LEFM 200 Modbus User Manual
IB0147 Rev. 8
December 2010
Page 11
Section 2
Using the above coefficients, the transmitter does a linear scale:
Analog Input (engineering units) = Y1 +(Analog Input-X1)*(Y2-Y1)/(X2-X1)
For example, for a 100
RTD (-100 to 100°C), 0 volts represent -100°C and 5 volts represents
100°C.
Holding Register Address
Variable Description
Name
Meter Body
Temp Input1
Pressure
Input 2
Fluid Temp
Input 3*
Density
Input 4*
Minimum Voltage for Inputs
X1(j)
104
112
120
128
Minimum Engineering Value at
Minimum Voltage
Y1(j)
106
114
122
130
Maximum Voltage for Inputs
X2(j)
108
116
124
132
Maximum Engineering Value at
Maximum Voltage
Y2(j)
110
118
126
134
Setup Variable
Holding Register
Variable
Definition
Address
Note
Meter Body Temp
Float
1170
Use these registers to override the Analog
Inputs with values from the Flow Computer
or Plant Computer
Fluid Pressure
Float
1172
Fluid Temperature
Float
1174
Density
Float
1176