background image

Camille Bauer 

Operating instructions V604s Be 

5

Output settings

 

Limit
Gain/offset trimming
Inversion

Relay contact output

 

Contact 

1 pole, normally open contact

Switching capacity 

AC: 2 A / 250 V AC

 

 

DC: 2 A / 30 V

Bus/programming connection

 

Interface, protocol 

RS-485, Modbus RTU

Baudrate 

9,6...115,2 kBaud, adjustable

Transmission behaviour

Measured variables 
for the outputs 

•  Input 1
• Input 2
•  Input 1 + Input 2
•  Input 1 – Input 2
•  Input 2 – Input 1
•  Input 1  ·  Input 2
•  Minimum value, maximum   
 value
  or mean value of Input 1 
  and Input 2
• Sensor redundancy
  Input 1 or Input 2

Transmission function 

Linear,
user-specifi c via
basic value table 
(24 basic values per measured 
variable)

Settling time: 

Adjustable 1…30 s

Limit values and monitoring

Number of limit values  2
Measured variables for 
limit values 

•  Input 1
• Input 2
•  Measured variable for outputs
•  Input 1 – Input 2 
  (e.g. drift monitoring in case of 
 2 

sensors)

•  Input 2 – Input 1
  (e.g. drift monitoring in case of 
 2 

sensors)

Functions Absolute 

amount

Gradient dx/dt (e.g. temperature 
gradient monitoring)

Time delay 

Adjustable 0…3600 s

Signaling 

Relay contact, alarm LED, 
Status 1

Sensor breakage and 
short circuit monitoring measuring input

Signalling 

Relay contact, alarm LED,
Status 1
Output value in case of a fault

Other monitoring operations

Drift monitoring 

Monitoring of measured value  
between 2 input sensors for a 
certain period of time (e.g. due to 
different sensor response times).
If this time is exceeded, an alarm 
is signalled. 
(See Limit values 1 and 2)

Sensor redundancy 

Measurement with 2 temperature 
sensors; if Sensor 1 fails (fault) 
Sensor 2 is activated for bridg-
ing (see measuring variable for 
outputs).

Alarm signalling

Relay contact 

With closed contact, 
the yellow LED shines,
invertible

Alarm LED 
Time delay 

Adjustable 0…60 s

Output value 
in case of a fault 

For sensor breakage and short 
circuit, value adjustable –10…
110%

Power supply

Rated voltage UN

Tolerance

24…230 V DC *

±15%

100…230 V AC, 45…400 Hz

±15%

* In case of a power supply voltage >125 V DC, the power 
supply circuit must contain an external fuse

Power consumption 

>3 W or 7 VA

Displays at the instrument

LED

Color

Function

ON

green

Power on

green fl ashing

Communication activ

ERR

red

Alarm

yellow

Relay on

Confi guration, programming

Operation with PC software «CB-Manager»

Accuracies 

(according to EN/IEC 60770-1)

Reference conditions

Ambient temperature 

23 °C ± 2 K

Power supply 

24 V DC

Reference value 

Span

Settings 

Input 1: Direct voltage mV, 
0…1000 mV

 

 

Output 1: 4…20 mA, burden 
resistance 300 Ω

 

 

Mains frequency 50 Hz,
Setting time 1 s

 

 

Input 2, output 2, relay, monitor-
ing off or not active, for voltage 
output: range 0...10 V, burden 
resistance 2 kΩ

Installation position 

Vertically, detached

Basic accuracy

At reference conditions  ±0.1%

Other types of measurement and input ranges:

RTD Pt100, Ni100 

±0.1% ±0.2 K

Resistance measurement  ±0,1% ±0.1 Ω
TC Type K, E, J, T, N, L, U ±0.1% ±0.4 K, 

measurement value > –100 °C

TC Type R, S 

±0.1% ±2.4 K

TC Type B 

±0.1% ±2.4 K, 
measurement value > 300°C

Summary of Contents for SINEAX V604s

Page 1: ...Operating instructions SINEAX V604s Programmable multifunctional transmitter Camille Bauer AG Aargauerstrasse 7 CH 5610 Wohlen Switzerland Phone 41 56 618 21 11 Fax 41 56 618 21 21 info camillebauer...

Page 2: ...TC and resistance Sensor connection without any external jumpers 2 inputs e g for sensor redundancy or difference formation 2 outputs U and or I 2 inputs can be linked with each other and allocated t...

Page 3: ...pter COM4 The existing COM ports are determined as the communi cation interface when starting the program and selecting RS232 RS485 Only COM ports found are available for selection Limiting the range...

Page 4: ...rence junction 20 70 C Resistance measurement teletransmitter potentiometer Measuring range limits See Table 1 Wiring 2 3 or 4 wire connection Resistance teletransm Type WF and WF DIN Measuring curren...

Page 5: ...due to different sensor response times If this time is exceeded an alarm is signalled See Limit values 1 and 2 Sensor redundancy Measurement with 2 temperature sensors if Sensor 1 fails fault Sensor...

Page 6: ...egulations Electromagnetic compatibility EN 61000 6 2 61000 6 4 Ingress protection acc IEC 529 or EN 60529 Housing IP 40 terminal IP20 Electric design Acc IEC or EN 61010 Degree of pollution 2 Between...

Page 7: ...rt circuit Alarm1 Alarm delay Relay 1 LED Relay 1 LED Alarm PERCENT1 inv Output 2 PERCENT2 Value in case of a fault Output behaviour ERRVAL1 ERRVAL2 Measured variables Configuration paramerters LIMIT2...

Page 8: ...400 56 000 57 600 115 200 Baud Mode 11 bit format 2 stop bit without parity or 1 stop bit with even uneven parity 6 2 Coding and addressing Addressing In the telegram all data addresses refer to zero...

Page 9: ...x03 0x06 0x10 Read Holding Registers Force Single Register 1 Preset Multiple Registers 1 not implemented Toreducethecommands thedeviceimagewasrepresented as far as possible in holding registers Segmen...

Page 10: ...13 14 15 Reserved Reserved Device fault Parameter fault Sensor breakage Input 1 Sensor short circuit Input 1 Reserved Sensor breakage Input 2 Sensor short circuit Input 2 Reserved Alarm 1 Alarm 2 rela...

Page 11: ...ible if the settings are known The following technique resets the MODBUS settings to the delivery status Device address 01h Baudrate 19200 Parity None Stop bits 2 A plug prepared for this purpose Term...

Page 12: ...07h Sensor earthed TC internally compensated K 3 4 66h Sensor earthed TC ext cold junction thermostat K 3 4 27h Sensor earthed TC with ext Pt100 on Terminals 1 4 K 1 3 4 Wiring variant B 10h Voltage...

Page 13: ...meter correction2 40534 INPUT2 UINT8 0 FFh at 2xmA 50h Type of measurement Input 2 same as Input 1 1 FFh Sensor type Input 2 same as Input 1 40535 INPRANGE2 REAL Measuring range Input 2 same as Input...

Page 14: ...imum value Input 1 2 89h Sensor redundancy Mean value Input 1 2 Only measured variables of the same unit may be linked Product formation Only possible for combinations V mV V mA mA mA mV mA and mV mV...

Page 15: ...LIMIT2 40567 LIMIT2OFF REAL 0 0 Switching off threshold Limit value 2 unit of LIMIT2 40569 OUTSET1 UINT16 05h at VB604s 01h Output settings Output 1 Bit Description 0 1 2 3 4 5 6 7 8 15 Output limit...

Page 16: ...es Table 2 Automatic parameter correction2 40594 TAB1_YA REAL 10 0 Table 1 Y value 10 in of the measuring range 40596 TAB1_X REAL 20 0 0 Table 1 X values in of the measuring range 40636 TAB1_Y REAL 20...

Page 17: ...Maximum value Input 1 2 Max Min1 Min2 Max Max1 Max2 Mean value Input 1 2 Min1 Min2 2 Max1 Max2 2 Sensor backup Input 1 Min1 1 Max1 1 Sensor backup Input 2 Min2 1 Max2 1 Sensor backup minimum value Inp...

Page 18: ...tion thermostat or internally compen sated 7 8 3 4 Thermocouple with Pt100 at the termi nals at the same input 7 2 8 3 Pt100 1 4 Wiring with 2 input sensors If 2 input sensors or input variables are u...

Page 19: ...altung folgender Normen The above mentioned product has been manufactured according to the regulations of the fol lowing European directives proven through compliance with the following standards Nr N...

Reviews: