background image

 

10

 

7.4 

 FILTER KIT 

 
A louvered rear panel is the standard air inlet configuration for the MicoFlame series 2. A filter 
kit is available. The filter is washable and accounts for an additional pressure loss of less than 
0.05” W.C. Highly recommended for dusty environments.  
 
The filter kit can also be provided when using the outdoor air kit. 
 

7.5 

 STANDARD VENTING 

 
The MicoFlame series 2 is a category 1 appliance and is approved for venting into a common 
standard chimney. If chimney height is much greater than 30 feet or if drafts are excessive, it 
may be preferable to provide a single acting barometric damper directly above the vent collar. 
This damper will ensure smooth light off and minimize standby loss through the boiler. Be sure 
to position the damper at least 6 “ away from the wall of the vent connector. 
 

7.6 

 VENTING FOR CONDENSING APPLICATION 

 
When supplied with the optional condensing cartridge, the MicoFlame series 2 is 95% efficient 
(category II or IV appliance) which requires the use of special venting system.  Refer to 
installation instruction No. 93-0152-1. Only venting components listed by a nationally recognized 
testing agency may be used. 

8.     RELIEF VALVE 

 
A pressure relief valve is supplied as standard equipment. The relief valve protects against 
damage that could be caused by malfunctioning controls or excessive water pressure. If a relief 
valve is not used, warranty is void. 
 
The relief valve is to be located as near as practical to the outlet of the boiler. To maintain 
capacity do not reduce the inlet connection of the relief valve. Connect the outlet of the relief 
valve to a suitable drain. The drainpipe must point down from the valve and must not be smaller 
than the outlet of the valve. The end of the drain line should not be concealed or threaded and 
should be protected against freezing. No valve of any kind should be installed between the relief 
valve and the unit or in the drain line. Extensive runs, traps or bends could reduce the capacity 
of the valve. This valve should be checked for proper operation at least once a year by a 
qualified service technician. 

9.     FREEZE PROTECTION 

 
Boiler installations are not recommended in areas where the danger of freezing exists unless 
precautions are taken. Maintaining a mixture of 50% water and 50% propylene glycol is the 
preferred method of freeze protection in hydronic systems. This mixture will protect the boiler to 
approximately -35 

°

F (-37 

°

C). To maintain the same temperature rise across the boiler 

increase the G.P.M. flow by 15% and the head loss by 20%.  
 
A snow screen should be installed to prevent snow and ice accumulation around the boiler. 
Regular inspections should be made to ensure that air intake and vent are free of snow and ice.  

Summary of Contents for MICOFLAME 2 Series

Page 1: ...r appliance WHAT TO DO IF YOU SMELL GAS o Do not try to light any appliance o Do not touch any electrical switch do not use any phone in your building o Immediately call your gas supplier from a neigh...

Page 2: ...8 RELIEF VALVE 10 9 FREEZE PROTECTION 10 10 WARNING REGARDING CHILLED WATER SYSTEMS 11 11 PIPING OF SYSTEM TO BOILER FIG 4 11 12 PLACING BOILER IN OPERATION 13 13 IGNITION SYSTEM SAFETY SHUT OFF DEVI...

Page 3: ...ty having jurisdiction the installation must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers ANSI ASME CSD 1 The qualified installer shall instruct the end user...

Page 4: ...installed above the level of the building s radiation system a low water cutoff device must be installed in the boiler outlet at the time of installation Some local codes require the installation of a...

Page 5: ...tion leading to reversal of the natural draft action of the venting system Under these circumstances an engineered air supply is necessary If the heater is to be installed near a corrosive or potentia...

Page 6: ...fans must be running in order for the appliance to proceed to trial for ignition MicoFlame series 2 is supplied with more than one burner may use burners that are not of identical size in order to acc...

Page 7: ...to operate at inlet gas pressures not exceeding PSI 14 W C If higher pressures are present consult the gas company for correction When pressure testing the gas supply piping at pressures above PSI th...

Page 8: ...upported approximately every 4 feet to prevent sagging and maintain a minimum upward slope of per foot from the boiler to the vent terminal When an existing boiler is removed from a common venting sys...

Page 9: ...structions from the chimney and flue which might impede draft action Replace any damaged or deteriorated parts of the venting system A qualified service technician should follow this procedure when in...

Page 10: ...efficient and is considered to be a category II or IV appliance Three venting options are available for this boiler in both condensing and non condensing configurations See Figure 2 for details Pleas...

Page 11: ...ACNA AFTS 100 73 Standard When venting through unheated spaces with single wall vent insulation should be wrapped around the vent pipe to prevent flue gas condensation inside the vent Periodically che...

Page 12: ...inst damage that could be caused by malfunctioning controls or excessive water pressure If a relief valve is not used warranty is void The relief valve is to be located as near as practical to the out...

Page 13: ...tic means to prevent gravity circulation of chilled water through the boiler Chilled water in the boiler will create condensate on the boiler tubes which will collect in the combustion chamber causing...

Page 14: ...radiation level it must be provided with a low water cutoff device at the time of boiler installation Available from factory A pressure relief valve is supplied with each MicoFlame series 2 boiler Th...

Page 15: ...ance filled with air Start up boiler following instructions provided Operate entire system including pumps and radiation for at least 1 hour Check water level in expansion tank If level exceeds of tan...

Page 16: ...he inlet temperature is greater than 110 F but not greater than 140 F no further adjustment is required e Check the inlet temperature after 5 minutes and make final adjustments 15 INSTANTANEOUS WATER...

Page 17: ...t burner every six months for proper flame characteristics 16 1 MAIN BURNER The main burner figure 7 should display the following characteristics Acceptable CO and CO2 levels for complete combustion L...

Page 18: ...1 6 1 9 1 6 1 9 1 2 1 6 1 2 1 6 2000 1 9 2 2 1 9 2 2 1 5 1 9 1 5 1 9 Depending on field conditions air box pressures will have to be adjusted accordingly Always set the appliance for a CO2 level in th...

Page 19: ...e electrode does not appear overheated or fouled with carbon It may be necessary to clean the ignition electrode using steel wool Once the pilot appears to be properly set reinstall it into the applia...

Page 20: ...ction 15 of this manual After the first season of operation inspect the heat exchanger and venting Follow the detailed instructions in section 6 of this manual CAUTION Label all wires prior to disconn...

Page 21: ...If pilot fails to light and you suspect air in the line close the main manual valve and repeat lighting steps 1 thru 5 7 Once the pilot lights it should envelope the ignition rod and ground electrode...

Page 22: ...und electrodes are positioned properly Clean with steel wool if necessary Verify that back of burner box is fully engaged into the retaining slot in the combustion chamber base 5 Pilot lights but main...

Page 23: ...ICAL DIAGRAMS Each MicoFlame series 2 boiler will be provided with its own wiring diagram to guarantee that any options ordered with the unit are properly detailed The following diagram 99 5072 and 99...

Page 24: ...22...

Page 25: ...23...

Page 26: ...24 22 EXPLODED VIEW...

Page 27: ...25 23 MICO FLAME REPLACEMENT PARTS LIST...

Page 28: ...standard warranty 2 Years six through ten replacement purchase price pro rated at the following schedule Year six 60 Year seven 65 Year eight 70 Year nine 75 Year ten 80 of the current list price of t...

Page 29: ...t water heaters and heating boilers as well as a into every single unit For more information supplier of specialty HVAC products Our service line is open 24 hours 7 days a week on our innovative produ...

Reviews: