Vent and Air Inlet Diameters Equivalent Length of Vent Air Intake Pipes at Recommended Diameter Input BTU hr Cat...

Page 13: ...of the vent terminal shall be located at least 3 feet 1m above grade or above normal snow levels In all cases the appliance shall be installed in accordance with local codes 3 The TH can vent up to 10...

Page 14: ...te below a forced air inlet at any distance 4 The termination cannot terminate below grade Position the termination where vapours will not damage walls or plants or may be otherwise objectionable 5 Th...

Page 15: ...east 3 feet 1m above grade or above normal snow levels In all cases the appliance shall be installed in accordance with local codes 3 The termination MUST NOT terminate below a forced air inlet at any...

Page 16: ...liance connection Installation of a union at the appliance gas line connection is required for ease of service and removal of the gas train Install a manual main gas shutoff valve outside of the appli...

Page 17: ...rve burner response The burner should ignite promptly Flame profile should be stable see section 10 2 Visually Check Main Burner Flames Turn system off and allow burner to cool then cycle burner again...

Page 18: ...e burner Airborne contaminants such as dust dirt concrete dust or dry wall dust can be drawn into the burner with the combustion air and block the burner surface area DO NOT operate this appliance dur...

Page 19: ...nt number of straight feet of pipe for each valve and fitting in the connecting piping must be considered to properly arrive at the total equivalent feet of straight pipe in the field installed piping...

Page 20: ...m 120VAC 60Hz single phase 15A circuit is required for the TH models TH 082 through TH 502 The appliance when installed must be electrically grounded in accordance with the requirements of the authori...

Page 21: ...fault is corrected the boiler will automatically return to normal operating state 5 4 ERROR TABLE The following tables provide a description of all the possible errors with the TH boiler Errors can be...

Page 22: ...circulate until the pump overrun timer is satisfied Frost Protection To prevent freezing of the heat exchanger the on board pump is turned on if the DHW temperature is below 45 o F The on board pump...

Page 23: ...te of the appliance 7 4 GAS VALVE Figure 19 Venturi and Gas Valve Arrangement The Gas Valve supplied with the TH is a combined valve venturi assembly A servo pressure regulator is incorporated into th...

Page 24: ...text on the LCD will be shown for 2 seconds followed by the software version number for an additional 2 seconds The Version relates to the version of software uploaded onto the boiler control The disp...

Page 25: ...a Temperature Display delta T temperature Outlet Temperature Inlet Temperature DHW Temperature Display DHW temperature When UP DOWN is pressed this allows the DHW setpoint temperature to be changed Ra...

Page 26: ...degrees Fahrenheit or degrees Celcius Range o F o C LBTHODLOD not used LBT Low Boiler Reset Temperature Range Off On 32 to 230 o F 0 110 o C Default Off HOD High Outdoor Reset Temperature Range Off O...

Page 27: ...ot require manual intervention The last received alert code is displayed in User mode To clear the alert code press the Reset button Refer to Table 13 in Section 5 4 2 for more details Alerts are auto...

Page 28: ...emperature display After 5 minutes of inactivity or when the Done button is pressed the TH returns to normal operation Maximum Firing Rate Max icon is flashing and the Diag icon is solid The heater wi...

Page 29: ...use of the boiler User Access to general boiler and display settings and adjustments to the central heating and domestic hot water setpoint Installer Access to all user parameters and allows for chang...

Page 30: ...er operation DHW Pump Pump C Additional contact rated for 1 6hp Sequence of Operation Pump A is energized on DHW Interlock Flow switch LWCO if equipped Blocked flue switch N C Low gas switch 4 5 w c N...

Page 31: ...CAL 2 Press and select Login 3 Select Advanced Setup 4 Select DHW Config Inlet Sensor operation 5 Select Demand switch Sensor only and Press 6 Select Mod sensor Inlet and Press go to step 7 DHW Stat o...

Page 32: ...es in LOCAL 2 Press and select Login 3 Select Advanced Setup 4 Select Burner Control Ignition 5 Select Adjustable lightoff rate and enter desired lightoff rate using 5 way control and press Adjust sta...

Page 33: ...iption Programming Instructions To view burner run time pump cycles for maintenance and service purposes 1 Place both toggle switches in LOCAL 2 Press and select Login 3 Select Advanced Setup 4 Select...

Page 34: ...ontrol Panel will be required to restart the ignition sequence The boiler has failed to ignite the burner after 5 unsuccessful attempts Verify that all air has been purged from gas line Inspect spark...

Page 35: ...ler if necessary Noisy Operation Supply Gas Issue Refer to Part 3 Gas Connection in this manual Natural Gas Pressure should read between 3 w c and 14 w c L P Gas Pressure should be at 11 w c Air Gas M...

Page 36: ...ceeded the maximum temperature allowed Measure the resistance of the flue sensor at room temperature it should be approximately 10k The supply outlet temperature has exceeded the setpoint temperature...

Page 37: ...turn at a time NO Verify gas valve is being powered by ignition control Check ignition speed is between 2500 to 3000 RPM using System Monitor NO Adjust ignition speed to 3000 RPM YES YES Burner light...

Page 38: ...tripped optional To identify the safety that is open set the multimeter to Vac and measure the voltage from one contact to ground The contacts produce a 24Vac when the circuit is closed Is vent and o...

Page 39: ...to ground The contacts produce a 24Vac when the circuit is closed Is pump powered NO Check pump wiring and pump delay relay YES Use meter to verify amperage draw on pump and verify it with rating labe...

Page 40: ...150 o F is selected and PVC venting is used the setpoint must be reduced to below 150 o F to avoid nuisance flame failures If a setpoint greater than 150 o F is required venting with CPVC AL29 4C 316...

Page 41: ...rod Is Flame sensor plug secure NO Fasten flame sensor plug securely to flame sensor wire and check for corrosion deposits at wire terminals YES Check continuity of flame sensor wire from flame sensor...

Page 42: ...Figure 25 Venturi Gas Valve Assembly To adjust the high fire setting on standard display Press and hold the Next button for 3 seconds to enter the diagnostic menu on the TH Control Panel Press Next u...

Page 43: ...ollowing screen appears Figure 30 Low Fire Adjustment Screen To return to normal operation press Done To adjust the low fire setting on the upgraded display 1 Press the button 2 Select Test and press...

Page 44: ...NINGS in this manual are complied with To service or adjust this appliance it is imperative that the serviceman utilize a combustion analyzer to read CO2 and CO according to Camus Hydronics recommenda...

Page 45: ...NOTE All gaskets on disassembled components must be replaced with new gaskets sealant on re assembly if required Gasket kits are available from the factory CAUTION When the vent system is disconnecte...

Page 46: ...o the fan inlet Disconnect the fan motor power wires at the harness Remove the direct spark igniter and the flame sensor Remove the three 3 T 25 screws holding the front burner flange in place to gain...

Page 47: ...supplied to 24VAC components may cause operational problems 10 11 COMBUSTIBLE MATERIALS CAUTION Keep appliance clear from combustible materials do not store GASOLINE and other flammable vapors and liq...

Page 48: ...h fresh water until the water begins to flow out of drain 5 Re install the lid and hold down screw on the condensate collection box WARNING The condensate collection box must be filled with water to p...

Page 49: ...ater on and allow time for the temperature to stabilize Check the temperature rise when the burner is firing at 100 of rated input 4 Compare the temperature rise on the Control Panel with the required...

Page 50: ...46 11 9 IGNITION CYCLE The ignition cycle is shown in the table below The values are the default factory settings Figure 36 TH Ignition Cycle...

Page 51: ...Figure 37 Dedicated DHW Suggested Piping Arrangement Figure 38 Combination Application Suggested Piping Arrangement Note Cold water piping should be below hot water connections to prevent heat migrat...

Page 52: ...48 PART 13 EXPLODED VIEW PARTS LIST...

Page 53: ...Air Inlet Adapter 14 0379 X X X X X X X 44 0009 X 9 Transition Arm GM20 70 020 01 X X X X X X X GM10 15 997 03 10 Venturi 459000 444 003 X X 459000 444 001 X 459000 446 051 X X 45900450 010 X X VMU30...

Page 54: ...X X X X 32 HX Support 14 5632 X X X 14 5612 X X 33 Flame Sensor GM10 35 109 01 X 34 Igniter GM10 35 108 01 X 35 Current Transformer MCSS A U X 36 Right Bracket 14 5513 20 25 X 37 Left Bracket 14 5410...

Page 55: ...r X 53 Metal Latch 6521 00 0551 YT X 54 Strike 7800 02 55 On Off Switch C6000ALBBCHLI X 56 Standard Display S7910B1006 X 57 Upgraded Display DSP49G2094 X 58 Gas Valve Relay T9CP1A54 24 X 59 TH Wire Ha...

Page 56: ...52 PART 14 ELECTRICAL DIAGRAMS 14 1 TH 82 502 INTERNALWIRING DIAGRAM...

Page 57: ...nd 2 Display Data Receive 3 Display Common J4 24VAC Power 1 9 Not Used 10 24VAC 11 Not Used 12 Ground J5 Gas Valve Safety String 1 Safety String Return 2 Gas Valve 24VAC 3 7 Not Used J6 Safety Annunci...

Page 58: ...d appliance temperature or operating at temperatures exceeding 210o F BURNER If within FIVE years after initial installation of the appliance a burner shall prove upon examination by Camus to be defec...

Page 59: ...uilt water heaters and heating boilers as well as a into every single unit For more information supplier of specialty HVAC products Our service line is open 24 hours 7 days a week on our innovative pr...

Reviews: