13
Address
Description
Data type
#
Default
Description
40524
INPRANGE1
REAL
Measuring range Input 1
Variable
Range
Minimum span
U[mV]:
±0 mV … 1000 mV
2 mV
U[V]:
±0 V … 300 V
1 V
RTD:
Acc. sensor limits
TC:
Acc. sensor limits
R:
0 … 5000 [Ω]
see special case WF, WFDIN *
8 Ohm
I [mA]:
±0 … 50 mA
0.2 mA
Automatic parameter correction
2
0
0.0
at 2xmA:
4.0
Measuring range start
1
1000.0
at 2xmA:
20.0
Measuring range end
40528
SCALE1
REAL
1.0
Scaling factor for INPUT1 (larger than 0.0)
40530
SENSVAL1
REAL
100.0
Input 1: Sensor value [Ω] at 0°C (e.g. 100.0 for Pt100)
Pt20 … Pt1000
Ni50 … Ni1000
WF, WFDIN: SENSVAL1=Rd
Automatic parameter correction
2
40532
REF1
REAL
0.0
Reference value Input 1:
– Line resistance [Ω] in 2-wire measurement: 0…30 Ohm
– Reference temperature in TC ext. comp.: -20 … 70 °C
Automatic parameter correction
2
40534
INPUT2
UINT8
0
FFh
at 2xmA:
50h
Type of measurement Input 2 (same as Input 1)
1
FFh
Sensor type Input 2 (same as Input 1)
40535
INPRANGE2
REAL
Measuring range Input 2 (same as Input 1)
0
0.0
at 2xmA:
4.0
Measuring range start
1
1000.0
at 2xmA:
20.0
Measuring range end
40539
SCALE2
REAL
1.0
Scaling factor for INPUT2 (larger than 0.0)
40541
SENSVAL2
REAL
100.0
Input 2: Sensor value [Ω] at 0°C (e.g. 100.0 for Pt100)
Pt20 … Pt1000
Ni50 … Ni1000
WF, WFDIN: SENSVAL1=Rd
Automatic parameter correction
2
40543
REF2
REAL
0.0
Reference value Input 2:
– Line resistance [Ω] in 2-wire measurement: 0 … 30 Ohm
– Reference temperature [°C] in TC ext. comp.: -20 … 70 °C
40545
FREQ
REAL
50.0
System frequency [Hz]: 10 … 100 Hz
Automatic parameter correction
2
Parameter
Meaning
INPRANGE1, measuring range start
Ra
INPRANGE1, measuring range end
Re
SENSVAL1
Rd
* Resistance teletransmitter
For teletransmitters the measuring range is defi ned by 3 resistance values
Input 2: Same as Input 1.
7
2
8
3
Ra
Rd
0%
100%
Re
1
4
8
2
7
4
Ra
Rd
0%
100%
Re
1
3