background image

 

 

15

 

PART 4 

WATER CONNECTION  

 

Check  all  applicable  local  heating,  plumbing  and 
building safety codes before proceeding. 

 

If the appliance is installed above radiation level it must 
be provided with a low water cut-off device at the time 
of appliance installation (available from Camus). Some 
local  codes  require  the  installation  of  a  low  water  cut-
off on all systems. 

 

A  temperature  and  pressure  relief  valve  is  supplied 
with  each  TH.  The  relief  valve  must  be  mounted  in  a 
vertical  position  and  piped  to  the  floor  in  a  manner 
acceptable to the enforcing authority. 

 

Be sure to provide unions and gate valves at inlet and 
outlet to the appliance so that it can be easily isolated 
for service.  

 

This  appliance  is  a  low  mass  stainless  steel  tube 
design  which  provides  for  instant  heat  transfer.  All 
appliances  are  supplied  with  an  internal  suitable 
specific  pump  mounted  in  place.  When  replacing  the 
pump, replace with one of equal or better-performance. 

 

An  air  vent  is  supplied  on  the  heat  exchanger  header 
to eliminate trapped air. Install venting devices at high 
points in the system as well to eliminate trapped air in 
the piping.  

 

Use  suitable  pipe  hangers  or  floor  stands  to  support 
the weight of all water and gas piping. 

 

The  TH  must  be  installed  so  that  the  gas  ignition 
system  components  are  protected  from  water 
(dripping,  spraying,  rain,  etc.)  during  appliance 
operation  and  service  (circulator  replacement,  control 
replacement, etc.)  

 

Pipe  cold  water  supply  below  hot  water  connection  to 
prevent  heat  migration  during  times  of  low  heat 
demand 

4.1 

INLET AND OUTLET CONNECTIONS 

 

All  water  connections  must  meet

 

American  National 

Standard Pipe Threads (NPT).  

 

For ease of service, install unions on inlet and outlet of 
the appliance. The connection to the appliance marked 
“Inlet” on the header should be used for return from the 
system. The connection on the header marked “Outlet” 
is to be connected to the supply side of the system.  

4.2 

MINIMUM PIPE SIZE REQUIREMENTS 

Minimum  water  pipe  connections  are  as  follows  for  TH 
single  unit  installations.  The  equivalent  number  of  straight 
feet  of  pipe  for  each  valve  and  fitting  in  the  connecting 
piping  must  be  considered  to  properly  arrive  at  the  total 
equivalent feet of straight pipe in the field installed piping to 
the appliance. Consult factory if longer piping distances are 
required for a specific application. It is recommended to use 
copper piping for all system piping to reduce the possibility 
of  the  formation  of  deposits,  which  may  result  in  heat 
exchanger starvation. 

System  pipe  size  must  be  in  accordance  with  Table  9 
(depending  on  model).  Connection  sizes  at  the  heater  are 
given in Table 4.  

 
 

 

 

Table 9: Minimal System Pipe Size 

Input, 

Water Size, 

NPT 

Btu/Hr 

[in.] 

80,000 

100,000 

150,000 

199,000 

1  

250,000 

1 1/4 

299,000 

1 1/4 

399,000 

1 1/2 

500,000 

1 1/2 

4.3 

HEAT EXCHANGER 

This appliance uses precision formed stainless steel tubing to 
maximize the heat transfer process and achieve 97% steady-
state efficiency. This heat exchanger is designed to withstand 
160 PSIG working pressure. 
A factory installed circulating pump ensures proper water flow 
during  burner  operation  and  creates  enough  velocity  inside 
the stainless steel tubes and headers that prevents scaling.  

4.4 

LOW WATER TEMPERATURE SYSTEMS  

In  combination  applications  where  the  heating  system 
requires supply water temperatures below 110°F, connections 
may  be  made  directly  to  the  TH  (Refer  to  Figure  35).  At 
incoming  temperatures  of  80

o

F  or  lower  the  TH  achieves 

maximum  efficiency.  Inlet  temperatures  must  not  drop  below 
40

o

F to prevent freezing. 

4.5 

PIPING ARRANGEMENTS 

4.5.1 

Field Supplied Components 

1)  Heater system piping 

Boiler  system  piping  MUST  be  sized  according  to 
Table 9. Reducing the pipe size can restrict the flow 
rate  through  the  tank  and  cause  an  excessive 
pressure drop. 

2)  Isolation Valves 

Use  only  full  port  ball  valves.  Failure  to  supply  full 
port  ball  valves  may  result  in  reduced  flow  rate 
through the tank. 

3)  Anti-Scald Mixing Valve  

An  anti-scaled  mixing  valve  is  recommended  when 
DHW storage is above 120

o

F. 

4)  Unions 

Recommended for ease of serviceability. 

5)  System Temperature Sensor 

A system temperature sensor is to be installed in the 
main  header  at  a  point  to  detect  controlled 
temperature  and  where  it  will  not  lead  to  short-
cycling of the boiler. 

 

 

Summary of Contents for TH082

Page 1: ...ity of this or any other appliance WHAT TO DO IF YOU SMELL GAS o Do not try to light any appliance o Do not touch any electrical switch do not use any phone in your building o Immediately call your ga...

Page 2: ......

Page 3: ...ERMINATION AND AIR INLET CLEARANCES 9 2 5 1 Sidewall Venting 9 2 5 2 Sidewall Air Inlet 10 2 5 3 Sidewall Concentric Vent Air 10 2 6 Vertical Direct Venting 10 PART 3 GAS CONNECTION 12 3 1 GAS CONNECT...

Page 4: ...MENT 41 10 4 1 Condensate Volume 41 10 5 IGNITER AND FLAME SENSOR ELECTRODES 42 10 6 CHECK IGNITER GROUND WIRING 42 10 7 BURNER MAINTENANCE 42 10 7 1 Burner Removal and Cleaning 42 10 8 REMOVAL OF COM...

Page 5: ...arrier 1 4 DISPLAY UNIT The display unit will indicate status and will display selected temperature Refer to Part 8 TH Control Panel which provides details to modes and error codes displayed on the ap...

Page 6: ...n anything against it store trash or debris near it stand on it or in any way block the flow of fresh air to appliance UNDER NO CIRCUMSTANCES may flammable materials such as gasoline or paint thinner...

Page 7: ...ll soot or other obstructions from the chimney and flue which might impede draft action Replace any damaged or deteriorated parts of the venting system A qualified service technician should follow thi...

Page 8: ...e designed for indoor installation Indoor Models must be installed indoors where it is protected from exposure to wind rain and weather The appliance designed for outdoor installation Outdoor Models m...

Page 9: ...im F in Dim G in Dim H in Equivalent Length of Vent Air Intake Pipes at Recommended Diameter in Water Conn at Boiler in NPT Gas Conn at Boiler in NPT Category IV CAT II Comb Vents Over 25 and up to 10...

Page 10: ...r adequate operation All installations must allow sufficient space for servicing the vent connections water pipe connections circulating pump bypass piping and other auxiliary equipment as well as the...

Page 11: ...to the vent terminal The weight of the venting system must not rest on the unit Adequate support of the venting system must be provided in compliance with local codes and other applicable codes All co...

Page 12: ...vertical or horizontal Outside air ducted to jacket flange Indoor Air Table 6 Required Vent and Air Inlet Diameters Equivalent Length of Vent Air Intake Pipes at Recommended Diameter Input BTU hr Cat...

Page 13: ...of the vent terminal shall be located at least 3 feet 1m above grade or above normal snow levels In all cases the appliance shall be installed in accordance with local codes 3 The TH can vent up to 10...

Page 14: ...te below a forced air inlet at any distance 4 The termination cannot terminate below grade Position the termination where vapours will not damage walls or plants or may be otherwise objectionable 5 Th...

Page 15: ...east 3 feet 1m above grade or above normal snow levels In all cases the appliance shall be installed in accordance with local codes 3 The termination MUST NOT terminate below a forced air inlet at any...

Page 16: ...liance connection Installation of a union at the appliance gas line connection is required for ease of service and removal of the gas train Install a manual main gas shutoff valve outside of the appli...

Page 17: ...rve burner response The burner should ignite promptly Flame profile should be stable see section 10 2 Visually Check Main Burner Flames Turn system off and allow burner to cool then cycle burner again...

Page 18: ...e burner Airborne contaminants such as dust dirt concrete dust or dry wall dust can be drawn into the burner with the combustion air and block the burner surface area DO NOT operate this appliance dur...

Page 19: ...nt number of straight feet of pipe for each valve and fitting in the connecting piping must be considered to properly arrive at the total equivalent feet of straight pipe in the field installed piping...

Page 20: ...m 120VAC 60Hz single phase 15A circuit is required for the TH models TH 082 through TH 502 The appliance when installed must be electrically grounded in accordance with the requirements of the authori...

Page 21: ...fault is corrected the boiler will automatically return to normal operating state 5 4 ERROR TABLE The following tables provide a description of all the possible errors with the TH boiler Errors can be...

Page 22: ...circulate until the pump overrun timer is satisfied Frost Protection To prevent freezing of the heat exchanger the on board pump is turned on if the DHW temperature is below 45 o F The on board pump...

Page 23: ...te of the appliance 7 4 GAS VALVE Figure 19 Venturi and Gas Valve Arrangement The Gas Valve supplied with the TH is a combined valve venturi assembly A servo pressure regulator is incorporated into th...

Page 24: ...text on the LCD will be shown for 2 seconds followed by the software version number for an additional 2 seconds The Version relates to the version of software uploaded onto the boiler control The disp...

Page 25: ...a Temperature Display delta T temperature Outlet Temperature Inlet Temperature DHW Temperature Display DHW temperature When UP DOWN is pressed this allows the DHW setpoint temperature to be changed Ra...

Page 26: ...degrees Fahrenheit or degrees Celcius Range o F o C LBTHODLOD not used LBT Low Boiler Reset Temperature Range Off On 32 to 230 o F 0 110 o C Default Off HOD High Outdoor Reset Temperature Range Off O...

Page 27: ...ot require manual intervention The last received alert code is displayed in User mode To clear the alert code press the Reset button Refer to Table 13 in Section 5 4 2 for more details Alerts are auto...

Page 28: ...emperature display After 5 minutes of inactivity or when the Done button is pressed the TH returns to normal operation Maximum Firing Rate Max icon is flashing and the Diag icon is solid The heater wi...

Page 29: ...use of the boiler User Access to general boiler and display settings and adjustments to the central heating and domestic hot water setpoint Installer Access to all user parameters and allows for chang...

Page 30: ...er operation DHW Pump Pump C Additional contact rated for 1 6hp Sequence of Operation Pump A is energized on DHW Interlock Flow switch LWCO if equipped Blocked flue switch N C Low gas switch 4 5 w c N...

Page 31: ...CAL 2 Press and select Login 3 Select Advanced Setup 4 Select DHW Config Inlet Sensor operation 5 Select Demand switch Sensor only and Press 6 Select Mod sensor Inlet and Press go to step 7 DHW Stat o...

Page 32: ...es in LOCAL 2 Press and select Login 3 Select Advanced Setup 4 Select Burner Control Ignition 5 Select Adjustable lightoff rate and enter desired lightoff rate using 5 way control and press Adjust sta...

Page 33: ...iption Programming Instructions To view burner run time pump cycles for maintenance and service purposes 1 Place both toggle switches in LOCAL 2 Press and select Login 3 Select Advanced Setup 4 Select...

Page 34: ...ontrol Panel will be required to restart the ignition sequence The boiler has failed to ignite the burner after 5 unsuccessful attempts Verify that all air has been purged from gas line Inspect spark...

Page 35: ...ler if necessary Noisy Operation Supply Gas Issue Refer to Part 3 Gas Connection in this manual Natural Gas Pressure should read between 3 w c and 14 w c L P Gas Pressure should be at 11 w c Air Gas M...

Page 36: ...ceeded the maximum temperature allowed Measure the resistance of the flue sensor at room temperature it should be approximately 10k The supply outlet temperature has exceeded the setpoint temperature...

Page 37: ...turn at a time NO Verify gas valve is being powered by ignition control Check ignition speed is between 2500 to 3000 RPM using System Monitor NO Adjust ignition speed to 3000 RPM YES YES Burner light...

Page 38: ...tripped optional To identify the safety that is open set the multimeter to Vac and measure the voltage from one contact to ground The contacts produce a 24Vac when the circuit is closed Is vent and o...

Page 39: ...to ground The contacts produce a 24Vac when the circuit is closed Is pump powered NO Check pump wiring and pump delay relay YES Use meter to verify amperage draw on pump and verify it with rating labe...

Page 40: ...150 o F is selected and PVC venting is used the setpoint must be reduced to below 150 o F to avoid nuisance flame failures If a setpoint greater than 150 o F is required venting with CPVC AL29 4C 316...

Page 41: ...rod Is Flame sensor plug secure NO Fasten flame sensor plug securely to flame sensor wire and check for corrosion deposits at wire terminals YES Check continuity of flame sensor wire from flame sensor...

Page 42: ...Figure 25 Venturi Gas Valve Assembly To adjust the high fire setting on standard display Press and hold the Next button for 3 seconds to enter the diagnostic menu on the TH Control Panel Press Next u...

Page 43: ...ollowing screen appears Figure 30 Low Fire Adjustment Screen To return to normal operation press Done To adjust the low fire setting on the upgraded display 1 Press the button 2 Select Test and press...

Page 44: ...NINGS in this manual are complied with To service or adjust this appliance it is imperative that the serviceman utilize a combustion analyzer to read CO2 and CO according to Camus Hydronics recommenda...

Page 45: ...NOTE All gaskets on disassembled components must be replaced with new gaskets sealant on re assembly if required Gasket kits are available from the factory CAUTION When the vent system is disconnecte...

Page 46: ...o the fan inlet Disconnect the fan motor power wires at the harness Remove the direct spark igniter and the flame sensor Remove the three 3 T 25 screws holding the front burner flange in place to gain...

Page 47: ...supplied to 24VAC components may cause operational problems 10 11 COMBUSTIBLE MATERIALS CAUTION Keep appliance clear from combustible materials do not store GASOLINE and other flammable vapors and liq...

Page 48: ...h fresh water until the water begins to flow out of drain 5 Re install the lid and hold down screw on the condensate collection box WARNING The condensate collection box must be filled with water to p...

Page 49: ...ater on and allow time for the temperature to stabilize Check the temperature rise when the burner is firing at 100 of rated input 4 Compare the temperature rise on the Control Panel with the required...

Page 50: ...46 11 9 IGNITION CYCLE The ignition cycle is shown in the table below The values are the default factory settings Figure 36 TH Ignition Cycle...

Page 51: ...Figure 37 Dedicated DHW Suggested Piping Arrangement Figure 38 Combination Application Suggested Piping Arrangement Note Cold water piping should be below hot water connections to prevent heat migrat...

Page 52: ...48 PART 13 EXPLODED VIEW PARTS LIST...

Page 53: ...Air Inlet Adapter 14 0379 X X X X X X X 44 0009 X 9 Transition Arm GM20 70 020 01 X X X X X X X GM10 15 997 03 10 Venturi 459000 444 003 X X 459000 444 001 X 459000 446 051 X X 45900450 010 X X VMU30...

Page 54: ...X X X X 32 HX Support 14 5632 X X X 14 5612 X X 33 Flame Sensor GM10 35 109 01 X 34 Igniter GM10 35 108 01 X 35 Current Transformer MCSS A U X 36 Right Bracket 14 5513 20 25 X 37 Left Bracket 14 5410...

Page 55: ...r X 53 Metal Latch 6521 00 0551 YT X 54 Strike 7800 02 55 On Off Switch C6000ALBBCHLI X 56 Standard Display S7910B1006 X 57 Upgraded Display DSP49G2094 X 58 Gas Valve Relay T9CP1A54 24 X 59 TH Wire Ha...

Page 56: ...52 PART 14 ELECTRICAL DIAGRAMS 14 1 TH 82 502 INTERNALWIRING DIAGRAM...

Page 57: ...nd 2 Display Data Receive 3 Display Common J4 24VAC Power 1 9 Not Used 10 24VAC 11 Not Used 12 Ground J5 Gas Valve Safety String 1 Safety String Return 2 Gas Valve 24VAC 3 7 Not Used J6 Safety Annunci...

Page 58: ...d appliance temperature or operating at temperatures exceeding 210o F BURNER If within FIVE years after initial installation of the appliance a burner shall prove upon examination by Camus to be defec...

Page 59: ...uilt water heaters and heating boilers as well as a into every single unit For more information supplier of specialty HVAC products Our service line is open 24 hours 7 days a week on our innovative pr...

Reviews: