IB0147 Rev. 08
LEFM 200 Modbus User Manual
Section 2
Page 14
December 2010
Default Outputs
Output 1 Flow,
Output 2 VOS (sound velocity),
Output 3 Temperature,
Output 4 Density
The default output units are as follows:
Flow – based on units conversion and time units conversion
VOS (Sound velocity) is units of velocity – in/s or m/s
Temperature is °F or °C
Relative Density in Density Units
The outputs can also be mapped to any Modbus Input Register by putting that register value into
AnalogOutputMap register, 1124 to 1127. The units are then the units of that register and the
scaling must be adjusted accordingly.
Setup Variable Holding
Register
Variable
Definition
Address
Note
AnalogOutputMap1
Integer
1124
0 = Use Default Output Values
Use Modbus Input Register Value to
Output the Value of that Register.
AnalogOutputMap2
Integer
1125
AnalogOutputMap3
Integer
1126
AnalogOutputMap4
Integer
1127
The following table defines addresses for the Analog Output setups. The variables are entered as
Floats, however, the counts values are limited to integers. The equation used is as follows:
Analog Output(i) (counts) = B1 +(Output(i)-A1)*(B2-B1)/(A2-A1)
Where:
65535 is full scale (i.e., 20 mA for a 4-20 mA output)
0 is minimum scale (i.e., 4 mA for a 4-20 mA output)
For Ci Units there is only one (1) analog output and the full scale counts are configured at the
factory.
Holding Register Address
Variable Description
Name
Output1
Output 2
Output 3
Output 4
Minimum Engineering Value
A1(j)
136
144
152
160
Minimum Count Value
B1(j)
138
146
154
162
Maximum Engineering Value
A2(j)
140
148
156
164
Maximum Count Value
B2(j)
142
150
158
166
Summary of Contents for LEFM 200
Page 4: ...IB0147 Rev 08 LEFM 200 Modbus User Manual Table of Contents Page ii December 2010 ...
Page 22: ...IB0147 Rev 08 LEFM 200 Modbus User Manual Section 2 Page 18 December 2010 ...
Page 28: ...IB0147 Rev 08 LEFM 200 Modbus User Manual Section 3 Page 24 December 2010 ...
Page 40: ...IB0147 Rev 08 LEFM 200 Modbus User Manual Section 4 Page 36 December 2010 ...