Operating instructions V604s Be 

Camille Bauer

Limitations of confi guration parameters

Options to combine types of measurement

Register: 40523, 40534

The numerous types of measurement can be combined with 
each other in different ways.

See Table 3 page 19

The "earthed" combination is used if both sensors are 
connected to each other.

Measuring ranges

Register: 40524, 40535

see table 1 / page 4

Address

Description

Data  type

#

Default

Description

40580

OUTSET2

UINT16

05h, 
at VB604s 
01h

Output settings Output 2 (same as Output 1)

40581

OUTRANGE2

REAL

Output range Output 2

0

4.0

Minimum value 

–20…20 [mA] / –10…10 [V]

1

20.0

Maximum value 

–20…20 [mA] / –10…10 [V]

40585

TRIM2

REAL

Output trimming Output 2

0

0.0

Offset trimming
[in % of the output range, setting range +/– 10%]

1

1

100.0

Gain trimming
[in % of the output range, setting range 90…110%]

1

40589

ERRVAL2

REAL

0.0

Output value Output 2 in case of a fault
[in % of the output range, setting range -10…+110%)

1

40591

GRAD_TIME

REAL

1.0

Time span between two measured values for gradient calculation of limit values in seconds
Range: 4 x TSET … 26210 s

Automatic parameter correction

2

40593

NUMTAB

UINT8

Number of table values

0

0

Number of table values Table 1

Automatic parameter correction

2

1

0

Number of table values Table 2

Automatic parameter correction

2

40594

TAB1_YA

REAL

-10.0

Table 1: Y-value (-10%) in % of the measuring range

40596

TAB1_X

REAL[20]

0.0

Table 1: X-values in % of the measuring range

40636

TAB1_Y

REAL[20]

0.0

Table 1: Y-values in % of the measuring range

40676

TAB1_YE

REAL

110.0

Table 1: Y-value (110%) in % of the measuring range

40678

TAB2_YA

REAL

-10.0

Tabelle 1: Y-Wert (-10%) in % vom Messbereich

40680

TAB2_X

REAL[20]

0.0

Tabelle 1: X-Werte in % vom Messbereich

40720

TAB2_Y

REAL[20]

0.0

Tabelle 1: Y-Werte in % vom Messbereich

40760

TAB2_YE

REAL

110.0

Tabelle 1: Y-Wert (110%) in % vom Messbereich

1

  Max. +/-22 mA or +/-11 V

2

  Automatic correction of parameters in the device.

  Each parameter must range within permitted limits. These partly depend on other parameters.
  If parameters determining the limits of dependent parameters are changed,
  (e.g. measuring range is dependent on the type of measurement), the respective parameters are automatically limited to the permitted parameters. The status will show that such a
  correction has taken place.

Due to linking and scaling, the measuring ranges are rescaled 
to different ranges.

This is automatically realised in the device.

Abbreviations:

k

1

: SCALE1

k

2

: SCALE2

T

1a

…T

1e

  INPRANGE1 

Min1 = T

1a

 * k

1

 

Max1 = T

1e

 * k

1

T

2a

…T

2e

  INPRANGE2 

Min2 = T

2a

 * k

2

 

Max2 = T

2e

 * k

2

Matrix

Minimum value
MEAS1

Maximum value
MEAS1

Input 1

Min1

Max1

Input 2

Min2

Max2

Input 1 + 2

Min1 + Min2

Max1 + Max2

Input 1 - 2

Min1 – Max2

Max1 – Min2

Input 2 - 1

Min2 – Max1

Max2 – Min1

Summary of Contents for SINEAX V604s

Page 1: ...Operating instructions SINEAX V604s Programmable multifunctional transmitter Camille Bauer AG Aargauerstrasse 7 CH 5610 Wohlen Switzerland Phone 41 56 618 21 11 Fax 41 56 618 21 21 info camillebauer...

Page 2: ...TC and resistance Sensor connection without any external jumpers 2 inputs e g for sensor redundancy or difference formation 2 outputs U and or I 2 inputs can be linked with each other and allocated t...

Page 3: ...pter COM4 The existing COM ports are determined as the communi cation interface when starting the program and selecting RS232 RS485 Only COM ports found are available for selection Limiting the range...

Page 4: ...rence junction 20 70 C Resistance measurement teletransmitter potentiometer Measuring range limits See Table 1 Wiring 2 3 or 4 wire connection Resistance teletransm Type WF and WF DIN Measuring curren...

Page 5: ...due to different sensor response times If this time is exceeded an alarm is signalled See Limit values 1 and 2 Sensor redundancy Measurement with 2 temperature sensors if Sensor 1 fails fault Sensor...

Page 6: ...egulations Electromagnetic compatibility EN 61000 6 2 61000 6 4 Ingress protection acc IEC 529 or EN 60529 Housing IP 40 terminal IP20 Electric design Acc IEC or EN 61010 Degree of pollution 2 Between...

Page 7: ...rt circuit Alarm1 Alarm delay Relay 1 LED Relay 1 LED Alarm PERCENT1 inv Output 2 PERCENT2 Value in case of a fault Output behaviour ERRVAL1 ERRVAL2 Measured variables Configuration paramerters LIMIT2...

Page 8: ...400 56 000 57 600 115 200 Baud Mode 11 bit format 2 stop bit without parity or 1 stop bit with even uneven parity 6 2 Coding and addressing Addressing In the telegram all data addresses refer to zero...

Page 9: ...x03 0x06 0x10 Read Holding Registers Force Single Register 1 Preset Multiple Registers 1 not implemented Toreducethecommands thedeviceimagewasrepresented as far as possible in holding registers Segmen...

Page 10: ...13 14 15 Reserved Reserved Device fault Parameter fault Sensor breakage Input 1 Sensor short circuit Input 1 Reserved Sensor breakage Input 2 Sensor short circuit Input 2 Reserved Alarm 1 Alarm 2 rela...

Page 11: ...ible if the settings are known The following technique resets the MODBUS settings to the delivery status Device address 01h Baudrate 19200 Parity None Stop bits 2 A plug prepared for this purpose Term...

Page 12: ...07h Sensor earthed TC internally compensated K 3 4 66h Sensor earthed TC ext cold junction thermostat K 3 4 27h Sensor earthed TC with ext Pt100 on Terminals 1 4 K 1 3 4 Wiring variant B 10h Voltage...

Page 13: ...meter correction2 40534 INPUT2 UINT8 0 FFh at 2xmA 50h Type of measurement Input 2 same as Input 1 1 FFh Sensor type Input 2 same as Input 1 40535 INPRANGE2 REAL Measuring range Input 2 same as Input...

Page 14: ...imum value Input 1 2 89h Sensor redundancy Mean value Input 1 2 Only measured variables of the same unit may be linked Product formation Only possible for combinations V mV V mA mA mA mV mA and mV mV...

Page 15: ...LIMIT2 40567 LIMIT2OFF REAL 0 0 Switching off threshold Limit value 2 unit of LIMIT2 40569 OUTSET1 UINT16 05h at VB604s 01h Output settings Output 1 Bit Description 0 1 2 3 4 5 6 7 8 15 Output limit...

Page 16: ...es Table 2 Automatic parameter correction2 40594 TAB1_YA REAL 10 0 Table 1 Y value 10 in of the measuring range 40596 TAB1_X REAL 20 0 0 Table 1 X values in of the measuring range 40636 TAB1_Y REAL 20...

Page 17: ...Maximum value Input 1 2 Max Min1 Min2 Max Max1 Max2 Mean value Input 1 2 Min1 Min2 2 Max1 Max2 2 Sensor backup Input 1 Min1 1 Max1 1 Sensor backup Input 2 Min2 1 Max2 1 Sensor backup minimum value Inp...

Page 18: ...tion thermostat or internally compen sated 7 8 3 4 Thermocouple with Pt100 at the termi nals at the same input 7 2 8 3 Pt100 1 4 Wiring with 2 input sensors If 2 input sensors or input variables are u...

Page 19: ...altung folgender Normen The above mentioned product has been manufactured according to the regulations of the fol lowing European directives proven through compliance with the following standards Nr N...

Reviews: