Head Loss and Flow Vs Temperature Rise
20 °F
30 °F
35 °F
Model
USGPM
∆
P ft.
USGPM
∆
P ft.
USGPM
∆
P ft.
800 66.6 2.8 44.4 1.1 38.0 0.8
1000 83.3 4.9 55.5 2.0 47.6 1.5
1200
100.0 6.9 66.7 3.1 57.1 2.4
1400 *
* 77.8 4.3 66.7 3.4
1600 *
* 88.9 5.4 76.2 4.0
1800 * * 100.0
6.9 85.7 5.1
2000
* * * *
95.2
6.2
*
Contact factory for recommendations
Table 3
Figure 4
If the boiler is installed above radiation level, it must be provided with a low water cutoff device
at the time of boiler installation. (Available from factory)
A pressure relief valve is supplied with each MicoFlame series 2 boiler. The relief valve must be
piped to the floor in a manner acceptable to the enforcing authority.
To eliminate trapped air, install venting devices at high points in the system as well as in the
piping on the suction of the pump and in the piping on the discharge of the boiler.
Suitable pipe hangers must support the weight of all water and gas piping or floor stands.