Camille Bauer SINEAX V604s Operating Instructions Manual Download Page 9

Camille Bauer 

Operating instructions V604s Be 

9

Bytes

Modbus does not know a byte or character data type (see 
address space). Strings or byte arrays are mapped in "hold-
ing registers“ (2 characters per register) and transmitted as 
a "character stream", e.g. "Hello_World“.

Register

HEX

char

Register

HEX

char

40101

Ox4865

‚H’ ‚e’

40104

0x576F

‚W’ ‚o’

40102

Ox6C6C

‚l’

‚l’

40105

0x726C

‚r’

‚l’

40103

Ox6F5F

‚o’ ‚_’

40106

0x6400

‚d’

Words

Registers or words are transmitted according to specifi cation 
in "Big Endian“ format, e.g. Read Holding Register 40101 
of Slave 17.

Real

Modbus does not know any data types to represent fl oat-
ing point numbers. On principle, any data structures may 
be mapped  on the 16Bit register ("cast“). The IEEE 754 
standard is the most used standard to represent fl oating 
point numbers.

M M

M

M

M

M

M

M

M

M

E

E

E

E

E

E

E

E

V

M M M M M M M M M M M M M M

0

16 15

8

7

24

31

Exponent

Mantissa

Algebraic sign

Bit

23

The fi rst register contains Bits 15 – 0 of the 32-bit number 
(bit 0…15 of the mantissa).

The second register contains Bits 16 – 32 of the 32-bit number 
(algebraic sign, exponent and Bit 16- 22 of the mantissa).

6.3 Mapping

Address space

The address space may be divided into 4 address spaces 
according to the 4 types of data.

Space

r/w

Address area

Function code

Coil 

Readable
Writeable

00001 - 09999

0x01
0x05
0x0F

Read Coil Status 

1)

Force Single Coil 

1)

Force Multiple Coils 

1)

Discrete  input

Only reada-
ble

10001 - 19999

0x02

Read Input Status 

1)

Input  register

Only reada-
ble

30001 - 39999

0x04

Read Input Register 

1)

Holding 
register 

Readable
Writeable

40001 - 49999

0x03
0x06
0x10

Read Holding 
Registers
Force Single 
Register 

1)

Preset Multiple 
Registers

1)

 not implemented

To reduce the commands, the device image was represented 
as far as possible in "holding registers".

Segments

Address

Description

Permitted function codes

40209 - 40210
40257 - 40284
40515 - 40516
40517 - 40761

Actions
Measured values, status
Settings (Modbus)
Confi guration data

0x03
0x10

Read Holding Registers
Preset Multiple Regi-
sters

41076

Device type

0x03

Read Holding Registers

Syntax

Address

Start address of the described data block (register, coil 
or input status)

Description

Unique variable or structure description

Data  type

Data type of variable (U: unsigned, INT: integer, 8/16/32 
bit, REAL or CHAR[..])

#

Offset from the start address in the data type unit, for 
Byte 0: Low, 1: High byte

Default

Value upon derlivery or after a hardware reset

Description

Exact details concerning the variable described

6.4 Device identifi cation

The device is identifi ed by "Read Slave ID“.

Function 11h: Report Slave ID

Master telegram:

Device
address

Function

CRC

ADDR

0x11

LO

HI

Slave telegram:

Device
Address

Function

Number 

data bytes

Slave

ID

Sub

ID

Data

2

CRC

ADDR

0x11

3

LO

HI

Device
ID

Sub-ID

Device

Description

0x01

0x00

VR660

Temperature controller

0x02

0x00

A200R

Display

0x03

0x01

CAM

Universal measuring unit for heavy current 
variables

0x04

0x00 APLUS 

Multifunctional 

display

0x05

0x00

V604s

Universal transmitter

0x05

0x01

VB604s

Universal transmitter multi in/out

0x05

0x02

VC604s

Universal transmitter second Relay

0x05

0x03

VQ604s

Universal transmitter fast setting time

Device information

Adress

Description

Data type

Description 

41076

DEVICE

UINT16

Device type

Bit Description 
0  

Reserved

1  

Reserved

2  

0:  V / mA inputs

 

1:  2 x mA inputs

3-15  

Reserved 

Summary of Contents for SINEAX V604s

Page 1: ...Operating instructions SINEAX V604s Programmable multifunctional transmitter Camille Bauer AG Aargauerstrasse 7 CH 5610 Wohlen Switzerland Phone 41 56 618 21 11 Fax 41 56 618 21 21 info camillebauer...

Page 2: ...TC and resistance Sensor connection without any external jumpers 2 inputs e g for sensor redundancy or difference formation 2 outputs U and or I 2 inputs can be linked with each other and allocated t...

Page 3: ...pter COM4 The existing COM ports are determined as the communi cation interface when starting the program and selecting RS232 RS485 Only COM ports found are available for selection Limiting the range...

Page 4: ...rence junction 20 70 C Resistance measurement teletransmitter potentiometer Measuring range limits See Table 1 Wiring 2 3 or 4 wire connection Resistance teletransm Type WF and WF DIN Measuring curren...

Page 5: ...due to different sensor response times If this time is exceeded an alarm is signalled See Limit values 1 and 2 Sensor redundancy Measurement with 2 temperature sensors if Sensor 1 fails fault Sensor...

Page 6: ...egulations Electromagnetic compatibility EN 61000 6 2 61000 6 4 Ingress protection acc IEC 529 or EN 60529 Housing IP 40 terminal IP20 Electric design Acc IEC or EN 61010 Degree of pollution 2 Between...

Page 7: ...rt circuit Alarm1 Alarm delay Relay 1 LED Relay 1 LED Alarm PERCENT1 inv Output 2 PERCENT2 Value in case of a fault Output behaviour ERRVAL1 ERRVAL2 Measured variables Configuration paramerters LIMIT2...

Page 8: ...400 56 000 57 600 115 200 Baud Mode 11 bit format 2 stop bit without parity or 1 stop bit with even uneven parity 6 2 Coding and addressing Addressing In the telegram all data addresses refer to zero...

Page 9: ...x03 0x06 0x10 Read Holding Registers Force Single Register 1 Preset Multiple Registers 1 not implemented Toreducethecommands thedeviceimagewasrepresented as far as possible in holding registers Segmen...

Page 10: ...13 14 15 Reserved Reserved Device fault Parameter fault Sensor breakage Input 1 Sensor short circuit Input 1 Reserved Sensor breakage Input 2 Sensor short circuit Input 2 Reserved Alarm 1 Alarm 2 rela...

Page 11: ...ible if the settings are known The following technique resets the MODBUS settings to the delivery status Device address 01h Baudrate 19200 Parity None Stop bits 2 A plug prepared for this purpose Term...

Page 12: ...07h Sensor earthed TC internally compensated K 3 4 66h Sensor earthed TC ext cold junction thermostat K 3 4 27h Sensor earthed TC with ext Pt100 on Terminals 1 4 K 1 3 4 Wiring variant B 10h Voltage...

Page 13: ...meter correction2 40534 INPUT2 UINT8 0 FFh at 2xmA 50h Type of measurement Input 2 same as Input 1 1 FFh Sensor type Input 2 same as Input 1 40535 INPRANGE2 REAL Measuring range Input 2 same as Input...

Page 14: ...imum value Input 1 2 89h Sensor redundancy Mean value Input 1 2 Only measured variables of the same unit may be linked Product formation Only possible for combinations V mV V mA mA mA mV mA and mV mV...

Page 15: ...LIMIT2 40567 LIMIT2OFF REAL 0 0 Switching off threshold Limit value 2 unit of LIMIT2 40569 OUTSET1 UINT16 05h at VB604s 01h Output settings Output 1 Bit Description 0 1 2 3 4 5 6 7 8 15 Output limit...

Page 16: ...es Table 2 Automatic parameter correction2 40594 TAB1_YA REAL 10 0 Table 1 Y value 10 in of the measuring range 40596 TAB1_X REAL 20 0 0 Table 1 X values in of the measuring range 40636 TAB1_Y REAL 20...

Page 17: ...Maximum value Input 1 2 Max Min1 Min2 Max Max1 Max2 Mean value Input 1 2 Min1 Min2 2 Max1 Max2 2 Sensor backup Input 1 Min1 1 Max1 1 Sensor backup Input 2 Min2 1 Max2 1 Sensor backup minimum value Inp...

Page 18: ...tion thermostat or internally compen sated 7 8 3 4 Thermocouple with Pt100 at the termi nals at the same input 7 2 8 3 Pt100 1 4 Wiring with 2 input sensors If 2 input sensors or input variables are u...

Page 19: ...altung folgender Normen The above mentioned product has been manufactured according to the regulations of the fol lowing European directives proven through compliance with the following standards Nr N...

Reviews: