background image

 

 

41

 

10.3  CLEANING BOILER HEAT EXCHANGER 

Figure 35: Heat Exchanger & Burner Assembly 

 

1)  Shut down boiler: 

 

a) Turn the main power off to the boiler 

b) Shut off gas supply at the main manual valve  in 

the gas piping of the main appliance 

c) DO NOT drain the boiler unless it will be exposed 

to  freezing  temperatures.  If  using  antifreeze 
prevention  fluid  in  the  heat  exchanger,  DO  NOT 
drain. 

2)  Allow time for the boiler to cool to room temperature if it 

has been firing. 

3)  Remove the upper sheetmetal jacket. 

4)  Remove  igniter  and  flame  sensor  electrodes.  If 

necessary,  clean  with  steel  wool.  DO  NOT  use 
sandpaper. 

5)  Remove  the  fan/  mixing  tube  assembly  from  the  heat 

exchanger door. 

6)  Remove burner.  

7)  Examine burner and clean if required as per 10.7.1. 

8)  Examine  heat  exchanger  surfaces  to  determine  if 

cleaning  is  required.  If  cleaning  is  required  remove  the 
(6)  nuts  fastening  the  heat  exchanger  flange  from  the 
heat exchanger. 

9)  Disconnect  the  condensate  hose  from  the  heat 

exchanger  and  connect  a  5/8”  diameter  hose  (field 
supplied)  from  the  bottom  of  the  heat  exchanger  to  a 
drain 

10)  Use water proof material to carefully cover the refractory 

at  the  rear  of  the  combustion  chamber  of  the  heat 
exchanger 

11)  Use  a  vacuum  cleaner  to  remove  any  debris  that  has 

collected on the heat exchanger surfaces. DO NOT use 
any type of solvent. 

12)  Brush the heat exchanger with a nylon bristle brush. DO 

NOT  use  a  metal  brush.  Re-vacuum  the  heat 
exchanger. 

13)  Finish  cleaning  by  wiping  down  the  boiler  heating 

surfaces with a clean, damp cloth. 

14)  Rinse  out  any  additional  debris  with  a  low  pressure 

water  supply.  Start  rinsing  from  the  rear  of  the  heat 

exchanger  and  slowly  working  your  way  towards  the 
front of the heat exchanger. 

15)  Remove  the  water  proof  material  after  cleaning  is 

complete. 

16)  Re-install  the  heat  exchanger  door  by  evenly  torquing 

down  the  (6)  nuts  to  3  ft-lbs,  burner,  igniter  and  flame 
sensor, and fan/ mixing tube assembly. Fasten the nuts 
back to the heat exchanger assembly. 

17)  Re-connect the fan assembly to the boiler mixing tube. 

18)  Re-connect the condensate hose to the heat exchanger. 

NOTE

 

All gaskets on disassembled components  must  be  replaced 
with new gaskets/sealant on re-assembly, if required. Gasket 
kits are available from the factory 

 

CAUTION 

When the vent system is  disconnected for any reason it must 
be 

reassembled 

and 

resealed 

according 

to 

vent 

manufacturer’s instruction 

10.4 

CONDENSATE TREATMENT 

Condensate  occurs  when  the  products  of  combustion  are 
cooled  below  their  dew  point  in  the  heat  transfer  process. 
The  liquid  condensate formed  from  this  high efficiency  heat 
transfer  process  is  mildly  acidic.  The  condensate  will 
typically  have  a  pH  ranging  from  4.0  to  5.0  as  it  is 
discharged from the condensate drain of the appliance. The 
condensate collection box where the condensate is collected 
is  constructed  of  a  non-corrosive  plastic.  All  materials 
external  to  the  appliance  in  contact  with  the  condensate 
must  be  corrosion  resistant.  Condensate  must  be  able  to 
flow  freely  from  the  appliance.  All  condensate  flow  is 
accomplished  by  gravity  requiring  a  minimum  downward 
slope  of  1/4”  per  foot  (21mm/m)  to  ensure  proper  flow  to  a 
suitable drain. A neutralizer box is mounted inside each TH. 
All  condensate  piping  and  connections  must  be  easily 
accessible for routine maintenance and inspection. Use solid 
piping when running condensate line across the floor. Check 
neutralized  pH  level  regularly  or  as  required  by  local 
jurisdiction. Replace neutralizer medium as required. 

10.4.1 

Condensate Volume 

There  are  several  factors  affecting  amount  of  condensation 
created  by  the  appliance,  however  for  rough  approximation 
use. 
Condensation  Volume,  US  Gallon/Hr  =  Input,  MBH/1000  x 
5.0 

Many  codes  will  require  the  acidic  condensate  to  be 
neutralized  before  it  can  be  placed  in  a  drain  system.  A 
neutralizer  to  control  the  pH  of  the  liquid  discharged  to  a 
drain  system  is  provided  with  every  TH  boiler.  The 
neutralizer  consists  of  an  industrial  grade,  non-corrosive 
plastic  reservoir  for  collection  of  the  condensate.  The 
condensate  collects  in  the  reservoir  where  it  is  in  direct 
contact  with  calcium  carbonate  neutralizer  medium.  As  the 
reservoir  fills,  it  provides  an  extended  residence  time  to 
neutralize the condensate. Residency time in the neutralizer 
reservoir  allows  time  for  the  pH  to  be  raised.  Prime  the 
neutralizer reservoir with 1 litre of water. 

 

Summary of Contents for TH082

Page 1: ...ity of this or any other appliance WHAT TO DO IF YOU SMELL GAS o Do not try to light any appliance o Do not touch any electrical switch do not use any phone in your building o Immediately call your ga...

Page 2: ......

Page 3: ...ERMINATION AND AIR INLET CLEARANCES 9 2 5 1 Sidewall Venting 9 2 5 2 Sidewall Air Inlet 10 2 5 3 Sidewall Concentric Vent Air 10 2 6 Vertical Direct Venting 10 PART 3 GAS CONNECTION 12 3 1 GAS CONNECT...

Page 4: ...MENT 41 10 4 1 Condensate Volume 41 10 5 IGNITER AND FLAME SENSOR ELECTRODES 42 10 6 CHECK IGNITER GROUND WIRING 42 10 7 BURNER MAINTENANCE 42 10 7 1 Burner Removal and Cleaning 42 10 8 REMOVAL OF COM...

Page 5: ...arrier 1 4 DISPLAY UNIT The display unit will indicate status and will display selected temperature Refer to Part 8 TH Control Panel which provides details to modes and error codes displayed on the ap...

Page 6: ...n anything against it store trash or debris near it stand on it or in any way block the flow of fresh air to appliance UNDER NO CIRCUMSTANCES may flammable materials such as gasoline or paint thinner...

Page 7: ...ll soot or other obstructions from the chimney and flue which might impede draft action Replace any damaged or deteriorated parts of the venting system A qualified service technician should follow thi...

Page 8: ...e designed for indoor installation Indoor Models must be installed indoors where it is protected from exposure to wind rain and weather The appliance designed for outdoor installation Outdoor Models m...

Page 9: ...im F in Dim G in Dim H in Equivalent Length of Vent Air Intake Pipes at Recommended Diameter in Water Conn at Boiler in NPT Gas Conn at Boiler in NPT Category IV CAT II Comb Vents Over 25 and up to 10...

Page 10: ...r adequate operation All installations must allow sufficient space for servicing the vent connections water pipe connections circulating pump bypass piping and other auxiliary equipment as well as the...

Page 11: ...to the vent terminal The weight of the venting system must not rest on the unit Adequate support of the venting system must be provided in compliance with local codes and other applicable codes All co...

Page 12: ...vertical or horizontal Outside air ducted to jacket flange Indoor Air Table 6 Required Vent and Air Inlet Diameters Equivalent Length of Vent Air Intake Pipes at Recommended Diameter Input BTU hr Cat...

Page 13: ...of the vent terminal shall be located at least 3 feet 1m above grade or above normal snow levels In all cases the appliance shall be installed in accordance with local codes 3 The TH can vent up to 10...

Page 14: ...te below a forced air inlet at any distance 4 The termination cannot terminate below grade Position the termination where vapours will not damage walls or plants or may be otherwise objectionable 5 Th...

Page 15: ...east 3 feet 1m above grade or above normal snow levels In all cases the appliance shall be installed in accordance with local codes 3 The termination MUST NOT terminate below a forced air inlet at any...

Page 16: ...liance connection Installation of a union at the appliance gas line connection is required for ease of service and removal of the gas train Install a manual main gas shutoff valve outside of the appli...

Page 17: ...rve burner response The burner should ignite promptly Flame profile should be stable see section 10 2 Visually Check Main Burner Flames Turn system off and allow burner to cool then cycle burner again...

Page 18: ...e burner Airborne contaminants such as dust dirt concrete dust or dry wall dust can be drawn into the burner with the combustion air and block the burner surface area DO NOT operate this appliance dur...

Page 19: ...nt number of straight feet of pipe for each valve and fitting in the connecting piping must be considered to properly arrive at the total equivalent feet of straight pipe in the field installed piping...

Page 20: ...m 120VAC 60Hz single phase 15A circuit is required for the TH models TH 082 through TH 502 The appliance when installed must be electrically grounded in accordance with the requirements of the authori...

Page 21: ...fault is corrected the boiler will automatically return to normal operating state 5 4 ERROR TABLE The following tables provide a description of all the possible errors with the TH boiler Errors can be...

Page 22: ...circulate until the pump overrun timer is satisfied Frost Protection To prevent freezing of the heat exchanger the on board pump is turned on if the DHW temperature is below 45 o F The on board pump...

Page 23: ...te of the appliance 7 4 GAS VALVE Figure 19 Venturi and Gas Valve Arrangement The Gas Valve supplied with the TH is a combined valve venturi assembly A servo pressure regulator is incorporated into th...

Page 24: ...text on the LCD will be shown for 2 seconds followed by the software version number for an additional 2 seconds The Version relates to the version of software uploaded onto the boiler control The disp...

Page 25: ...a Temperature Display delta T temperature Outlet Temperature Inlet Temperature DHW Temperature Display DHW temperature When UP DOWN is pressed this allows the DHW setpoint temperature to be changed Ra...

Page 26: ...degrees Fahrenheit or degrees Celcius Range o F o C LBTHODLOD not used LBT Low Boiler Reset Temperature Range Off On 32 to 230 o F 0 110 o C Default Off HOD High Outdoor Reset Temperature Range Off O...

Page 27: ...ot require manual intervention The last received alert code is displayed in User mode To clear the alert code press the Reset button Refer to Table 13 in Section 5 4 2 for more details Alerts are auto...

Page 28: ...emperature display After 5 minutes of inactivity or when the Done button is pressed the TH returns to normal operation Maximum Firing Rate Max icon is flashing and the Diag icon is solid The heater wi...

Page 29: ...use of the boiler User Access to general boiler and display settings and adjustments to the central heating and domestic hot water setpoint Installer Access to all user parameters and allows for chang...

Page 30: ...er operation DHW Pump Pump C Additional contact rated for 1 6hp Sequence of Operation Pump A is energized on DHW Interlock Flow switch LWCO if equipped Blocked flue switch N C Low gas switch 4 5 w c N...

Page 31: ...CAL 2 Press and select Login 3 Select Advanced Setup 4 Select DHW Config Inlet Sensor operation 5 Select Demand switch Sensor only and Press 6 Select Mod sensor Inlet and Press go to step 7 DHW Stat o...

Page 32: ...es in LOCAL 2 Press and select Login 3 Select Advanced Setup 4 Select Burner Control Ignition 5 Select Adjustable lightoff rate and enter desired lightoff rate using 5 way control and press Adjust sta...

Page 33: ...iption Programming Instructions To view burner run time pump cycles for maintenance and service purposes 1 Place both toggle switches in LOCAL 2 Press and select Login 3 Select Advanced Setup 4 Select...

Page 34: ...ontrol Panel will be required to restart the ignition sequence The boiler has failed to ignite the burner after 5 unsuccessful attempts Verify that all air has been purged from gas line Inspect spark...

Page 35: ...ler if necessary Noisy Operation Supply Gas Issue Refer to Part 3 Gas Connection in this manual Natural Gas Pressure should read between 3 w c and 14 w c L P Gas Pressure should be at 11 w c Air Gas M...

Page 36: ...ceeded the maximum temperature allowed Measure the resistance of the flue sensor at room temperature it should be approximately 10k The supply outlet temperature has exceeded the setpoint temperature...

Page 37: ...turn at a time NO Verify gas valve is being powered by ignition control Check ignition speed is between 2500 to 3000 RPM using System Monitor NO Adjust ignition speed to 3000 RPM YES YES Burner light...

Page 38: ...tripped optional To identify the safety that is open set the multimeter to Vac and measure the voltage from one contact to ground The contacts produce a 24Vac when the circuit is closed Is vent and o...

Page 39: ...to ground The contacts produce a 24Vac when the circuit is closed Is pump powered NO Check pump wiring and pump delay relay YES Use meter to verify amperage draw on pump and verify it with rating labe...

Page 40: ...150 o F is selected and PVC venting is used the setpoint must be reduced to below 150 o F to avoid nuisance flame failures If a setpoint greater than 150 o F is required venting with CPVC AL29 4C 316...

Page 41: ...rod Is Flame sensor plug secure NO Fasten flame sensor plug securely to flame sensor wire and check for corrosion deposits at wire terminals YES Check continuity of flame sensor wire from flame sensor...

Page 42: ...Figure 25 Venturi Gas Valve Assembly To adjust the high fire setting on standard display Press and hold the Next button for 3 seconds to enter the diagnostic menu on the TH Control Panel Press Next u...

Page 43: ...ollowing screen appears Figure 30 Low Fire Adjustment Screen To return to normal operation press Done To adjust the low fire setting on the upgraded display 1 Press the button 2 Select Test and press...

Page 44: ...NINGS in this manual are complied with To service or adjust this appliance it is imperative that the serviceman utilize a combustion analyzer to read CO2 and CO according to Camus Hydronics recommenda...

Page 45: ...NOTE All gaskets on disassembled components must be replaced with new gaskets sealant on re assembly if required Gasket kits are available from the factory CAUTION When the vent system is disconnecte...

Page 46: ...o the fan inlet Disconnect the fan motor power wires at the harness Remove the direct spark igniter and the flame sensor Remove the three 3 T 25 screws holding the front burner flange in place to gain...

Page 47: ...supplied to 24VAC components may cause operational problems 10 11 COMBUSTIBLE MATERIALS CAUTION Keep appliance clear from combustible materials do not store GASOLINE and other flammable vapors and liq...

Page 48: ...h fresh water until the water begins to flow out of drain 5 Re install the lid and hold down screw on the condensate collection box WARNING The condensate collection box must be filled with water to p...

Page 49: ...ater on and allow time for the temperature to stabilize Check the temperature rise when the burner is firing at 100 of rated input 4 Compare the temperature rise on the Control Panel with the required...

Page 50: ...46 11 9 IGNITION CYCLE The ignition cycle is shown in the table below The values are the default factory settings Figure 36 TH Ignition Cycle...

Page 51: ...Figure 37 Dedicated DHW Suggested Piping Arrangement Figure 38 Combination Application Suggested Piping Arrangement Note Cold water piping should be below hot water connections to prevent heat migrat...

Page 52: ...48 PART 13 EXPLODED VIEW PARTS LIST...

Page 53: ...Air Inlet Adapter 14 0379 X X X X X X X 44 0009 X 9 Transition Arm GM20 70 020 01 X X X X X X X GM10 15 997 03 10 Venturi 459000 444 003 X X 459000 444 001 X 459000 446 051 X X 45900450 010 X X VMU30...

Page 54: ...X X X X 32 HX Support 14 5632 X X X 14 5612 X X 33 Flame Sensor GM10 35 109 01 X 34 Igniter GM10 35 108 01 X 35 Current Transformer MCSS A U X 36 Right Bracket 14 5513 20 25 X 37 Left Bracket 14 5410...

Page 55: ...r X 53 Metal Latch 6521 00 0551 YT X 54 Strike 7800 02 55 On Off Switch C6000ALBBCHLI X 56 Standard Display S7910B1006 X 57 Upgraded Display DSP49G2094 X 58 Gas Valve Relay T9CP1A54 24 X 59 TH Wire Ha...

Page 56: ...52 PART 14 ELECTRICAL DIAGRAMS 14 1 TH 82 502 INTERNALWIRING DIAGRAM...

Page 57: ...nd 2 Display Data Receive 3 Display Common J4 24VAC Power 1 9 Not Used 10 24VAC 11 Not Used 12 Ground J5 Gas Valve Safety String 1 Safety String Return 2 Gas Valve 24VAC 3 7 Not Used J6 Safety Annunci...

Page 58: ...d appliance temperature or operating at temperatures exceeding 210o F BURNER If within FIVE years after initial installation of the appliance a burner shall prove upon examination by Camus to be defec...

Page 59: ...uilt water heaters and heating boilers as well as a into every single unit For more information supplier of specialty HVAC products Our service line is open 24 hours 7 days a week on our innovative pr...

Reviews: